Chapter 10 - Means of Egress
Section 1028 - ASSEMBLY
Subsection 1028.6 - Width of means of egress for assembly
Current through Register 1531, September 27, 2024
The clear width of aisles and other means of egress shall comply with Section 1028.6.1 where smoke-protected seating is not provided and with Section 1028.6.2 or 1028.6.3 where smoke-protected seating is provided. The clear width shall be measured to walls, edges of seating and tread edges except for permitted projections.
1028.6.1 Without smoke protection. The clear width of the means of egress shall provide sufficient capacity in accordance with all of the following, as applicable:
1028.6.2 Smoke-protected seating. The clear width of the means of egress for smoke-protected assembly seating shall not be less than the occupant load served by the egress element multiplied by the appropriate factor in Table 1028.6.2. The total number of seats specified shall be those within the space exposed to the same smoke-protected environment. Interpolation is permitted between the specific values shown. A life safety evaluation, complying with NFPA 101, shall be done for a facility utilizing the reduced width requirements of Table 1028.6.2 for smoke-protected assembly seating.
Exception: For an outdoor smoke-protected assembly with an occupant load not greater than 18,000, the clear width shall be determined using the factors in Section 1028.6.3.
TABLE 1028.6.2 WIDTH OF AISLES FOR SMOKE-PROTECTED ASSEMBLY
TOTAL NUMBER OF SEATS IN THE SMOKE- PROTECTED ASSEMBLY OCCUPANCY | INCHES OF CLEAR PER SEAT SERVED | |||
Stairs and aisle steps with handrails within 30 inches | Stairs and aisle steps without handrails within 30 inches | Passageways, doorways and ramps not steeper than 1 in 10 in slope | Ramps steeper than 1 in 10 in slope | |
Equal to or less than 5,000 | 0.200 | 0.250 | 0.150 | 0.165 |
10,000 | 0.130 | 0.163 | 0.100 | 0.110 |
15,000 | 0.096 | 0.120 | 0.070 | 0.077 |
20,000 | 0.076 | 0.095 | 0.056 | 0.062 |
Equal to or greater than 25,000 | 0.060 | 0.075 | 0.044 | 0.048 |
For SI: 1 inch = 25.4 mm. |
Exception: A roof canopy in an outdoor stadium shall be permitted to be less than 15 feet (4572 mm) above the highest aisle or aisle accessway provided that there are no objects less than 80 inches (2032 mm) above the highest aisle or aisle accessway.
Exceptions:
1028.6.3 Width of means of egress for outdoor smoke-protected assembly. The clear width in inches (mm) of aisles and other means of egress shall be not less than the total occupant load served by the egress element multiplied by 0.08 (2.0 mm) where egress is by aisles and stairs and multiplied by 0.06 (1.52 mm) where egress is by ramps, corridors, tunnels or vomitories.
Exception: The clear width in inches (mm) of aisles and other means of egress shall be permitted to comply with Section 1028.6.2 for the number of seats in the outdoor smoke-protected assembly where Section 1028.6.2 permits less width.