Current through Register 1531, September 27, 2024
Chapter
1
Administration. Chapter 1
is deleted in its entirety and replaced as follows:
1.1
General Considerations. This
Code shall apply to both new and existing conditions. Unless the provisions of
this
Code specify that a requirement shall apply to existing
occupancies, conditions or systems, an installation completed prior to the
effective date of this
Code shall be deemed in compliance if
the installation was made in accordance with the applicable
Code in effect at the time of the installation and was
approved by the AHJ. Notwithstanding the provisions of Section 1.1, if any
prior installation or condition exists which constitutes an imminent danger;
the AHJ may require compliance with the provisions of this
Code.
1.1.1
Massachusetts General Law and State Building Code. Applicable
Massachusetts General Law and requirements of the 780 CMR: State
Building Code, also referred herein as the Building Code, and
specialized codes as referenced in Chapter 2 and defined in Chapter 3 shall be
adhered to in the design and construction of buildings, structures, and
equipment.
1.1.2
Construction
Requirements for Buildings and Structures. Unless otherwise regulated by
the provisions contained in
527 CMR
1.00:1.03, or as otherwise indicated by specific
language, reference or context, any provision of
527 CMR
1.00 or any standard or code referenced in
527 CMR
1.00 relative to construction, alteration, movement,
enlargement, replacement, repair, equipment, use and occupancy, location,
removal or demolition of buildings or structures or any appurtenances connected
or attached to such buildings or structures shall not be considered a
requirement of this Code, but rather a reference to the
applicable provisions of the Building Code. Such reference is
for the convenience of the reader and shall be subject to the jurisdiction of
the appropriate Building Official.
1.1.3
Requirements of Specialized
Codes. Unless otherwise indicated by language, specific reference or
context, any provisions of
527 CMR
1.00 or any standard or code referenced in
527 CMR
1.00 relative to the installation, alteration,
replacement or repair of any equipment or system subject to the jurisdiction of
a specialized code including, but not limited to: plumbing, electrical, sheet
metal, or elevator, shall not be considered a requirement of this
Code, but rather a reference to the applicable specialized
code. Such reference is for the convenience of the reader and shall be subject
to the jurisdiction of the appropriate specialized code official.
1.1.4
Continued Maintenance of Any
Equipment, System, Construction Requirement, Specification or Method Relating
to Fire Protection. Notwithstanding the provisions of Sections 1.1.2 or
1.1.3, any equipment, system, construction requirement, specification or method
relating to fire protection of persons or property within a building,
structure, or ship or vessel shall be properly maintained and shall continue to
perform in accordance with the applicable requirements of the Building
Code or applicable specialized code as of the date of such approved
installation or construction.
1.2
Reserved
1.3
Application
1.3.1
Reserved
1.3.2*
Referenced Standards.
1.3.2.1 Except as provided in
Sections 1.1.2 and 1.1.3, all codes and standards referenced
in 527 CMR
1.00 shall be considered as part of this
Code.
1.3.2.3
Nothing herein shall diminish the authority of the AHJ to determine compliance
with this Code for those activities or installations, as may
be otherwise granted under the authority of the provisions of M.G.L. chs. 22D,
48, 148, 148A, and other applicable provisions of Massachusetts General
Law.
1.3.3
Conflicts.
1.3.3.1 When a
requirement differs between this Code and a referenced
document, the requirement of this Code shall apply.
1.3.3.2 When a conflict between a general
requirement and a specific requirement occurs, the specific requirement shall
apply.
1.3.3.3 When the
requirements of this Code conflict with any other applicable
regulation, or ordinance, the provisions which establish the higher standard
for the promotion and protection of safety and welfare shall prevail.
1.3.4
Reserved
1.3.5
Vehicles and Marine Vessels. Vehicles and marine vessels, or other
similar conveyances, when in fixed locations and occupied as buildings, as
described by Section 11.6 of NFPA 101: Life Safety
Code, shall be treated as buildings and comply with this
Code.
1.3.6
Buildings and Structures.
1.3.6.1
Buildings, structures, additions, and alterations permitted for construction
after the adoption of this Code shall comply with the
provisions stated herein for new buildings.
1.3.6.2* Except as provided in
Section 10.3.2, buildings in existence or permitted for
construction prior to the adoption of this Code shall comply
with the provisions stated herein or referenced for existing
buildings.
1.3.6.3 Repairs
renovations, alterations, reconstruction, change of occupancy, and additions to
buildings shall conform to this Code, and the Building
Code and applicable specialized codes as authorized by M.G.L. c. 143,
§ 96.
1.3.6.4 Newly introduced
equipment, materials, processes, and operations regulated by this
Code shall comply with the requirements for this
Code.
1.3.7
Severability. If any
provision of this Code or the application thereof to any
person or circumstance is held invalid, the remainder of the
Code and the application of such provision to other persons or
circumstances shall not be affected thereby.
1.4
Equivalencies, Alternatives, and
Modifications. The provisions of this
Code shall not
prevent the use of equivalencies, alternatives, or modifications unless
specifically prohibited herein.
1.4.1
Equivalencies. Nothing in this Code is intended
to prevent the use of systems, methods, or devices of equivalent or superior
quality, strength, fire resistance, effectiveness, durability, and safety to
those prescribed by this Code, provided technical
documentation is submitted to the AHJ in writing to demonstrate equivalency and
the system, method, or device is approved for the intended purpose.
1.4.2
Alternatives. The specific
requirements of this Code shall be permitted to be altered by
the AHJ upon application in writing to allow alternative methods that will
secure equivalent fire safety, but in no case shall the alternative afford less
fire safety, in the judgment of the AHJ, which would be provided by compliance
with the provisions contained in this Code.
1.4.3
Modifications. The AHJ is
authorized to modify any of the provisions of this Code upon
application in writing by the owner, a lessee, or a duly authorized
representative where there are practical difficulties in the way of carrying
out the provisions of this Code, provided that the intent of
the Building Code or specialty code is complied with and
public safety is secured.
1.4.4
Buildings with equivalency, alternatives, or modifications approved by the AHJ
shall be considered as conforming with this Code.
1.4.5 Each application for an alternative
system, method, or device regulated by this Code shall be
filed with the AHJ in writing and shall be accompanied by such evidence,
letters, statements, results of tests, or other supporting information as
required to justify the request. The AHJ shall keep a record of actions on such
applications together with the information that supported the action in
accordance with Section 1.11, and a signed copy of the AHJ's
decision shall be provided to the applicant.
1.4.6
Approval. Where allowed by
this Code, the AHJ shall approve such alternative, systems,
materials, or methods of design when it is substantiated that the standards of
this Code are at least equaled. If, in the opinion of the AHJ,
the standards of this Code shall not be equaled by the
alternative requested, approval for permanent work shall be refused.
Consideration shall be given to test or prototype installations.
1.4.7
Tests.
1.4.7.1 Whenever evidence of compliance with
the requirements of this Code is insufficient or evidence that
any material or method does not conform to the requirements of this
Code or to substantiate claims for alternative, equivalent or
modifications to systems, materials, or methods, the AHJ shall be permitted to
require tests for proof of compliance to be made at the expense of the owner or
his or her agent.
1.4.7.2 Test
methods shall be as specified by this Code for the material in
question. If appropriate test methods are not specified in this
Code, the AHJ is authorized to accept an applicable test
procedure from another recognized source.
1.4.7.3 Copies of the results of all such
tests shall be retained in accordance with Section
1.11.
1.5
Units.
1.5.1
International System of
Units. Metric units of measurement in this Code are in
accordance with the modernized metric system, known as the International System
of Units (SI).
1.5.2
Primary
and Equivalent Values. If a value for a measurement as given in this
Code is followed by an equivalent value in other units, the first stated value
shall be regarded as the requirement. A given equivalent value could be
approximate.
1.6
Enforcement. This Code shall be administered and
enforced by the AHJ.
1.7
Authority.
1.7.1
Administration. The provisions of this Code shall
apply without restriction, unless specifically exempted.
1.7.2
Reserved
1.7.3
Interpretations.
1.7.3.1 Upon a written request of any
interested person the Board of Fire Prevention Regulations may render written
advisory rulings and interpretations of this Code, pursuant to
the provisions of M.G.L. c. 30A, § 8.
1.7.4
Enforcement Assistance.
Police and other enforcement agencies shall have authority to render necessary
assistance in the enforcement of this Code when requested to
do so by the AHJ.
1.7.5
Delegation of Authority. The AHJ may delegate to other qualified
individuals such powers as necessary for the administration and enforcement of
this Code as provided in M.G.L. c. 148.
1.7.6
Reserved
1.7.7
Inspections.
1.7.7.1 To the full extent allowed by the
provisions of M.G.L. c. 148, the AHJ shall be authorized to inspect, at all
reasonable times, any building or premises for dangerous or hazardous
conditions or materials in order to determine compliance with this
Code.
1.7.7.1.1
Coordinated Inspections. In circumstances involving compliance
with two or more Massachusetts codes including, but not limited to, the
Building Code, Uniform State Plumbing Code,
Massachusetts Electrical Code (Amendments), Elevator
Code and Sheet Metal Code, the AHJ, while enforcing
this Code shall, to the extent as reasonably practicable,
coordinate inspections so that owners and occupants of a building or structure
shall not be subjected to visits by numerous inspectors nor multiple or
conflicting orders.
1.7.7.1.2
Notification to Other Officials. Whenever the AHJ observes an
apparent or actual violation of some provision of law, ordinance, code, or
bylaw not within the AHJ's authority, the AHJ shall report the findings to the
appropriate code official having jurisdiction to enforce said law, ordinance,
code, or bylaw.
1.7.7.2
The AHJ shall have authority to order, in writing, any person(s) to remove or
remedy any dangerous or hazardous condition or material as provided in M.G.L.
c. 148 and this Code.
1.7.7.3 The AHJ engaged in fire prevention
and inspection work shall be authorized at all reasonable times to enter and
examine any building, structure, marine vessel, vehicle, or premises for the
purpose of making fire safety inspections, to the full extent allowed by the
provisions of M.G.L. c. 148 and this Code.
1.7.7.4 Before entering, the AHJ shall obtain
the consent of the occupant thereof or obtain a proper warrant authorizing
entry for the purpose of inspection, except where an emergency exists, or as
otherwise permitted by law.
1.7.7.4.1 The
applicant for any permit, certificate, or license issued pursuant to the
provisions of this Code or M.G.L. c. 148, or any person who
seeks to renew or continue to hold such permit, certificate or license, shall
be deemed to have consented to the inspection, at any reasonable hour, of any
documents, premises, structure, marine vessel, building or vehicle reasonably
associated with said permit, license, or certificate, or application or renewal
thereof, in order to confirm compliance with the requirements of this
Code, M.G.L. c. 148 or other related law or regulation related
to such permit, license, or certificate.
1.7.7.5 As used in Section
1.7.7.4, emergency shall mean conditions or circumstances that
the AHJ knows, or has reason to believe, exist and that can constitute imminent
danger.
1.7.8
Imminent Danger Conditions. Where conditions exist and are deemed
to be an imminent danger by the AHJ, the AHJ shall have the authority to
immediately abate or require immediate abatement of such conditions.
1.7.9
Interference with
Enforcement. No person shall interfere or cause conditions that would
interfere with an AHJ carrying out any duties or functions prescribed by this
Code.
1.7.10
Impersonation. Persons shall not use a badge, uniform, or other
credentials to impersonate the AHJ.
1.7.11
Reserved
1.7.12
Plans and Specifications.
