Section 1707 - SPECIAL INSPECTIONS FOR SEISMIC RESISTANCE
Subsection 1707.6 - Architectural components

Universal Citation: 780 CMR MA Code of Regs 1707.6

Current through Register 1531, September 27, 2024

Periodic special inspection during the erection and fastening of exterior cladding, interior and exterior nonbearing walls and interior and exterior veneer in structures assigned to Seismic Design Category D, E or F.

Exceptions:

1. Special inspection is not required for exterior cladding, interior and exterior nonbearing walls and interior and exterior veneer 30 feet (9144 mm) or less in height above grade or walking surface.

2. Special inspection is not required for exterior cladding and interior and exterior veneer weighing 5 psf (24.5 N/m2) or less.

3. Special inspection is not required for interior nonbearing walls weighing 15 psf (73.5 N/m2) or less.

Disclaimer: These regulations may not be the most recent version. Massachusetts may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.