Section 1019 - EGRESS BALCONIES
Subsection 1019.2 - Wall separation

Universal Citation: 780 CMR MA Code of Regs 1019.2
Current through Register 1531, September 27, 2024

Exterior egress balconies shall be separated from the interior of the building by walls and opening protectives as required for corridors.

Exception: Separation is not required where the exterior egress balcony is served by at least two stairs and a dead-end travel condition does not require travel past an unprotected opening to reach a stair.

Disclaimer: These regulations may not be the most recent version. Massachusetts may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.