1.7.12.1 The AHJ shall have the authority to
require plans and specifications to ensure compliance with this
Code and M.G.L. c. 148. Construction documents and shop
drawings submitted shall be acted upon before work commences and within 30 days
of the date of receipt of a completed application and construction documents
unless extended by the AHJ.
1.7.13
Inspection of Construction and
Installation.
1.7.13.1 The AHJ shall be
notified by the person performing the work when the installation is ready for a
required inspection.
1.7.13.2
Whenever any installation subject to inspection prior to use is covered or
concealed without having first been inspected, the AHJ shall have the authority
to require that such work be exposed for inspection.
1.7.13.3 When any construction or
installation work is being performed in violation of the plans and
specifications as approved by the AHJ, a written notice shall be issued to the
responsible party to stop work on that portion of the work that is in
violation.
1.7.13.4 The notice of
violation shall identify the violation together with the Section of this
Code in violation.
1.7.13.5 The AHJ may issue a stop work order
at which time the work shall not continue until the violation has been
corrected.
1.7.13.5.1 A stop work order, if
issued, shall be incorporated with the notice of violation.
1.7.14
Certificate
of Occupancy. When the Building Code requires a
certificate of occupancy, the certificate of occupancy shall be issued in
accordance with the Building Code.
1.7.15
Stop Work Order. AHJ
shall have the authority to order an operation, construction, or use stopped
when any of the following conditions exist:
(1) Work is being done contrary to provisions
of this Code.
(2)
Work is occurring without a permit required by Section
1.12.
(3) An imminent
danger is present.
1.7.16
Imminent Dangers and Evacuation.
1.7.16.1 Whenever the maintenance, operation,
or use of any land, building, structure, material or other object, or any part
thereof, including vehicles used in the transport of hazardous materials,
constitutes an imminent danger or a fire or explosion hazard which is dangerous
or unsafe, or a menace to the public safety (including, but not limited to,
fires, explosions, hazardous material incidents, motor vehicle accidents,
structural collapses, mass casualty incidents and emergency extrication
incidents) and the action to be taken to eliminate such dangerous or unsafe
condition which create, or tend to create, the same is not specifically
provided for in this Code, and unless otherwise prohibited by
law, ordinance, by-law, or regulation, the AHJ is hereby authorized and
empowered to take such action as may be necessary to abate such dangerous or
unsafe conditions.
1.7.17
Public Fire Education.
1.7.17.1
The AHJ shall have the authority to develop and implement a public fire safety
education program as deemed necessary for the general welfare with respect to
the potential fire hazards within the jurisdiction.
1.7.17.2 The AHJ shall have the authority to
ensure duly authorized public fire safety education programs or public fire
safety messages are disseminated to the general
public.
1.8
Reserved
1.9
Reserved
1.10
Fire Prevention Regulations Appeals Board.
1.10.1
Establishment and Membership of
the Fire Prevention Regulations Appeals Board.
(1) Pursuant to the provisions of M.G.L. c.
22D, § 5, there shall be a Fire Prevention Regulations Appeals
Board.
(2) The Appeals Board shall
consist of the 16 members of the Board of Fire Prevention Regulations,
established under M.G.L c. 22D, § 4.
(3) The Chairman of the Board of Fire
Prevention Regulations shall serve as the chairman of the Appeals
Board.
1.10.1.1
Authority of
the Fire Prevention Regulations Appeals Board. The Fire Prevention
Regulations Appeals Board is authorized to conduct appeals pursuant to the
provisions of M.G.L. c. 22D, § 5.
(1)
Whoever is aggrieved by any act, rule, order, directive, decision, or
requirement of the AHJ charged with the enforcement of this
Code, relative to the fire protection requirements for
buildings or structures, may submit an application for an appeal to the Appeals
Board within 45 days following the service of notice of such act, rule, order,
decision, requirement, or directive.
1.10.1.2
Matters not within the
Jurisdiction of the Appeals Board. The Fire Prevention Regulations
Appeals Board does not have jurisdiction to hear appeals relating to the
following matters:
(1) Matters arising out of
construction or installation requirements of the Building
Code, (Building Code Appeals Board, M.G.L. c. 143, §
100);
(2) Matters arising out of
the enforcement of the statutory enhanced automatic sprinkler provisions of
M.G.L. c. 148, § 26A1/2, 26G, 26G1/2, or 26H (Automatic
Sprinkler Appeals Board, M.G.L. c. 6, § 201);
(3) Matters arising out of an appeal of a
determination of the municipal wiring inspector and/or involving the
application of Massachusetts Electrical Code (Amendments),
(Board of Electrician's Appeal, M.G.L. c. 143, § 3P);
(4) Matters arising out the issuance of a
"Non-Criminal Fire Code Violation Notice" issued under the civil enforcement
provisions of M.G.L. c. 148A;
(5)
Matters arising out of the enforcement of a violation of any statute, including
the provisions of M.G.L. c. 148 or arising out of any Order issued by the Head
of the Fire Department or the State Fire Marshal relating to the abatement of a
condition that constitutes a fire or explosion hazard or which is dangerous or
unsafe or a menace to public safety (M.G.L. c. 148, § 5);
(6) Administrative matters initiated by the
State Fire Marshal relating to the suspension, revocation or refusal to issue
any certificate of competency or user's certificate issued by the State Fire
Marshal;
(7) Matters arising out of
the AHJ's determination to suspend, revoke, issue or renew any permit based
upon the exercise of discretionary function rather than a technical fire
protection requirement of this Code; and
(8) Matters arising out of the enforcement of
a city ordinance or town by-law or regulation promulgated or adopted by the
municipality.
1.10.1.3
Means of Appeal. Application for an appeal shall be made, within
45 days following the service of notice of such act, rule, order, decision,
requirement, or directive which is the subject of the appeal on forms
prescribed or approved by the Fire Prevention Regulations Appeals Board.
1.10.1.3.1 Such application shall be
accompanied by the required fee and include copies of all records, references,
reports, and other information related to the appeal.
1.10.1.3.2 An appeal shall stay all
proceedings in the furtherance of the action or failure to act which is the
subject of the appeal, unless the AHJ presents evidence that a stay would cause
imminent peril of life or property.
1.10.1.4
Appeals Board Hearings.
The Chairman of the Appeals Board shall designate three members of the Appeals
Board to hold public hearings, hear testimony and take evidence.
1.10.1.4.1 The Appeals Board shall not be
bound by the strict rules of evidence prevailing in courts of law or
equity.
1.10.1.4.2 The chairman
shall fix the time and place for hearings and a hearing shall take place not
later than 60 days following the filing of an appeal unless such time is
extended by agreement with the appellant.
1.10.1.4.3 The chairman shall give at least
ten days' notice of the time and place of the hearing to all interested
parties. Any party may appear in person, by agent or by attorney at the
hearing.
1.10.1.5
Appeals Board Decisions. The three members of the Appeals Board
conducting the hearing shall decide the appeal and issue a written decision.
Every decision shall require the concurrence of at least two of the three
members and the written decision shall state findings of fact, conclusions, and
reasons for the decision and indicate the vote of each member participating in
the decision.
1.10.1.5.1 The Appeals Board
shall issue a decision or order reversing, affirming, or modifying, in whole or
in part, such interpretation, order, or decision, or a postponement of the
application thereof, within 45 days following the hearing, unless such time is
extended by agreement with the appellant.
1.10.1.5.2 The Appeals Board may grant a
variance from any provision of this Code and related rules and
regulations in any particular case determine the suitability of alternate
materials or methods of compliance and provide reasonable interpretations of
this Code consistent with the purpose thereof.
1.10.1.6
Record of Appeals
Board Decisions. A record of all Appeals Board decisions and of votes
thereunder, properly indexed, shall be maintained in the office of the
Department of Fire Services in accordance with Section
1.11.
1.11
Records and Reports
1.11.1 A record of examinations, approvals,
disapprovals, equivalencies, modifications and alternatives shall be maintained
by the AHJ and shall be available for public inspection in accordance with
provisions of the applicable Massachusetts Public Records Laws.
1.11.2 In accordance with the provisions of
the applicable Massachusetts Public Records Laws, the AHJ shall keep records of
fire prevention inspections and investigations, including the date of
inspections and a summary of violations found to exist, the date of the
services of notices, and a record of the final disposition of all violations,
in accordance with the applicable records retention schedule.
1.11.3
Emergency Response
Records.
1.11.3.1
Reserved
1.11.3.2 The
fire department shall report all incident data collected in accordance with the
applicable provisions of Massachusetts General Law.
1.11.4 All records shall be retained in
accordance with the manner and duration required by the Massachusetts Public
Records Law.
1.12
Permits and Permit Approvals.
1.12.1 An application for permit shall be
made in writing on a form acceptable by the State Fire Marshal and submitted to
the applicable enforcement AHJ. Such application shall be legible and completed
in its entirety.
1.12.1.2 The AHJ shall be
authorized to issue permits and approvals as required by this
Code.
1.12.1.3
Persons named in the permit shall comply with this
Code.
1.12.2 Applications for permits shall be
accompanied by such data as required by the AHJ and such fees as required by
Massachusetts General Laws.
1.12.2.1 The AHJ
shall review all applications submitted and issue permits as
required.
1.12.2.2 If an
application for a permit is rejected by the AHJ, a written notification shall
be sent to the applicant as to the reasons for such rejection.
1.12.2.3 Permits for activities requiring
evidence of financial responsibility by the jurisdiction shall not be issued
unless proof of any required financial responsibility is furnished.
1.12.3
Conditions of
Approval.
1.12.3.1 Any conditions of
the approval by the AHJ of a permit shall remain with said permit, unless
modified by the AHJ.
1.12.3.2 The
AHJ shall be permitted to require conditions of approval to be memorialized via
recording on the permit or, if relating to land or buildings, at the
appropriate registry of deeds.
1.12.4
Approvals by Other
Authorities.
1.12.4.1 The AHJ shall
have the authority to require evidence to show that other regulatory agencies
having jurisdiction over the design, construction, alteration, repair,
equipment, maintenance, process, activity, and relocation of structures have
issued appropriate approvals.
1.12.4.2 The AHJ shall not be held
responsible for enforcement of the regulations of such other regulatory
agencies unless specifically mandated to enforce those agencies'
regulations.
1.12.5
Reserved
1.12.6
Permits.
1.12.6.1 A permit shall
be conditioned upon the continued compliance with the requirements of this
Code.
1.12.6.1.1 Unless
specifically stated otherwise, permits required in Section
1.12.8 shall be issued by the AHJ and issued as a precondition
before conducting any work or activity regulated under the provisions of this
Code.
1.12.6.2 Any permit issued under this
Code shall not take the place of any other approval,
certificate, license, or permit required by any other regulations or
laws.
1.12.6.3 Where additional
permits or approvals are required by other agencies, approval shall be obtained
from those other agencies.
1.12.6.4
The AHJ shall have the authority to require or conduct an inspection prior to
the issuance of a permit.
1.12.6.5
A permit issued under this Code shall remain valid for the
period of time designated on the permit unless suspended, revoked, or otherwise
extended pursuant to Section 1.12.6.8.
1.12.6.6 The permit shall be issued to one
person or entity only and shall be limited to locations or purposes described
in the permit.
1.12.6.7 Any change
that affects any of the conditions of the permit shall require a new or amended
permit.
1.12.6.8 The AHJ shall have
the authority to grant an extension of the permit time period upon presentation
by the permittee of a satisfactory reason for failure to start or complete the
work or activity authorized by the permit.
