Code of Massachusetts Regulations
780 CMR - STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
Chapter 14 - Exterior Walls
Section 1406 - COMBUSTIBLE MATERIALS ON THE EXTERIOR SIDE OF EXTERIOR WALLS
Subsection 1406.2 - Combustible exterior wall coverings
Current through Register 1531, September 27, 2024
Combustible exterior wall coverings shall comply with this section.
Exception: Plastics complying with Chapter 26.
1406.2.1 Ignition resistance. Combustible exterior wall coverings shall be tested in accordance with NFPA 268.
Exceptions:
TABLE 1406.2.1.2 MINIMUM FIRE SEPARATION FOR COMBUSTIBLE VENEERS
FIRE SEPARATION DISTANCE (feet) | TOLERABLE LEVEL INCIDENT RADIANT HEAT ENERGY (kW/m2) | FIRE SEPARATION DISTANCE (feet) | TOLERABLE LEVEL INCIDENT RADIANT HEAT ENERGY (kW/m2) |
5 6 7 8 9 10 11 12 13 14 15 |
12.5 11.8 11.0 10.3 9.6 8.9 8.3 7.7 7.2 6.7 6.3 |
16 17 18 19 20 21 22 23 24 25 |
5.9 5.5 5.2 4.9 4.6 4.4 4.1 3.9 3.7 3.5 |
For SI: 1 foot = 304.8 mm. |
1406.2.2 Type I, II, III and IV construction. On buildings of Type I, II, III and IV construction, exterior wall coverings shall be permitted to be constructed of wood in accordance with Section 1405.5, or other equivalent combustible material, complying with the following limitations:
1406.2.3 Location. Where combustible exterior wall covering is located along the top of exterior walls, such trim shall be completely backed up by the exterior wall and shall not extend over or above the top of exterior walls.
1406.2.4 Fireblocking. Where the combustible exterior wall covering is furred from the wall and forms a solid surface, the distance between the back of the covering and the wall shall not exceed 15/8 inches (41 mm). Where required by Section 717, the space thereby created shall be fireblocked.