Adobe construction shall comply with this section and shall
be subject to the requirements of this code for Type V construction, Chapter 5
of TMS 402/ACI 530/ASCE 5, and this section.
2109.3.1
Unstabilized adobe.
2109.3.1.1
Compressive strength.
Adobe units shall have an average compressive strength of 300 psi (2068 kPa)
when tested in accordance with ASTM C 67. Five samples shall be tested and no
individual unit is permitted to have a compressive strength of less than 250
psi (1724 kPa).
2109.3.1.2
Modulus of rupture. Adobe units shall have an average modulus of
rupture of 50 psi (345 kPa) when tested in accordance with the following
procedure. Five samples shall be tested and no individual unit shall have a
modulus of rupture of less than 35 psi (241 kPa).
2109.3.1.2.1
Support conditions.
A cured unit shall be simply supported by 2-inch-diameter (51 mm) cylindrical
supports located 2 inches (51 mm) in from each end and extending the full width
of the unit.
2109.3.1.2.2
Loading conditions. A 2-inch-diameter (51 mm) cylinder shall be
placed at midspan parallel to the supports.
2109.3.1.2.3
Testing procedure.
A vertical load shall be applied to the cylinder at the rate of 500 pounds per
minute (37 N/s) until failure occurs.
2109.3.1.2.4
Modulus of rupture
determination. The modulus of rupture shall be determined by the
equation:
f r = 3
PLs /2
Sw
(St2) |
(Equation 21-2) |
where, for the purposes of this section only:
Sw = Width of the
test specimen measured parallel to the loading cylinder, inches (mm).
fr = Modulus of
rupture, psi (MPa).
Ls = Distance between
supports, inches (mm).
St = Thickness of the
test specimen measured parallel to the direction of load, inches (mm).
P = The applied load at failure, pounds
(N).
2109.3.1.3
Moisture content requirements. Adobe units shall have a moisture
content not exceeding 4 percent by weight.
2109.3.1.4
Shrinkage cracks.
Adobe units shall not contain more than three shrinkage cracks and any single
shrinkage crack shall not exceed 3 inches (76 mm) in length or
1/8 inch (3.2 mm) in width.
2109.3.2
Stabilized adobe.
2109.3.2.1
Material requirements. Stabilized adobe shall comply with the material
requirements of unstabilized adobe in addition to Sections 2109.3.2.1.1 and
2109.3.2.1.2.
2109.3.2.1.1
Soil
requirements. Soil used for stabilized adobe units shall be chemically
compatible with the stabilizing material.
2109.3.2.1.2
Absorption
requirements. A 4-inch (102 mm) cube, cut from a stabilized adobe unit
dried to a constant weight in a ventilated oven at 212°F to 239°F
(100°C to 115°C), shall not absorb more than
21/2 percent moisture by
weight when placed upon a constantly water-saturated, porous surface for seven
days. A minimum of five specimens shall be tested and each specimen shall be
cut from a separate unit.
2109.3.3
Allowable stress. The
allowable compressive stress based on gross cross-sectional area of adobe shall
not exceed 30 psi (207 kPa).
2109.3.3.1
Bolts. Bolt values shall not exceed those set forth in Table 2109.3.3.1.
TABLE 2109.3.3.1 ALLOWABLE SHEAR ON BOLTS IN ADOBE
MASONRY
DIAMETER OF BOLTS
(inches) |
MINIMUM EMBEDMENT
(inches) |
SHEAR (pounds) |
1/2 |
- |
- |
5/8 |
12 |
200 |
3/4 |
15 |
300 |
7/8 |
18 |
400 |
1 |
21 |
500 |
11/8 |
24 |
600 |
For SI: 1 inch = 25.4 mm, 1 pound = 4.448 N. |
2109.3.4
Construction.
2109.3.4.1
General. Adobe
construction shall be limited as stated in Sections 2109.3.4.1.1 through
2109.3.4.1.4.
2109.3.4.1.1
Height
restrictions. Adobe construction shall be limited to buildings not
exceeding one story, except that two-story
construction is allowed when designed by a registered design
professional.
2109.3.4.1.2
Mortar restrictions. Mortar for stabilized adobe units shall
comply with Chapter 21 or adobe soil. Adobe soil used as mortar shall comply
with material requirements for stabilized adobe. Mortar for unstabilized adobe
shall be portland cement mortar.
2109.3.4.1.3
Mortar joints.
Adobe units shall be laid with full head and bed joints and in full running
bond.
2109.3.4.1.4
Parapet
walls. Parapet walls constructed of adobe units shall be
waterproofed.
2109.3.4.2
Wall thickness. The minimum thickness of exterior
walls in one-story buildings shall be 10 inches (254 mm). The walls
shall be laterally supported at intervals not exceeding 24 feet (7315 mm). The
minimum thickness of interior load-bearing walls shall be 8
inches (203 mm). In no case shall the unsupported height of any wall
constructed of adobe units exceed 10 times the thickness of such
wall.
2109.3.4.3
Foundations. Foundations for adobe construction shall be in accordance
with Sections 2109.3.4.3.1 and 2109.3.4.3.2.
2109.3.4.3.1
Foundation support.
Walls and partitions constructed of adobe units shall be supported by
foundations or footings that extend not less than 6 inches (152 mm) above
adjacent ground surfaces and are constructed of solid masonry (excluding adobe)
or concrete. Footings and foundations shall comply with Chapter 18.
2109.3.4.3.2
Lower course
requirements. Stabilized adobe units shall be used in adobe walls for
the first 4 inches (102 mm) above the finished first-floor elevation.
2109.3.4.4
Isolated piers
or columns. Adobe units shall not be used for isolated piers or columns
in a load-bearing capacity. Walls less than 24 inches (610 mm) in length shall
be considered isolated piers or columns.
2109.3.4.5
Tie beams.
Exterior walls and interior
load-bearing
walls constructed of adobe units shall have a continuous tie beam at
the level of the floor or roof bearing and meeting the following requirements.
2109.3.4.5.1
Concrete tie beams.
Concrete tie beams shall be a minimum depth of 6 inches (152 mm) and a
minimum width of 10 inches (254 mm). Concrete tie beams shall be continuously
reinforced with a minimum of two No. 4 reinforcing bars. The specified
compressive strength of concrete shall be at least 2,500 psi (17.2
MPa).
2109.3.4.5.2
Wood tie
beams. Wood tie beams shall be solid or built up of lumber having a
minimum nominal thickness of 1 inch (25 mm), and shall have a minimum depth of
6 inches (152 mm) and a minimum width of 10 inches (254 mm). Joints in wood tie
beams shall be spliced a minimum of 6 inches (152 mm). No splices shall be
allowed within 12 inches (305 mm) of an opening. Wood used in tie beams shall
be approved naturally decay-resistant or preservative-treated
wood.
2109.3.4.6
Exterior finish. Exterior walls constructed of
unstabilized adobe units shall have their exterior surface covered with a
minimum of two coats of portland cement plaster having a minimum thickness of
3/4 inch (19.1 mm) and
conforming to ASTM C 926. Lathing shall comply with ASTM C 1063. Fasteners
shall be spaced at 16 inches (406 mm) o.c. maximum. Exposed wood surfaces shall
be treated with an approved wood preservative or other
protective coating prior to lath application.
2109.3.4.7
Lintels. Lintels
shall be considered structural members and shall be designed in accordance with
the applicable provisions of Chapter 16.