Code of Massachusetts Regulations
780 CMR - STATE BOARD OF BUILDING REGULATIONS AND STANDARDS
Chapter 10 - Means of Egress
Section 1018 - CORRIDORS
Subsection 1018.1 - Construction
Current through Register 1531, September 27, 2024
Corridors shall be fire-resistance rated in accordance with Table 1018.1. The corridor walls required to be fire-resistance rated shall comply with Section 709 for fire partitions.
Exceptions:
1. A fire-resistance rating is not required for corridors in an occupancy in Group E where each room that is used for instruction has at least one door opening directly to the exterior and rooms for assembly purposes have at least one-half of the required means of egress doors opening directly to the exterior. Exterior doors specified in this exception are required to be at ground level.
2. A fire-resistance rating is not required for corridors contained within a dwelling or sleeping unit in an occupancy in Group R.
3. A fire-resistance rating is not required for corridors in open parking garages.
4. A fire-resistance rating is not required for corridors in an occupancy in Group B which is a space requiring only a single means of egress complying with Section 1015.1.
TABLE 1018.1 CORRIDOR FIRE-RESISTANCE RATING
OCCUPANCY | OCCUPANT LOAD SERVED BY CORRIDOR | REQUIRED FIRE-RESISTANCE RATING (hours) | |
Without sprinkler system | With sprinkler systemc | ||
H-1, H-2, H-3 | All | Not Permitted | 1 |
H-4, H-5 | Greater than 30 | Not Permitted | 1 |
A, B, E, F, M, S, U | Greater than 30 | 1 | 0 |
R | Greater than 10 | Not Permitted | 0.5 |
I-2a, I-4 | All | Not Permitted | 0 |
I-1, I-3 | All | Not Permitted | 1b |
a. | For requirements for occupancies in Group I-2, see Sections 407.2 and 407.3. |
b. | For a reduction in the fire-resistance rating for occupancies in Group I-3, see Section 408.8. |
c. | Buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1 or 903.3.1.2 where allowed. |