1.12.6.9 A copy of the permit shall be posted
or otherwise readily accessible at each place of operation and shall be subject
to inspection as specified by the AHJ.
1.12.6.10 Any activity authorized by any
permit issued under this Code shall be conducted by the
permittee or the permittee's agents or employees, in compliance with all
requirements of this Code applicable thereto and in accordance
with the approved plans and specifications.
1.12.6.11 No permit issued under this
Code shall be interpreted to justify a violation of any
provision of this Code any other applicable law or
regulation.
1.12.6.12 Any addition
or alteration of approved plans or specifications shall be approved in advance
by the AHJ, as evidenced by the issuance of a new or amended permit.
1.12.6.13 Permits shall bear the name and
signature of the AHJ or that of the AHJ's designated representative. In
addition, the permit shall indicate the following:
(1) Operation or activities for which the
permit is issued;
(2) Address or
location where the operation or activity is to be conducted;
(3) Name of the owner, with the address and
phone number and the name of the installer, with the address and phone number,
if applicable;
(4) Permit
number;
(5) Period of validity of
the permit;
(6) Inspection
requirements and other permit conditions;
(7) Name of the agency authorizing the permit
(AHJ);
(8) Date of
Issuance;
(9) Quantities of
materials to be kept, used or stored, as applicable;
(10) Certificate and/or license issued under
M.G.L. c. 148, § 13, as applicable;
(11) Permit conditions as determined by the
AHJ.
1.12.6.14 Any
application for, or acceptance of, any permit requested or issued pursuant to
this Code shall constitute agreement and consent by the person
making the application or accepting the permit, to allow the AHJ to enter the
premises at any reasonable time to conduct such inspections or review such
records as required by this Code.
1.12.7
Revocation or Suspension of
Permits and Approvals.
1.12.7.1 The AHJ
shall be permitted to revoke or suspend a permit or approval issued by said AHJ
if any violation of this Code or of M.G.L. c. 148 is found
upon inspection or if any false statements or misrepresentations have been
submitted in the permit application or plans on which the permit or approval
was based.
1.12.7.2 Revocation or
suspension shall be constituted when the permittee is duly notified by the
AHJ.
1.12.7.3 Any person who
continues to engage in any permitted or approved business, operation,
occupation, or uses any premises, after the permit or approval has been
suspended or revoked pursuant to the provisions of this Code
and before such suspended permit or approval has been reinstated or a new
permit or approval is issued, shall be in violation of this
Code.
1.12.8*
Permit. A permit and an
application for permit shall be required as prescribed in Section
1.12.8. No work or activities described in this
Section shall commence without first complying with
Section 1.12 and the applicable Table in Section
1.12.8.
A.1.12.8
See M.G.L. c. 148, § 10A regarding heads of fire
departments, permits, inspections, and M.G.L. c. 148, § 23 regarding the
keeping and use of flammable fluids, permit, and M.G.L. c. 148, § 24
regarding keeping and handling of fire menace material.
1.12.8.1
General Safety Requirements
with Regards to Open Air Burning, Use of a Torch, Fogging and Storage of
Combustible Goods. [Chapter 10]
1.12.8.1.1 Permit holder shall be present at
such burning to control the fire until it is entirely extinguished.
1.12.8.1.2 Open air burning permits required
by Sections 10.10.1 and 10.10.4.1.1 shall be
issued for a period not exceeding two days from the date of the
permit.
1.12.8.1.3
Removal of
Paint using a Torch.
1.12.8.1.3.1
Permit. A permit shall be required for the use of a torch or other
flame or heat producing device for the removal of paint or the application or
removal of roofing material from any building or structure. An approved fire
extinguisher or an adequate water supply shall be readily available at all
times.
1.12.8.1.4 No work
or activity described in Table 1.12.8.1 shall be performed until such time as a
valid permit has been issued.
Chapter 10 |
General
Requirements |
Work/Activity |
Issuing Authority |
Code Section |
*Open Air Burning, see
Annex |
Forest Warden |
10.10.1 |
*Ceremonial Bonfires, see
Annex |
Head of Fire Department |
10.10.4.1.1 |
Open Flame (heat producing) devices |
10.10.1
10.10.9.1 |
Storage of combustible materials |
10.15.1.2
10.15.2.1
10.18.2 |
Fumigation and insecticidal fogging |
10.20.1 |
*Use of canine guards, see
Annex |
10.21.1 |
Table 1.12.8.1* Permits Required
A.1.12.8.1(1)
See M.G.L. c.
48, § 13, regarding open fires granted by the forest warden or chief of
the fire department in cities, towns and districts.
A.1.12.8.1(2)
See M.G.L. c.
111, § 142 G, regarding the burning of Christmas trees and; M.G.L. c. 111,
§ 142H regarding, ceremonial bonfires; permits and M.G.L. c. 111, §
142I regarding, bonfires from July 2nd through July
6th.
A.1.12.8.1(6)
See M.G.L. c.
148, § 28B regarding, buildings with canine
guards.
1.12.8.2
Building Services with Regards
to Fuel-Oil Heating Appliances [Chapter 11]
1.12.8.2.1
Permit Approval
1.12.8.2.1.1
Table 1.12.8.2
shall apply to Chapter 11, entitled Building Services. Except
as permitted by Section 1.12.8.2.1, and by Table
1.12.8.50 for heating appliances, on a form approved by the State Fire
Marshal, a permit shall be used, completed, required and issued as a
precondition before conducting any work/activity by Table
1.12.8.2.
1.12.8.2.1.2
Heating Appliances.
(1) A permit
shall not be required for routine maintenance, such as the replacement of
nozzles, ignition electrodes, or filters; and
(2) If an installation is made under
emergency conditions, an application for a permit shall be required within 24
hours thereafter, excluding Saturdays, Sundays and legal holidays.
1.12.8.2.2
Inspection.
1.12.8.2.2.1 If after
30 days, an inspection has not been conducted, then the delivery of fuel oil
shall not be prohibited for lack of a permit to store.
Table 1.12.8.2* Permits Required
Chapter 11 |
Oil Burners and Fuel-oil |
Work/Activity |
Issuing Authority |
Code Section |
*Installation or alteration of any fuel oil burning
equipment.
Oil-line upgrade |
Head of Fire Department |
11.5.1.8 |
Storage of acceptable liquid fuel |
11.5.1.10 |
*Installation, removal, or replacement of a fuel
storage tank, unless provided otherwise in NFPA Chapter 66 |
A.1.12.8.2(1)
See M.G.L. c. 148, § 10A regarding, heads of fire
departments; permits; inspections and; M.G.L. c. 148, § 10C regarding the
alteration, repair or installation of oil burners; necessity of certificate;
exceptions and; M.G.L. c. 148, § 38J regarding, residential property
utilizing heating oil tanks; safety requirements; inspection;
certification.
A.1.12.8.2(2)
See M.G.L. c. 148, § 10A regarding, heads of fire
departments; permits; inspections and; M.G.L. c. 148, 10C regarding, the
alteration, repair or installation of oil burners; necessity of certificate;
exceptions.
A.1.12.8.2(3)
See M.G.L. c. 148 § 10A regarding, heads of fire
departments; permits; inspections and; M.G.L. c. 148, § 23 regarding the
keeping and use of inflammable fluids; permit and; M.G.L. c. 148, § 4
regarding, the keeping and handling of fire menace material;
See M.G.L. c. 148, § 37 regarding, tanks more than 10,000
gallons used to store fluids other than water; permits; violation of statue or
regulation and; annual inspections and Chapter 66 of NFPA 1.
1.12.8.3
Smoke, Fire and Carbon Monoxide Protection Systems. [Chapter 13]
1.12.8.3.1 No person or entity may install
any fire protection system in any new or existing building or structure without
first complying with the provisions in this section and Table
1.12.8.3.
1.12.8.3.2 Fire
Protection System. Any fire alarm device or system or fire-extinguishing device
or system, or combination thereof, that is designed and installed for
detecting, controlling, or extinguishing a fire or otherwise alerting
occupants, or the fire department, or both, that a fire has occurred. A fire
protection system shall include any wiring, equipment, and systems used to
detect, suppress, or control smoke, fire, and carbon monoxide, or any
combination thereof.
1.12.8.3.3 No
permit shall be required for the replacement, in kind, of an individual device
(battery, carbon monoxide detector/alarm).
1.12.8.3.4
See Chapter 42
for additional fire protection system requirements.
Table 1.12.8.3 Permits Required
Chapter 13 |
Fire Protection System and Related
Equipment |
Work/Activity |
Issuing Authority |
Chapter/Code Section/M.G.L. |
Carbon monoxide/Smoke alarm installations [< 5
dwelling units] at time of property sale or transfer. |
Head of Fire Department |
M.G.L. c. 148, §§ 26F and
26F1/2Known as a Certificate of Compliance |
Installations of carbon monoxide protection technical
options. |
13.7.2 |
Impairment or disconnection of any sprinkler system,
water main, hydrant, or other device used for fire protection system, including
carbon monoxide detection and alarm. [M.G.L c. 148, § 27A] |
13.1.1.1.2
13.7.2.2 |
See also Section
1.12.8.3 |
1.12.8.4
Safeguarding Construction,
Alteration, and Demolition Operations. [Chapter 16]
1.12.8.4.1
See Chapter 41
and
Table 1.12.8.23 for permit requirements for Welding,
Cutting, and Other Hot Work.
Table 1.12.8.4 Permits Required
Chapter 16 |
Safeguarding Construction, Alteration, and
Demolition Operations |
Work/Activity |
Issuing Authority |
Code Section |
Heating and Cooling Equipment Used During
Construction, Alteration, or Demolition |
Head of Fire Department |
16.19.3.1.1 |
Torch-applied roofing operations |
16.22.1.1 |
See also Section
1.12.8.4 |
1.12.8.5
Combustible Waste and Refuse.
[Chapter 19]1.12.8.5.1 A permit shall
not be required for containers which are delivered to a location and removed in
the course of a single business day.
1.12.8.5.2 Containers shall be marked with
the name and telephone number of the company who can be reached in an
emergency.
Table 1.12.8.5 Permits Required
Chapter 19 |
Combustible Waste, Refuse, and Rubbish
Containers |
Work/Activity |
Issuing Authority |
Code Section |
Rubbish containers > 6 cubic yards |
Head of Fire Department |
19.1.1 |
See also 1.12.8.5 |
1.12.8.6
Occupancy Fire Safety.
[Chapter 20]1.12.8.6.1
Unvented
Heaters.
1.12.8.6.1.1 A copy of the
manufacturer's installation/operating literature for unvented propane or
natural gas-fired space heaters shall be submitted with each permit
application.
1.12.8.6.1.2 Before
operation of such heater, the Head of the Fire Department and the local or
State Plumbing/Gas Inspector shall inspect the installation.
Table 1.12.8.6 Permits Required
Chapter 20 |
Occupancy Fire Safety |
Work/Activity/Location |
Issuing Authority |
Code Section |
Assembly Occupancies |
Head of Fire Department |
20.1.1.1 |
Special Provisions for Food Service
Operations |
20.1.5.2.4.1 |
Open flame devices and Pyrotechnics |
20.1.5.3.1 |
Special Provisions for Exposition
Facilities |
20.1.5.5.1 |
Cellulose Nitrate Motion Picture Film
Storage |
20.15.7.2 |
High-piled Storage |
20.15.8.2 |
Unvented Fuel-Fired Heating
Equipment. |
20.2.4.5.1, 20.3.2.1.1,
20.8.2.6.1, 20.9.2.2.1, 20.10.2.1, and
20.11.2.1 |
See also Section
1.12.8.6 |
1.12.8.7
Chapter 21
Reserved
1.12.8.8
Chapter 22 Reserved
1.12.8.9
Cleanrooms. [Chapter
23]
1.12.8.9.1
See
chapters 60 through 75 for permitting requirements regarding hazardous
materials.
