Code of Massachusetts Regulations
780 CMR - STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
Chapter 10 - Means of Egress
Section 1021 - NUMBER OF EXITS AND CONTINUITY
Subsection 1021.1 - Exits from stories
Current through Register 1531, September 27, 2024
All spaces within each story shall have access to the minimum number of approved independent exits as specified in Table 1021.1 based on the occupant load of the story. For the purposes of this chapter, occupied roofs shall be provided with exits as required for stories.
Exceptions:
1. As modified by Section 403.5.2.
2. As modified by Section 1021.2.
3. Exit access stairways and ramps that comply with Exception 3 or 4 of Section 1016.1 shall be permitted to provide the minimum number of approved independent exits required by Table 1021.1 on each story.
4. In Group R-2 and R-3 occupancies, one means of egress is permitted within and from individual dwelling units with a maximum occupant load of 20 where the dwelling unit is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2.
5. Within a story, rooms and spaces complying with Section 1015.1 with exits that discharge directly to the exterior at the level of exit discharge, are permitted to have one exit.
TABLE 1021.1 MINIMUM NUMBER OF EXITS FOR OCCUPANT LOAD
OCCUPANT LOAD
(persons per story) |
MINIMUM NUMBER OF EXITS
(per story) |
1-500 | 2 |
501-1,000 | 3 |
More than 1,000 | 4 |