Section 1607 - LIVE LOADS
Subsection 1607.9 - Reduction in live loads
Current through Register 1531, September 27, 2024
Except for uniform live loads at roofs, all other minimum uniformly distributed live loads, Lo, in Table 1607.1 are permitted to be reduced in accordance with Section 1607.9.1 or 1607.9.2. Roof uniform live loads, other than special purpose roofs of Section 1607.11.2.2, are permitted to be reduced in accordance with Section 1607.11.2. Roof uniform live loads of special purpose roofs are permitted to be reduced in accordance with Section 1607.9.1 or 1607.9.2.
1607.9.1 General. Subject to the limitations of Sections 1607.9.1.1 through 1607.9.1.4, members for which a value of KLLATis 400 square feet (37.16 m2) or more are permitted to be designed for a reduced live load in accordance with the following equation:
Click to view image | (Equation 16-22) |
For SI: | Click to view image |
where:
L | = | Reduced design live load per square foot (square meter) of area supported by the member. |
Lo | = | Unreduced design live load per square foot (square meter) of area supported by the member (see Table 1607.1). |
KLL | = | Live load element factor (see Table 1607.9.1). |
AT | = | Tributary area, in square feet (square meters). |
L shall not be less than 0.50 Lo for members supporting one floor and L shall not be less than 0.40 Lo for members supporting two or more floors. |
ELEMENT | KLL | |
Interior columns Exterior columns without cantilever slabs |
4 4 | |
Edge columns with cantilever slabs | 3 | |
Corner columns with cantilever
slabs Edge beams without cantilever slabs Interior beams |
2 2 2 | |
All other members not identified above including: | 1 | |
Edge beams with cantilever slabs Cantilever beams One-way slabs Two-way slabs Members without provisions for continuous shear transfer normal to their span |
Exceptions:
Exception: The live loads for members supporting two or more floors are permitted to be reduced by a maximum of 20 percent, but the live load shall not be less than L as calculated in Section 1607.9.1.
1607.9.2 Alternate floor live load reduction. As an alternative to Section 1607.9.1, floor live loads are permitted to be reduced in accordance with the following provisions. Such reductions shall apply to slab systems, beams, girders, columns, piers, walls and foundations.
Exception: For uses other than storage, where approved, additional live load reductions shall be permitted where shown by the registered design professional that a rational approach has been used and that such reductions are warranted.
R = 0.08(A - 150) | (Equation 16-23) |
For SI: R = 0.861(A - 13.94)
Such reduction shall not exceed the smallest of:
R = 23.1(1 + D/Lo) | (Equation 16-24) |
where:
A | = | Area of floor supported by the member, square feet (m2). |
D | = | Dead load per square foot (m2) of area supported. |
Lo | = | Unreduced live load per square foot (m2) of area supported. |
R | = | Reduction in percent. |