Table 1.12.8.9 Permits Required
Chapter 23 |
Cleanrooms |
Work/Activity |
Issuing Authority |
Code Section |
Use, storage or handling of hazardous
materials |
Head of Fire Department |
23.3
61.1.2
61.5.3.3.1
63.1.2
66.1.5
69.1.2 |
1.12.8.10
Dry Cleaning. [Chapter
24]1.12.8.10.1
See
chapters 60 through 75 for permitting requirements regarding hazardous
materials.
Table 1.12.8.10 Permits Required
Chapter 24 |
Dry Cleaning |
Work/Activity |
Issuing Authority |
Code Section |
Use, storage or handling of hazardous
materials |
Head of Fire Department |
24.2
61.1.2
61.5.3.3.1
63.1.2
66.1.5
69.1.2 |
1.12.8.11
Chapter 25
Reserved
1.12.8.12
Laboratories Using Chemicals. [Chapter 26]
1.12.8.12.1
See chapters 60
through 75 for permitting requirements regarding hazardous materials.
Table 1.12.8.12 Permits Required
Chapter 26 |
Laboratories Using Chemicals |
Work/Activity |
Issuing Authority |
Code Section |
The handling or storage of chemicals in laboratory
buildings, laboratory units, and laboratory work areas whether located above or
below grade. |
Head of Fire Department |
26.2
61.1.2
61.5.3.3.1
63.1.2
66.1.5
69.1.2 |
1.12.8.13
Chapter 27
Reserved
1.12.8.14
Chapter 28 Reserved
1.12.8.15
Chapter 29
Reserved
1.12.8.16
Motor Fuel Dispensing Facilities and Repair Garages. [Chapter 30]
1.12.8.16.1
See chapters 60
through 75 for permitting requirements regarding hazardous materials.
Table 1.12.8.16 Permits Required
Chapter 30 |
Motor Fuel Dispensing Facilities and Repair
Garages |
Work/Activity |
Issuing Authority |
Code Section |
Use, storage or handling of hazardous
materials. |
Head of Fire Department |
30.1.1.3
61.1.2
61.5.3.3.1
63.1.2
66.1.5
69.1.2 |
1.12.8.17
Forest Products. [Chapter
31]
Table 1.12.8.17 Permits Required
Chapter 31 |
Forest Products |
Work/Activity |
Issuing Authority |
Code Section |
Storage of mulch > 300 cubic
yards. |
Head of Fire Department |
31.2 |
1.12.8.18
Motion Picture and Television
Production Studio Soundstages and Approved Production Facilities. [Chapter
32]
1.12.8.18.1
Notification.
1.12.8.18.1.1 A
permit shall not be required provided notification is given to the Head of the
Fire Department for production locations where 15 through 30 on-site personnel
are present, and when permits are not specifically required by Chapter 32.
Table 1.12.8.18 Permits Required
Chapter 32 |
Motion Picture and Television Production Studio
Soundstages and Approved Production Facilities |
Work/Activity |
Issuing Authority |
Code Section |
For activities listed in 32.2.2. |
Head of Fire Department |
32.2.2 |
See also Section
1.12.8.18 |
1.12.8.19
Chapter 33
Reserved
1.12.8.20
Chapter 34 Reserved
1.12.8.21.
Cannabis Growing,
Processing, or Extraction [Chapter 38]
1.12.8.21.1
Table 1.12.8.21
shall apply to Chapter 38 entitled Cannabis Growing, Processing, or Extraction
Facilities. No work or activity described in
Table 1.12.8.21
shall be performed until such time as a valid permit has been issued.
Table 1.12.8.21* Permits Required
Work/Activity |
Issuing Authority |
Code Section |
Processing or extraction of cannabis involving
hazardous materials, see 38.1. |
Head of Fire Department |
38.2
60.8 |
A Table 1.12.8.21. A permit is required for
processes involving hazardous materials in accordance with Section 60.8.
Chapter 38 provides specific requirements for operations and equipment utilized
in the processing and extraction activities commonly associated with cannabis
processing facilities. It is generally accepted that processes involving
hazardous materials will meet industry best practices. In the case of cannabis
processing and extraction, compliance with the published regulations of Chapter
38 are the minimum industry standard.
1.12.8.22
Dust Explosion and Fire
Prevention. [Chapter 40]1.12.8.22.1
Table 1.12.8.22 shall apply to Chapter 40 entitled Dust
Explosion and Fire Prevention. No work or activity described in
Table
1.12.8.22 shall be performed until such time as a valid permit has
been issued.
Table 1.12.8.22 Permits Required
Chapter 40 |
Dust Explosion and Fire
Prevention |
Work/Activity |
Issuing Authority |
Code Section |
An operation that uses or produces combustible
dust. |
Head of Fire Department |
40.2 |
1.12.8.23
Welding, Cutting and Other
Hot Work. [Chapter 41]1.12.8.23.1
Application for a Permit.
1.12.8.23.1.1 A permit application shall
specify the time and exact location of the work to be performed, the nature of
the work to be done, and any special precautions to be taken during that
work.
1.12.8.23.1.2 On the permit
application, the applicant shall provide written authorization, signed by the
property owner or his agent.
1.12.8.23.2
Permit Requirements.
1.12.8.23.2.1 A single permit shall be
permitted to be issued for both operation and storage.
1.12.8.23.2.2 For daily activities, an annual
hot work permit shall be permitted if in compliance with Section
41.7.
1.12.8.23.2.3 A permit
prescribed by the Head of the Fire Department shall be required before
conducting hot work processes in other than a designated area.
1.12.8.23.2.3.1 A permit prescribed by the
State Fire Marshal shall be used for hot work performed in other than
designated areas.
1.12.8.23.2.3.2
Replace with the following:
1.12.8.23.2.3.2 Before hot work operations
begin in a non-designated location, a written hot work permit by the Permit
Authorizing Individual (PAI) shall be required.
1.12.8.23.2.3.2.1
See Section
41.3.5.1.1.1 for sample hot work permit for permit required
areas.
1.12.8.23.3
Permits Not
Required.
1.12.8.23.3.1 A hot work
permit shall not be required by the Head of the Fire Department when hot work
is conducted in approved and designated areas in accordance with
Section 41.3.3.2.1.
1.12.8.23.3.1.1
See Section
41.5.4.4 Inspections permitted by the AHJ
1.12.8.23.3.2 A permit shall not be required
when the purpose of performing hot work is necessary for required maintenance.
1.12.8.23.3.2.1
See Section
41.4 entitled Sole Proprietors and Individual Operators.
1.12.8.23.3.3 Where an approved
facility hot work permit program exists that meets the requirements of Chapter
41, the permit shall be permitted to be issued for an entire facility
1.12.8.23.4
See
Chapters 60 through 75 for permitting requirements regarding hazardous
materials.
1.12.8.23.5
See
Section 16.6 for permitting requirements regarding use of
torch-applied roofing systems.
1.12.8.23.6
See Section 16.7
for permitting requirements regarding use of tar kettles.
Table 1.12.8.23 Permits Required
Chapter 41 |
Welding, Cutting, and Other Hot
Work |
Work/Activity |
Issuing Authority |
Chapter/Code Section |
Welding, Cutting and Other Hot Work |
Head of Fire Department |
41.1.5.3 |
41.3.3.2 |
Permit Authorizing Individual (PAI) |
41.3.5 |
See Section 1.12.8.23 |
1.12.8.24
Refueling (Chapter 42)
1.12.8.24.1
Application for
Permit.1.12.8.24.1.1 An application
for a permit shall be submitted by the person, firm, or corporation responsible
for the installation or construction of a motor vehicle fuel dispensing
station.
1.12.8.24.2
Permit Not Required.
1.12.8.24.2.1 A permit shall not be required
to make a connection in the fueling of gaseous fuel vehicles, replacement of a
portable container, or the filling of a stationary container.
Table 1.12.8.24 Permits Required
Chapter 42 |
Refueling |
Work/Activity |
Issuing Authority |
Code Section |
Installation or construction of a motor vehicle fuel
dispensing station |
Head of Fire Department |
42.1.2 |
See also Section
1.12.8.24 |
1.12.8.25
Refueling Cargo Tanks,
Portable Tanks or Transfer Tanks.
1.12.8.25.1
General.
1.12.8.25.1.1 All tanks shall be considered
full for the purpose of this Code.
1.12.8.25.1.2
Table
1.12.8.25 shall apply to Chapter 42 entitled refueling. A permit shall
be used, completed, and issued as a precondition before conducting any
work/activity described by Table 1.12.8.25
1.12.8.25.2
Cargo, Portable
and Transfer Tanks.
1.12.8.25.2.1 A
permit shall be required when tanks are left unattended.
1.12.8.25.2.2 Tanks shall only be left in an
area remote from buildings of habitation in such a manner required by the
AHJ.
1.12.8.25.3
Vehicles and Contents.
1.12.8.25.3.1 The Head of the Fire Department
may assume control of the tank vehicle and its contents if the owner is unable
or unwilling to remove the vehicle or its contents within a reasonable
time.
1.12.8.25.3.3
Inspections Required.
1.12.8.25.3.3.1 Transport vehicles used in
the transportation of combustible liquids shall be subject to inspection by the
AHJ.
1.12.8.25.3.4
Permits Not Required.
1.12.8.25.3.4.1 A permit shall not be
required for gasoline or other flammable petroleum product provided it is
transported in an open vehicle or in a compartment of a closed vehicle
separated from the passengers, where the total quantity does not exceed 21
gallons, provided such flammable liquid is contained in approved containers and
with no individual container exceeding seven gallons capacity.
1.12.8.25.3.4.2 A permit shall not be
required for combustible liquids transported in any open vehicle or in the
compartment of a closed vehicle separated from the passengers where the total
quantity does not to exceed 55 gallons, provided such combustible liquid is
contained in approved containers, substantial metal drums or other similar
containers.
1.12.8.25.3.7
CNG, LNG, Hydrogen, and LP-Gas (Alternative Fuels).
1.12.8.25.3.7.1
Notice of Completion
and Inspection of Work.
1.12.8.25.3.7.1.1 Upon completion of an
installation or connection, the person, firm or corporation having made the
installation or connection shall notify in writing on a form approved by the
State Fire Marshal to the Head of the Fire Department that the work has been
completed, and in conformity with the requirements of this
Code.
1.12.8.25.3.7.1.2 Upon receipt of such
notification, the AHJ shall make an inspection of the installation within a
reasonable time. If the work is found to be in accordance with this Code and,
if applicable,
502 CMR
5.00: Permit Requirements and Annual Inspection of
above Ground Storage Tanks or Containers of More than Ten Thousand Gallons
Capacity, the AHJ shall issue to the owner or occupant a permit for the
keeping, storage, manufacture or sale in connection therewith, except where
such storage is otherwise authorized by license.
1.12.8.25.3.7.2
Certificate of
Completion.1.12.8.25.3.7.2.1
See Section 1.12.8.51 for Certificate of Completion
requirements regarding alternate fuel storage installations and connections.
