Code of Massachusetts Regulations
780 CMR - STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
Chapter 17 - Structural Tests and Special Inspections
Section 1704 - SPECIAL INSPECTIONS
Subsection 1704.3 - Steel construction
Current through Register 1531, September 27, 2024
The special inspections for steel elements of buildings and structures shall be as required by Section 1704.3 and Table 1704.3.
Exceptions:
1. Special inspection of the steel fabrication process shall not be required where the fabricator does not perform any welding, thermal cutting or heating operation of any kind as part of the fabrication process. In such cases, the fabricator shall be required to submit a detailed procedure for material control that demonstrates the fabricator's ability to maintain suitable records and procedures such that, at any time during the fabrication process, the material specification, grade and mill test reports for the main stress-carrying elements are capable of being determined.
2. The special inspector need not be continuously present during welding of the following items, provided the materials, welding procedures and qualifications of welders are verified prior to the start of the work; periodic inspections are made of the work in progress and a visual inspection of all welds is made prior to completion or prior to shipment of shop welding.
TABLE 1704.3 REQUIRED VERIFICATION AND INSPECTION OF STEEL CONSTRUCTION
VERIFICATION AND INSPECTION | CONTINUOUS | PERIODIC | REFERENCED STANDARDa | IBC REFERENCE |
1. Material verification of high-strength bolts, nuts and washers: | ||||
a. Identification markings to conform to ASTM standards specified in the approved construction documents. | - | X | AISC 360, Section A3.3 and applicable ASTM material standards | |
b. Manufacturer's certificate of compliance required. | - | X | - | - |
2. Inspection of high-strength bolting: | ||||
a. Snug-tight joints. | - | X | AISC 360, Section M2.5 | 1704.3.3 |
b. Pretensioned and slip-critical joints using turn-of-nut with matchmarking, twist-off bolt or direct tension indicator methods of installation. | - | X | ||
c. Pretensioned and slip-critical joints using turn-of-nut without matchmarking or calibrated wrench methods of installation. | X | - | ||
3. Material verification of structural steel and cold-formed steel deck: | ||||
a. For structural steel, identification markings to conform to AISC 360. | - | X | AISC 360, Section M5.5 | |
b. For other steel, identification markings to conform to ASTM standards specified in the approved construction documents. | - | X | Applicable ASTM material standards | |
c. Manufacturer's certified test reports. | - | X | ||
4. Material verification of weld filler materials: | ||||
a. Identification markings to conform to AWS specification in the approved construction documents. | - | X | AISC 360, Section A3.5 and applicable AWS A5 documents | - |
b. Manufacturer's certificate of compliance required. | - | X | - | - |
5. Inspection of welding: | ||||
a. Structural steel and cold-formed steel deck: | ||||
1) Complete and partial joint penetration groove welds. | X | - | AWS D1.1 | 1704.3.1 |
2) Multipass fillet welds. | X | - | ||
3) Single-pass fillet welds > 5/16" | X | - | ||
4) Plug and slot welds. | X | - | ||
5) Single-pass fillet welds <= 5/16" | - | X | ||
6) Floor and roof deck welds. | - | X | AWS D1.3 | |
b. Reinforcing steel: | - | |||
1) Verification of weldability of reinforcing steel other than ASTM A 706. | - | X | AWS D1.4 ACI 318:Section 3.5.2 | |
2) Reinforcing steel resisting flexural and axial forces in intermediate and special moment frames, and boundary elements of special structural walls of concrete and shear reinforcement. | X | - | ||
3) Shear reinforcement. | X | - | ||
4) Other reinforcing steel. | - | X | ||
6. Inspection of steel frame joint details for compliance: | ||||
a. Details such as bracing and stiffening. | - | X | - | 1704.3.2 |
b. Member locations. | - | X | ||
c. Application of joint details at each connection. | - | X |
For SI: 1 inch = 25.4 mm. a. Where applicable, see also Section 1707.1, Special inspection for seismic resistance. |