Chapter 10 - Means of Egress
Section 1018 - CORRIDORS
Subsection 1018.6 - Corridor continuity
Universal Citation: 780 CMR MA Code of Regs 1018.6
Current through Register 1531, September 27, 2024
Fire-resistance-rated corridors shall be continuous from the point of entry to an exit, and shall not be interrupted by intervening rooms.
Exception: Foyers, lobbies or reception rooms constructed as required for corridors shall not be construed as intervening rooms.
Disclaimer: These regulations may not be the most recent version. Massachusetts may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.