Table 1.12.8.25* Permits Required
Chapter 42 |
Refueling [Cargo Tanks, Portable Tanks or
Transfer Tanks] |
Work/Activity |
Issuing Authority |
Code Section |
*To store flammable and combustible
liquids. |
Head of Fire Department |
1.12.8.50 |
For dispensing motor fuel from a tank
vehicle. |
42.7.6 |
On-Demand Mobile Fueling (dispensing, or
storage) |
42.12 |
CNG, LNG, Hydrogen, and LP-Gas (Alternative
Fuels) |
42.8.2.1 |
A Table 1.12.8.25 Permits Required. Used here, "to
store" includes the parking location of Cargo Tanks, Portable Tanks, or
Transfer Tanks during nonbusiness hours. As a condition of the
flammable/combustible storage permit, the tank vehicle should comply with NFPA
385 as referenced in Sections 42.7.2.2.1 and
42.7.6.2, the conditions of Section 42.15, and the
requirements of 49 CFR, Transportation. Each tank vehicle should be
specifically identified on the storage permit.
1.12.8.25
Marine Fueling. [Chapter 42]
1.12.8.25.1
Permit Holder. A
permit holder shall comply with following:
(1)
The permit holder of every marine fueling facility shall designate one or more
persons to be an authorized marine fueling operator.
(2) Each marine fueling operator shall be as
described in Section 1.12.8.26.2
(3) The permit holder shall keep a written
record for each authorized marine fueling operator.
(a) Such written record shall be maintained
for a period of three years.
(b)
Such written records shall include the following information:
1. The name, home address, telephone number,
and age;
2. The date and location
of the training;
3. A summary of
the training program topics;
4. A
dated signature of the employee administering the training; and
5. A dated signature from the employee
receiving the training.
1.12.8.25.2
Marine Fueling
Operator. The operator shall be 18 years of age or older and responsible
for the oversight of the actual fueling activity conducted by the marine
fueling facility and shall comply with the following:
(1) The operator shall be the permit holder
or shall be an agent or employee under the direct control or supervision of
said permit holder.
(2) All marine
fueling operator shall be adequately and properly trained prior to conducting
any fueling activity.
(3) Training
shall be conducted at least on an annual basis and at a minimum, shall include
the following areas:
(a) Familiarity of
Chapter 42 of this Code;
(b) The properties and hazards of flammable
and combustible liquids;
(c)
Handling precautions for flammable and combustible liquids;
(d) The manufacturers' operating instructions
for operating all fueling equipment (pumps, nozzles, controls, emergency
shutoff, etc.) and related equipment; and
(e) Familiarity with the operation and
location of all fueling equipment and of all emergency equipment and
procedures, including:
1. Emergency
notifications (for mobile operators site by site specific);
2. Evacuation procedures;
3. Emergency shutoff equipment location and
operation;
4. Fire extinguisher
locations and operations;
5.
Location and proper operation of any extinguishing systems; and
6. Standby for the arrival of emergency
responders.
1.12.8.26.3 Table 1.12.8.26 shall apply to
Chapter 42.9 entitled
Marine Fueling. No work or activity
described in
Table 1.12.8.26 shall be performed until such
time as a valid permit has been issued.
Table 1.12.8.26 Permits Required
Chapter 42 |
Refueling [Marine Fueling] |
Activity |
Issuing Authority |
Code Section |
The dispensing, transferring of fuel at marine
fueling facilities. |
Head of Fire Department or
State Fire Marshal |
42.9.1.4 |
To construct or alter a new or existing marine
fueling facility. |
To maintain a fueling facility. |
See also Section
1.12.8.26 |
1.12.8.27
Spraying, Dipping, and
Coating Using Flammable or Combustible Materials. [Chapter 43]
1.12.8.27.1
Prohibited Products.
1.12.8.27.1.1 The use of any clear or
pigmented wood finish formulated with nitrocellulose or synthetic resins to dry
by evaporation and without chemical reaction, having a flashpoint below 100
°F, and having a vapor pressure not exceeding 40 psi at 100°F,
including clear lacquer or sanding sealers, shall be prohibited. [M.G.L. c. 94,
§ 329]
1.12.8.27.2
See Chapters 60 through 75 for permitting requirements
regarding hazardous materials.
1.12.8.27.3
Table 1.12.8.27
shall apply to Chapter 43 entitled Spraying, Dipping, and Coating Using
Flammable or Combustible Materials. A permit shall be used, completed, and
issued as a precondition before conducting any work/activity described by
Table 1.12.8.27
Table 1.12.8.27 Permits Required
Chapter 43 |
Spraying, Dipping, and Coating Using Flammable
or Combustible Materials |
Work/Activity |
Issuing Authority |
Chapter |
Storage, use or handling of hazardous
materials |
Head of Fire Department |
43.1.1.4 |
See Section 1.12.8.27 |
1.12.8.28
Chapter 44
Reserved
1.12.8.29
Combustible Fibers. [Chapter 45]
1.12.8.29.1 No permit shall be required for
the agricultural storage of combustible fibers.
1.12.8.29.2
Table 1.12.8.29
shall apply to Chapter 45 entitled
Combustible Fibers. No work
or activity described in
Table 1.12.8.29 shall be performed
until such time as a valid permit has been issued.
Table 1.12.8.29 Permits Required
Chapter 45 |
Combustible Fibers |
Work/Activity |
Issuing Authority |
Code Section |
For storage or handling of combustible fibers >=
100 ft.3 (2.8
m3) |
Head of Fire Department |
45.1.4 |
See also Section
1.12.8.29 |
1.12.8.30
Chapter 50
Reserved
1.12.8.31
Industrial Ovens and Furnaces. [Chapter 51]
1.12.8.31.1
Table 1.12.8.31
shall apply to Chapter 51, entitled
Industrial Ovens and
Furnaces. No work or activity described in
Table
1.12.8.31 shall be performed until such time as a valid permit has
been issued.
Table 1.12.8.31 Permits Required
Chapter 51 |
Industrial Ovens and
Furnaces |
Work/Activity |
Issuing Authority |
Code Section |
Installation and operation of an industrial oven, or
industrial furnace. |
Head of Fire Department |
51.1.2 |
1.12.8.32.
Energy Storage Systems.
[Chapter 52]1.12.8.32.1
Table
1.12.8.32 shall apply to Chapter 52, entitled
Energy Storage
Systems. No work or activity described in
Table
1.12.8.32 shall be performed until such time as a valid permit has
been issued.
Table 1.12.8.32 Permits Required
Chapter 52 |
Energy Storage Systems |
Work/Activity |
Issuing Authority |
Code Section |
To install and operate energy storage systems having
a capacity greater than the quantities listed in Table 1.3 of NFPA
855. |
Head of Fire Department |
52.1.2 |
1.12.8.34
Hazardous Material. [Chapter
60]1.12.8.34.1
Permit
Requirements.(1) A permit holder shall
apply for the renewal on an annual basis.
(2) A new permit shall be required prior to
engaging in any new or modified hazardous material process activity, which
results in a change to a different process category authorized by the current
permit.
1.12.8.34.2
Process or Processing of any Hazardous Material at any Facility.
(1) A permit shall be required for the
process or processing of any hazardous material at any facility identified in
this Code as Category 2 through Category 5, as described in
Chapter 60.
(2) The AHJ may require
technical assistance in accordance with Section 1.15 to
evaluate the adequacy of a Category 3 or Category 4 facility process safety
conditions, programs, procedures, and practices undertaken at the facility, but
only after a notice of denial has been properly served upon the person making
application.
1.12.8.34.3
Table 1.12.8.34 shall apply to Chapter 60 entitled Hazardous
Materials. No work or activity described in
Table 1.12.8.34
shall be performed until such time as a valid permit has been issued.
Table 1.12.8.34 Permits Required
Chapter 60 |
Hazardous Material |
Work/Activity |
Issuing Authority |
Code Section |
Process or Processing of any Hazardous Material in
Category 2, 3, 4, and/or 5. |
Head of Fire Department |
Section 60.8.1.1.1 |
Crop ripening or color processing. |
Head of Fire Department |
60.8.4 |
Where that process involves the storage, handling,
and use of a flammable compressed gas |
63.1.2 |
Where that process involves the storage, handling,
and use of a combustible or flammable liquid |
66.1.5 |
See also Section
1.12.8.34 |
See Table 1.12.8.50 |
1.12.8.35
Aerosol Products. [Chapter
61]1.12.8.35.1
Permit
Requirement.
1.12.8.35.1.1 A permit
shall be required based on the aggregate quantity.
1.12.8.35.2
Permit Not Required.
1.12.8.35.2.1 A permit shall not be required
for level 1 aerosol products.
1.12.8.35.3
Table 1.12.8.35
shall apply to Chapter 61 entitled Aerosol Products. No work or activity
described in
Table 1.12.8.35 shall be performed until such
time as a valid permit has been issued.
Table 1.12.8.35 Permits Required
Chapter 61 |
Aerosol Products |
Work/Activity |
Issuing Authority |
Code Section |
Storage > 500 lbs. |
Head of Fire Department |
61.1.2 |
See also Section
1.12.8.35 |
1.12.8.36
Chapter 62
Reserved
1.12.8.37
Compressed Gases and Cryogenic Fluids. [Chapter 63]
1.12.8.37.1 Permits shall be required in
accordance with Tables 1.12.8.37(a), (b) and
(c).
1.12.8.37.2
See Chapters 41, 42, 60, 63, and 69 for additional
requirements and exceptions.
Table 1.12.8.37(a) Permits Required
Chapter 63 |
Compressed Gases and Cryogenic
Fluids |
Work/Activity |
Issuing Authority |
Code Section |
Storage of compressed gases Inside of a
building/Outside of a building. |
Head of Fire Department |
63.1.2
See Table 1.12.8.50
See Tables 1.12.8.37(b) and
(c) |
Table 1.12.8.37(b) Permit Amounts for Compressed
Gases
Type of Gas |
Amount* |
ft.3 |
m3 |
Corrosive |
>=00 |
>= 0.5.7 |
Flammable |
>=200 |
>= 0.5.7 |
Highly toxic |
Any amount |
Inert and simple asphyxiant |
>=6000 |
>=169.9 |
Oxidizing (including oxygen) |
>=504 |
>=14.3 |
Pyrophoric |
Any amount |
Toxic |
Any amount |
Unstable (reactive) |
Any amount |
*Cubic feet measured at normal temperature and pressure.
Table 1.12.8.37(c) Permit Amounts for
Cryogens
Type of
Cryogen |
Inside Building
(gal.) |
Outside Building
(gal.) |
Corrosive |
Over 1 |
Over 1 |
Flammable |
Over 1 |
60 |
Toxic/highly toxic |
Over 1 |
Over 1 |
Nonflammable |
60 |
500 |
Oxidizer (includes oxygen) |
10 |
50 |
1.12.8.38
Chapter 64
Reserved
1.12.8.39
Blasting, Explosives, Fireworks, and Model Rocketry. [Chapter 65]
1.12.8.39.1
Explosives and
Blasting.
1.12.8.39.1.1
Permit
Requirements. Compliance with the following shall be required:
(1) For the purpose of obtaining a permit,
the capacity of a storage magazine, in pounds, shall be the maximum constructed
storage capacity of the magazine as reported to the Bureau of Alcohol Tobacco,
Firearms and Explosives (ATF).
(2)
An application for a permit to conduct a blasting operation shall include the
submittal of an Explosives User's Certificate and a Certificate of
Competency.
(3) No permit to
detonate explosives shall be issued until compliance with M.G.L. c. 82
§§ 40-40E, has been established by the applicant.
(4) Such permit shall remain in effect for a
minimum of 30 days, unless extended, suspended, or revoked.
(5) For deliveries of explosive materials to
any magazine, building, or structure shall be in accordance with M.G.L. c. 148,
§ 12.
1.12.8.39.1.1.1
Sale or Transfer. Compliance with the following shall be required
for permits:
(1) The transferee shall
immediately apply for a new permit for the magazine, building or
structure.
(2) Any owner shall
notify the State Fire Marshal immediately of the sale or transfer of a
magazine, building or structure. The owner shall remove the permit number from
the magazine, building or structure upon sale or transfer.
1.12.8.39.1.1.2
Application to
Manufacture.
1.12.8.39.1.1.2.1
Applicants for a permit to manufacture explosives shall submit proof of a valid
license to manufacture explosives materials, which has been issued in
accordance with 27 CFR Part 55, entitled Commerce in
Explosives, and as applicable, a license and/or registration, to keep, store,
manufacture or sell explosive material, issued in accordance with M.G.L c. 148,
§ 13.
1.12.8.39.1.1.3
Information Required
for Application1.12.8.39.1.1.3.1 An
applicant for a permit to manufacture Explosives shall provide the following
information:
(1) The name of the owner and/or
occupant;
(2) A site plan, which is
drawn to scale, and details the arrangement of buildings and magazines, paths
of egress from each, their relative location to other buildings and property
lines, and the location(s) where explosives manufacturing will take
place;
(3) The names and maximum
quantities of any/all explosives, raw materials, and finished products
anticipated to be on site;
(4) The
manner in which the listed explosives, raw materials, and finished products are
the be kept, stored, and/or used;
(5) The nature of work to be carried out in
each building.
1.12.8.39.1.1.4
Permits Not
Required. Permits shall not be required for the following:
(1) For smokeless propellants displayed in
commercial establishments intended for sale and not exceeding 25 lbs. and
stored in original manufacturer's containers of one lb. maximum
capacity.
(2) Small arms
ammunition, primers, smokeless propellants and black powder stored in original
containers and stored in a locked cabinet, closet or box when not in use as
provided in Section 1.12.8.50. Small arms ammunition, as used
here, shall mean any shotgun, rifle, or pistol cartridge and any cartridge or
propellant actuated devices, excluding military ammunition containing bursting
charges or incendiary, tracer, spotting, or pyrotechnic projectiles.
1.12.8.39.1.1.5
Notification.1.12.8.39.1.1.5.1
For each day in which any blasting operations are to be performed, notification
shall be given to the head of the fire department at least two hours prior to
such operations, if required by the Head of the Fire Department. Failure to
notify may be cause for revocation of the permit.
1.12.8.39.2
Fireworks.
1.12.8.39.2.1
Permit Requirements. The following permit provisions shall be
complied with:
(1) An application for permit
has been submitted and shall include the submittal of a fireworks user's
certificate and a certificate of competency.
(2) The quantity and description of materials
to be used shall be listed on the permit application.
1.12.8.39.2.2
Displays.
(1) Applications shall be submitted, in
writing at least 20 days in advance of a display, unless this advance
notification requirement is waived by the Head of the Fire
Department.
(2) Upon receipt of an
application for a fireworks display, the Head of the Fire Department shall
make, or cause to be made, a review of the pertinent facts set forth in the
application and a physical inspection of the display grounds for the purpose of
determining compliance with the provisions of this
Code.
(3) These
requirements may be waived if the same display has been witnessed at similar
separate locations.
(4) Within five
(5) days of the completion of such review and inspection for a fireworks
display, the Head of the Fire Department shall transmit one copy of said
application to the State Fire Marshal and one copy to the applicant, with his
or her endorsement that the application complies with the applicable provisions
of Massachusetts General Law and this Code, or his or her reason for
withholding such endorsement.
(5)
Denial of a permit application for the use of special effects [fireworks] for
cause shall be determined by the Head of the Fire Department within 24 hours
after witnessing the preliminary display, and the applicant shall be so
notified in writing within the next 24 hours with the reasons for such denial
detailed.
(6) The Head of the Fire
Department shall notify the State Fire Marshal of substitutions of certificate
holders within two working days following the display.
(7) The applicant for the special effects
[fireworks] permit shall demonstrate the fireworks display in the presence of
the Head of the Fire Department or his designees at least four hours before the
performance at the proposed location of the performance. Notice of the
demonstration shall be given to the Head of the Fire Department at least four
days in advance documenting the date and time of such demonstration.
1.12.8.39.2.3
Permit Not
Required.1.12.8.39.2.3.1 A permit
shall not be required for the transporting [interstate] of such fireworks or
pyrotechnic materials if it is in accordance with U.S. DOT, Title 49
CFR.
1.12.8.39.2.4
Cannon Mortar.1.12.8.39.2.4.1
Permits Requirements.
1.12.8.39.2.4.1.1 A permit for the
supervision of the firing of a cannon shall not be issued unless the person
holds a valid Certificate of Competency.
1.12.8.39.2.4.3
Application.
(1) Applications shall be submitted
indicating where the supervised firing is to take place not less than 15 days
in advance of firing date, and shall state whether blank-fire or live-fire is
utilized.
(2) Submission of this
application is an assurance that the cannons to be fired will be inspected by
the competent operator and meets all safety requirements prior to
firing.
1.12.8.39.2.5
Permits Not
Required.1.12.8.39.2.5.1 Persons
holding a Certificate of Competency for cannons shall be allowed to store less
than 50 lbs. of black powder.
Table 1.12.8.39 Permits Required
Chapter 65 |
Blasting, Explosives, Fireworks, Model Rocketry
and Flame Effects |
Work/Activity |
Issuing Authority |
Code Section/M.G.L. |
Black Powder/Blasting/Explosives/Model
Rocketry/Pyrotechnics/Cannons/Flame Effects |
Display of Fireworks Supervision of the use of
explosives, fireworks and cannon mortar. |
Head of Fire Department |
65.2.3 |
Storage and manufacturing of
fireworks. |
State Fire Marshal |
A vehicle carrying explosive materials left
unattended and parked in an authorized area. |
Head of Fire Department |
Pyrotechnics before a proximate
audience. |
65.3.3 |
Flame effects before an audience. |
65.4.1.1
65.4.2 |
Fireworks manufacturing.
M.G.L. c. 148, § 12 |
State Fire Marshal |
65.5.1.2 |
Model rocketry including storage of solid propellant
model rocket motors, reloading kits, or motor components > 50 lbs. (23 kg)
net weight at a residence. |
Head of Fire Department |
65.6.1 |
High power rocketry, including storage of high power
model rocket motors, motor reloading kits, and pyrotechnic
modules. |
Head of Fire Department |
Section 65.8.2 |
Explosives including manufacturing and storage of
explosive materials.
M.G.L. c. 148, § 12 |
State Fire Marshal |
65.9.2.1 |
Blasting. |
Head of Fire Department |
65.9.2.2 |
Keeping and the storage of explosives. M.G.L. c. 148,
§ 13 |
State Fire Marshal |
65.9.2.1 |
Transportation [Intrastate]. M.G.L. c. 148, §
13 |
State Fire Marshal and Head of Fire
Department |
65.9.2.1 |
Storage of in any magazine, building or
structure. |
State Fire Marshal |
65.9.2.1 |
Delivery of fireworks to authorized
personnel. |
Head of Fire Department |
65.9.6.3 |
Cannon or Mortar Firing. |
65.11.2 |
See also Section
1.12.8.39 |
1.12.8.40
Flammable and Combustible
Liquids. [Chapter 66]
1.12.8.40.1
Permit Requirement.
1.12.8.40.1.1
Transport a Tank to a
Tank Yard.1.12.8.40.1.1.1 To transport
a tank to an approved tank yard, the person requesting the permit shall provide
the permit-granting authority (Head of the Fire Department) with notification
of the designated site of disposition.
1.12.8.40.1.1.2
Receipt of
Delivery.1.12.8.40.1.1.2.1 Any person
granted a permit to remove an installed tank shall, within 72 hours, provide a
receipt for delivery of said tank to the site designated on the
permit.
1.12.8.40.1.2
Inspection of
Tanks. The Head of the Fire Department shall periodically inspect
existing above ground tank installations for safety, and if he determines that
the installation or operation constitutes a hazard, he shall require unsafe
tanks to be removed from service.
1.12.8.40.1.3
Removal of Tanks and
Underground Piping.1.12.8.40.1.3.1
Within 24 hours after the removal of an underground tank and underground
piping, the owner shall acquire a measurement for the presence of a release of
oil or hazardous materials to the environment where contamination is most
likely to be present on the site and, if requested, submit such documented
measurements to the AHJ
1.12.8.40.1.3.2 If contamination is found,
the owner shall immediately notify the Head of the Fire Department as well as
the Department of Environmental Protection.
1.12.8.40.2
Abandoned Tanks and
Piping.1.12.8.40.2.1 Abandoned tanks
and piping shall be removed.
1.12.8.40.2.2 Abandoned, as used here, means
any tank and piping without use, either filling or draw off for a continuous
period:
(1) Any tank< 10,000 gallons for a
continuous period in excess of 12 months.
(2) Any above ground storage tank >10,000
gallons for a continuous period in excess of 60 months and in compliance with
502 CMR
5.00
: Permit and Inspection Requirements of
Above-ground Storage Tanks of More than Ten Thousand Gallons Capacity.
Table 1.12.8.40 Permits Required
Chapter 66 |
Flammable and Combustible
Liquids |
Work/Activity |
Issuing Authority |
Chapter/Code Section/M.G.L. |
Construction, maintenance or use of any aboveground
storage tank >10,000 gallons capacity, in aggregate. M.G.L. c. 148, §
37 502 CMR
5.00: Permit and Inspection Requirements of
Aboveground Storage Tanks of More than Ten Thousand Gallons
Capacity |
State Fire Marshal |
To keep, store, manufacture, handle flammables or
combustible liquids. |
Head of Fire Department |
66.1.5 |
Installation, maintenance, and storage of waste oil
storage tanks. |
66 |
Storage of alcohol based hand rub preparations >=
ten gallons. |
66 |
Removal of tanks and underground
piping. |
66 |
Abandoned tanks. |
66 |
See Section 1.12.8.40 |
1.12.8.41
Flammable Solids. [Chapter
67]
Table 1.12.8.41 Permits Required
Chapter 67 |
Flammable Solids |
Work/Activity |
Issuing Authority |
Code Section |
Storage of Flammable solids |
Head of Fire Department |
67.1.2 |
1.12.8.42
Chapter 68
Reserved.
1.12.8.43
Liquid Petroleum Gases and Liquefied Natural Gas. [Chapter 69]
1.12.8.43.1 Application for a Permit.
1.12.8.43.1.1 An application for a permit
shall be submitted by the person, firm or corporation who will make the
installation or connection to an LP-gas storage container, in the name of the
owner or occupant of the premises.
1.12.8.43.1.2
Notice of Completion and
Inspection of Work.1.12.8.43.1.2.1
Upon receipt of notification of completion of the work, the AHJ shall make an
inspection of the installation within a reasonable time. If same is found to be
in accordance with Chapter 69 and if applicable
502 CMR
5.00, the AHJ shall issue to the owner or occupant a
permit for the keeping, storage, manufacture or sale of LP-gas in connection
therewith, except where such storage is otherwise authorized by
license.
1.12.8.43.1.2.2
Violation.1.12.8.43.1.2.2.1 If
such installation is found not to be in accordance with Chapter 69, the permit
shall be withheld and shall not be issued until the proper corrections have
been made as directed, by written notice if requested, within a reasonably
specified time and prior to any LP-gas being stored in the
container(s).
1.12.8.43.1.2.2.2
Permits for the storage are considered null and void if such containers are
considered abandoned. Where containers are abandoned they shall be removed, as
provided in Table 1.12.8.43. If permitted by the AHJ, such
container may be reused in accordance with
1.12.8.43.1.1.
1.12.8.43.1.3
Certificate of
Completion.1.12.8.43.1.3.1
See
Section 1.12.8.51 for Certificate of Completion requirements regarding
LP- gas storage installations and connections.
1.12.8.43.2
Permits Not
Required.1.12.8.43.2.1 No permit shall
be required to make a connection in the replacement of a portable container, or
the filling of a stationary container.
Table 1.12.8.43 Permits Required
Chapter 69 |
Liquid Petroleum Gases and Liquefied Natural
Gas |
Work/Activity |
Issuing Authority |
Code Section |
Storage, use and handling and the installation or
modification of stationary installations. |
Head of Fire Department |
69.1.2 |
Keeping, removal, storage or use of LP-gas >42 lbs
aggregate capacity. |
See also Section
1.12.8.43 |
1.12.8.44
Chapter 70
Reserved.
1.12.8.45
Chapter 71 Reserved.
1.12.8.46
Chapter 72
Reserved.
1.12.8.47
Chapter 73 Reserved.
1.12.8.48
Ammonium Nitrate.
1.12.8.48.1 If applicable, permits shall
comply with the requirements of Chapter 65.
1.12.8.49
Chapter 75
Reserved.
1.12.8.50
Quantities, Permits and License Requirements.
1.12.8.50.1 The activities and aggregate
quantities listed in Table 1.12.8.50 shall be used in
determining permit and/or license thresholds.
1.12.8.50.2 All tanks, containers, vessels
and transport vehicles are to be considered full for the purpose of permitting
under this Code and under M.G.L. c. 148, §
13.
1.12.8.50.3
This section shall not apply to Class II and III liquids that are not heated to
or above their flash points and:
(1) That have
no fire point when tested by ASTM D 92, up to the boiling point of the liquid
or up to a temperature at which the sample being tested shows an obvious
physical change, or
(2) That are in
a water-miscible solution or in dispersion with a water and inert
(noncombustible) solids content of more than 80% by weight, which do not
sustain combustion when tested using the "Method of Testing for Sustained
Combustibility", per 49 CFR
173, Appendix H, or the UN
Recommendations on the Transport of Dangerous Goods.
1.12.8.50.4 If a license is
required based on the limits set forth in Table 1.12.8.50, it
shall be issued in accordance with M.G.L. c. 148, § 13.
1.12.8.50.5 A permit shall be obtained in
accordance with Table 1.12.8.1 through Table 1.12.8.50 as
applicable.
1.12.8.50.6 When
storing more than one class of liquid or other materials named in Table
1.12.8.50, a license shall only be required for the individual class
or materials, which exceed the amounts listed.
1.12.8.50.7 Explosive material classified as
Division 1.5 and 1.6 shall not be regulated as an explosive in determining
capacities subject to license requirements of M.G.L c. 148, § 13.
Table 1.12.8.50 Permit and/or License
Thresholds
Materials |
Quantities |
Permit |
License |
Class 1 liquids
Note 1: Gasoline may be used, kept, or stored in any
building not used for habitation nor frequented by the public, # 7 gallons and
provided the gasoline is stored in one or more approved containers without
permit.
Note 2: See alcohol based hand rub
Table 1.12.8.1.
* Note 3: No permit or license needed when stored in
portable tanks over 60 gallons capacity not intended for fixed use, including
intermediate bulk containers (IBCs) designed for mechanical handling.
* Note 4: No permit or license needed when stored in
portable tanks over 60 gallons capacity not intended for fixed use, including
intermediate bulk containers (IBCs) designed for mechanical
handling. |
< 793 Gallons* |
yes |
no |
>= 793 gallons |
yes |
yes |
Class I liquids (in fixed storage containers)
**Note: No permit or license needed for storage tanks
having a liquid capacity that exceeds 60 gallons capacity, intended for fixed
installation and not used for processing. |
<10,000 gallons** |
yes |
no |
>= 10,000 gallons |
yes |
yes |
Class II liquids. |
< 10,000 gallons |
yes |
no |
>= 10,000 gallons |
yes |
yes |
Class IIIA liquids. |
< 10,000 gallons |
yes |
no |
>= 10,000 gallons |
yes |
yes |
Class IIIB liquids. |
< 10,000 gallons |
yes |
no |
>= 10,000 gallons |
yes |
yes |
Flammable Solids. |
< 100 lbs. |
yes |
no |
>= 100 lbs. |
yes |
yes |
Flammable gases (within a building). |
< 3,000 cubic feet |
yes |
no |
>= 3,000 cubic feet |
yes |
yes |
Flammable gases (outside a building). |
< 10,000 cubic feet |
yes |
no |
>= 10,000 cubic feet |
yes |
yes |
Fuel oil that may be kept for use in a building or
other structure. |
< 10,000 gallons of light or of
heavy |
yes |
no |
>= 10.000 gallons of light or of
heavy |
yes |
yes |
Small arms ammunition of rim fire ammunition.
[private use] |
< 10,000 rounds |
no |
no |
>= 10.000- 30,000 rounds |
yes |
no |
>= 30,000 rounds |
yes |
yes |
Small arms ammunition of center fire ammunition.
[private use] |
< 10,000 rounds |
no |
no |
>= 10,000- 50,000 rounds |
yes |
no |
> 50,000 rounds |
yes |
yes |
Small arms ammunition of shotgun ammunition. [private
use] |
< 5,000 rounds |
no |
no |
>= 5,000 rounds- 50,000 rounds |
yes |
no |
> 50,000 rounds |
yes |
yes |
Small arms ammunition primers. [private
use] |
< 10,000 caps or other small arms
primers |
no |
no |
>= 10,000 caps or other small arms
primers |
yes |
yes |
Small arms ammunition primers. [commercial
use] |
< 100,000 caps or other small arms
primers |
yes |
no |
>= 100,000 caps or other small arms
primers |
yes |
yes |
Smokeless propellants. [private]
Note 1: Persons younger than 18 years old may not
keep or store smokeless propellants.
Note 2: Not more than two pounds of such propellant
shall be stored in a multiple family dwelling or a building of public
access. |
< 16 lbs. |
no |
no |
Smokeless propellants. [private] |
16 lbs. through 47 lbs. |
yes |
no |
>= 48 lbs. |
yes |
yes |
Smokeless propellants. [commercial] |
>= 16 lbs. through < 99 lbs. |
yes |
no |
>= 100 lbs. |
yes |
yes |
Black powder. [private]
Note: Persons younger than 18 years old may not keep
or store any amount of black powder. |
<= 2 lbs |
no |
no |
> 2 lbs. through < 5 lbs. |
yes |
no |
<= 5 lbs. |
yes |
yes |
Black powder. [commercial]
See Section 1.12.8.39.2.5.1 for
permit exempted individual. |
< 50 lbs. |
yes |
no |
>= 50 lbs. |
yes |
yes |
Special industrial explosive devices. |
< 50 lbs. net weight of explosives |
no |
no |
>= 50 lbs. net weight of
explosives |
yes |
yes |
Explosive material.
Note: Fireworks can be stored up to 30 days without a
land license. |
Classified Division 1.1 - 1.6 |
yes |
yes |
LP-gas. |
< 42 lbs. [10 gallons] |
no |
no |
>= 42 lbs. [10-gallons] through 2,000
gallons |
yes |
no |
> 2,000 gallons of LP-gas in the
aggregate |
yes |
yes |
Flammable or class II combustible liquids unattended
within cargo tanks, portable tanks or transfer tanks on a parcel of land. This
shall not apply to parcels of land permitted by the Head of the Fire Department
prior to September 1, 2008. |
<= 15,000 gallons in the aggregate |
yes |
no |
> 15,000 gallons in the aggregate |
yes |
yes |
1.12.8.50
Certificates of
Completion. A certificate of completion shall be filed as provided in
Table 1.12.8.51.1.12.8.50.1
A person making the installation or connection of an oil burner, alternate fuel
installation, or LP-gas installation shall within 72 hours (excluding Saturday,
Sunday and holidays) after test-firing the burner, file such Certificate of
Completion with the Head of the Fire Department.
1.12.8.50.2
Inspection. Upon
receipt of a Certificate of Completion, the Head of the Fire Department shall
make an inspection of the installation within a reasonable time, and if same is
found to be in accordance with this
Code, the AHJ shall issue
to the owner or occupant an applicable permit.
Table 1.12.8.51 Certificates Required for
Permit
Chapters 11, 42 and 69 |
Certificates of Completion |
Type |
Oil Burner Technician [Chapter
11] |
Upon completion, the person, firm or corporation
having made the installation or connection: |
Shall certify in writing on a form approved by the
State Fire Marshal to the Head of the Fire Department that the work has been
completed, and is in conformity with the requirements of this
Code. |
CNG, LNG, Hydrogen, and LP-Gas Alternate Fuels
[Chapter 42] |
Upon completion of an installation or connection the
person, firm or corporation having made the installation or
connection: |
Shall certify in writing on a form approved by the
State Fire Marshal to the Head of the Fire Department that the work has been
completed, and in conformity with the requirements of this
Code. |
LP-gas [Chapter 69] |
Upon completion of an installation or connection the
person, firm or corporation having made the installation or
connection: |
Shall certify in writing on a form approved by the
State Fire Marshal to the Head of the Fire Department that the work has been
completed, and in conformity with the requirements of this
Code. |
See Section 1.12.8.51 |
1.12.8.51
Certificates of
Completion. A certificate of completion shall be filed as provided in
Table 1.12.8.51.1.12.8.51.1
A person making the installation or connection of an oil burner, alternate fuel
installation, or LP-gas installation shall within 72 hours (excluding Saturday,
Sunday and holidays) after test-firing the burner, file such Certificate of
Completion with the Head of the Fire Department.
1.12.8.51.2
Inspection. Upon
receipt of a Certificate of Completion, the Head of the Fire Department shall
make an inspection of the installation within a reasonable time, and if same is
found to be in accordance with this
Code, the AHJ shall issue
to the owner or occupant an applicable permit.
Table 1.12.8.51 Certificates Required for
Permit
Chapters 11, 42 and 69 |
Certificates of
Completion |
Type |
Oil Burner Technician [Chapter
11] |
Upon completion, the person, firm or corporation
having made the installation or connection: |
Shall certify in writing on a form approved by the
State Fire Marshal to the Head of the Fire Department that the work has been
completed, and is in conformity with the requirements of this
Code. |
CNG, LNG, Hydrogen, and LP-Gas Alternate Fuels
[Chapter 42] |
Upon completion of an installation or connection the
person, firm or corporation having made the installation or
connection: |
Shall certify in writing on a form approved by the
State Fire Marshal to the Head of the Fire Department that the work has been
completed, and in conformity with the requirements of this
Code. |
LP-gas |
[Chapter 69] |
Upon completion of an installation or connection the
person, firm or corporation having made the installation or
connection: |
Shall certify in writing on a form approved by the
State Fire Marshal to the Head of the Fire Department that the work has been
completed, and in conformity with the requirements of this
Code. |
See Section 1.12.8.51 |
1.13
Certificates.
1.13.1
Authorization. The State
Fire Marshal shall have the authority to require certificates and collect fees
for individuals or companies performing any of the following activities.
(1) Sale, manufacture, possession or use of
explosive materials, blasting operations, firework displays, storage of
fireworks, or use of pyrotechnics or special effects before a proximate
audience; see Sections 1.13.10 and 1.13.11, and Chapter
65
(2) Inspection, servicing, or
recharging of portable fire extinguishers; see Section 1.13.5
and Chapter 13
(3) Installation,
servicing, or recharging of fixed fire extinguishing systems; see
Section 1.13.5 and Chapter 13
(4) Cleaning and inspection of commercial
cooking operations; see Section 1.13.8 and Chapter
50
(5) Operating self-service gas
stations; see Section 1.13.12 and Chapter 42
(6) Operating marine fueling facilities and
mobile marine fueling vehicles; Chapter 42
(7) Transportation of any combustible liquid;
Chapter 42
(8) Crowd management
services; see Section 1.13.6 and Chapter 20
(9) Activities related to the operation and
firing of muzzle-loading cannons; see Section 1.13.9 and
Chapter 65
(10) Altering,
repairing, or installing oil burning equipment; see Section
1.13.7 and Chapter 11
1.13.1.1 No person shall conduct a business
or engage in the work or activity prescribed in Section 1.13,
unless the appropriate certificate(s), as required in Sections 1.13.5
through 1.13.13, have been issued, and that such certificate is not
expired, suspended, revoked, or fee not paid.
1.13.1.2 The following provisions shall apply
to each certificate issued by the State Fire Marshal:
(1) Certificates shall be issued in such form
as prescribed by the State Fire Marshal;
(2) Certificates shall not be
transferable;
(3) Certificates
shall be issued for the period of time as indicated on the
certificate;
(4) Address change
shall be reported in writing to the State Fire Marshal's Office within 14 days
of such change to maintain validity of the affected certificate;
(5) A Certificate shall not be issued to
anyone younger than 18 years old;
(6) Any individual or company to whom a
certificate has been issued shall, upon request, produce and show proper
identification and the certificate to the AHJ or anyone for whom that
individual or facility seeks to render services;
(7) Certificates shall not be
altered;
(8) Any evidence of
alteration of any certificate shall render the certificate invalid. Altered
certificates shall be surrendered to the State Fire Marshal or his or her
designee; and
(9) Any insurance
company providing coverage shall be licensed in the Commonwealth of
Massachusetts by the Commissioner of Insurance.
1.13.1.3 Any individual or entity, who holds
a permit, certificate, or registration issued by the State Fire Marshal to
perform an activity prescribed in this chapter, shall constitute agreement and
consent by the individual or entity holding the permit, certificate, or
registration, to allow the State Fire Marshal to enter the premises at any
reasonable time to conduct such inspection, or review such records, as they
pertain to conformity with this Code, and/or the performance of activities
conducted pursuant to such permit, certificate, or registration.
1.13.1.3.1 Any individual or entity, as
described in 1.13.1.3, who fails to comply with the
requirements of 1.13.1.3, may be subject to suspension or
revocation of its permit, certificate, or registration. Such suspension or
revocation shall, where required under the provisions of M.G.L. 30A, be
effective after the individual or entity has been given adequate notice and an
opportunity to be heard.
1.13.2
Certificates Required by the
State Fire Marshal. The following certificates shall be required and
issued by the State Fire Marshal:
(1)
Certificate of Competency (CC). Issued to a person, in the
individual's name, authorizing the person named in the certificate to perform
an activity prescribed Section 1.13. The holder of a valid
Certificate of Competency must have the Certificate of Competency in his/her
possession whenever work is being performed under said Certificate of
Competency, and the Certificate of Competency shall be immediately presented to
any business interest, AHJ, or compliance officer upon request.
(2)
Certificate of Registration
(CR). Issued to a person, firm, company, or other legal entity
authorizing establishment, operation, and advertising of a business in the name
stated on the certificate that performs an activity prescribed in
Section 1.13.(a) A separate
Certificate of Registration is required for each business location.
(b) A Certificate of Registration does not
authorize the holder of the Certificate of Registration to perform work or
activities for which a Certificate of Competency is required.
(c) The holder of a Certificate of
Registration shall only advertise the name of the business as it is stated on
the Certificate of Registration. Any sign, listing, or advertisement of the
business shall display the certificate number.
(d) The holder of a Certificate of
Registration shall report annually the name, address, and Certificate of
Competency number of each certified person in his employ, in a manner
acceptable to the State Fire Marshal.
(e) Every business issued a Certificate of
Registration shall be properly equipped to perform the act or acts as permitted
by the Certificate of Registration.
(f) Each Certificate of Registration shall be
identified by type and shall bear an identifying number delineating as
MA-Certificate of Registration-(number), the "MA" indicating it is a
Massachusetts certificate.
(g) The
Head of the Fire Department shall be notified in writing by the business
conducting any service for which a certificate is required, within 48 hours of
any deficiencies found and within 48 hours of the completion of the work to
bring the system into compliance
(h) It shall be the responsibility of the
holder of a Certificate of Registration to ensure that any individual under
employ or control of the Certificate of Registration, who is required to hold a
certificate, or registration issued by the State Fire Marshal to perform an
activity prescribed in Section 13, holds a valid certificate, or registration
at the time the activity is performed.
(i) Failure by the holder of a Certificate of
Registration to comply with the requirement of 1.13.2(2)(h) may subject the
holder of the Certificate of Registration to suspension or revocation of its
Certificate of Registration. Such suspension or revocation shall, where
required under the provisions of M.G.L. 30A, be effective after the holder of
the Certificate of Registration has been given adequate notice and an
opportunity to be heard.
(3)
User Certificate (UC). A UC
is required when the holder of a valid Certificate of Registration wishes to
operate a business in a name other than the business name listed on the
Certificate of Registration. A separate UC is required for each alternate
business name that performs an activity prescribed in Section 1.13.
(a) A UC does not authorize the holder of the
UC to perform work or activities for which a Certificate of Competency is
required.
1.13.3
Application for
Certificate. Applications shall be made and submitted in a form and
manner as prescribed by the State Fire Marshal.
1.13.3.1 The State Fire Marshal or his or her
designee shall review every application for a certificate.
1.13.3.2
Examination.
1.13.3.2.1 The State Fire Marshal or his or
her designee shall administer a written exam that measures the applicant's
ability, knowledge, and skill level.
1.13.3.2.2 The State Fire Marshal shall be
permitted to allow an applicant to submit test results from an examination
given by a third-party certification entity, taken within two years of the date
of application.
1.13.3.2.2.1 The State Fire
Marshal or his or her designees shall determine if said test measures the
applicant's ability, knowledge, and skill level in a manner equivalent to or
greater than, the test administered by the State Fire Marshal.
1.13.3.2.2.2 The State Fire Marshal shall be
permitted to establish other examination criteria based on other laws and
regulations
1.13.3.2.3
The State Fire Marshal or his or her designee shall conduct an inspection to
determine that the applicant possesses the required equipment for the type of
certificate sought. A reasonable opportunity shall be given to correct any
deficiencies discovered by the inspection before the issuance of the
certificate.
1.13.3.3
Incomplete Applications. When the State Fire Marshal or his
designee determines that an application to receive a certificate is incomplete,
inadequate, or does not otherwise comply with the provisions of this
Code, policy, or any other applicable law, the State Fire
Marshal shall refuse to issue said certificate. If the refusal is based on the
applicant's inability to pass an examination given to determine competency, the
applicant may reapply in accordance with the policy of the State Fire
Marshal.
1.13.3.4
Applicants.(1) Applicants shall
meet the eligibility criteria for the applicable certificate as established by
the State Fire Marshal and provide documentation of knowledge and experience
particular to the profession as required on the application for certificate.
(2) Applicants applying for a
certificate issued under Section 1.13 shall furnish such
documents or other evidence as prescribed by the State Fire Marshal as a
condition to the issuance of such certificate.
1.13.3.5
Renewal of Certificate.
1.13.3.5.1 A certificate may be renewed upon
written request of the holder, subject to approval by the State Fire
Marshal.
1.13.3.5.2 Renewal
applications shall be accompanied by the appropriate fee and shall be submitted
at least one month in advance of the expiration date or as otherwise required
by the State Fire Marshal.
1.13.3.5.3 Applicants submitting a renewal
application shall meet the eligibility criteria for the applicable certificate
as established by the State Fire Marshal.
1.13.3.5.4 Certificates shall expire as
indicted in Table 1.13.12.
1.13.4 Revocation or Suspension of
Certificates issued by the State Fire Marshal.
1.13.4.1 The State Fire Marshal may, after
notice and opportunity for a hearing conducted by the Department, impose
administrative sanctions, including but not limited to the suspension or
revocation of any certificate, for failure by the holder to comply with any
applicable provision of this
Code and/or M.G.L. c. 148. The
State Fire Marshal may also suspend or revoke a certificate if any material
misrepresentations are knowingly submitted in the application on which issuance
of the certificate was based.
1.13.4.1.1
Administrative action shall be conducted in accordance with the requirements of
M.G.L. c. 30A.
1.13.4.1.2
Notice delivered. Any notice issued by the State Fire Marshal
under this Code, shall be deemed delivered and received by
said holder, if the notification is sent by certified mail, return receipt
requested, to the last known address of said holder, according to the records
of the State Fire Marshal at the time of such mailing.
1.13.4.1.3
Penalty for work during
suspension. Any person who engages in any work or trade regulated by
this Code, after suspension of said, certificate, or
registration issued by the State Fire Marshal shall be subject to a minimum
three-year suspension of said, certificate, or registration. Such suspension
shall, where required under the provisions of M.G.L. 30A, be effective after
the holder of the suspended, certificate, or registration has been given
adequate notice and an opportunity to be heard on the sole issue of whether the
holder of the suspended certificate, or registration engaged in work which
requires an active certificate, or registration issued by the State Fire
Marshal, pursuant to Section 1.13.
1.13.4.1.4
Penalty for allowing others
to use. Any person who knowingly loans, sells, transfers, or otherwise
allows another to use their certificate, or registration issued by the State
Fire Marshal shall be subject to permanent revocation of all certificates, or
registrations issued by the State Fire Marshal they hold, without the
eligibility for renewal. Said individual shall be permanently prohibited from
applying for and holding any certificate, or registration issued by the State
Fire Marshal in the future. Such permanent revocation and prohibition shall,
where required under the provisions of M.G.L. 30A, be effective after the
holder of said certificate, or registrations has been given adequate notice and
an opportunity to be heard.
1.13.4.1.5
Penalty for using or
possessing another's certificate or registration. Any person who
knowingly uses or possesses the certificate, or registration of another or who
otherwise falsely represents themselves as a holder of said license,
certification, or registration issued by the State Fire Marshal, shall be
permanently prohibited from applying for and holding any certificate, or
registration issued by the State Fire Marshal. Such prohibition shall be
effective, where required under the provisions of M.G.L. 30A, after adequate
notice and an opportunity to be heard.
1.13.4.1.6
Penalty for allowing
unlicensed employee to use. Any holder of a Certificate of Registration
or User Certificate who knowingly permits an unlicensed individual within their
employ to use or possess the certificate, or registration of another or to
otherwise falsely represent themselves as a holder of a license, certificate,
or registration issued by the State Fire Marshal, shall be subject to a minimum
three-year suspension of said Certificate of Registration or User Certificate.
Such suspension shall, where required under the provisions of M.G.L. 30A, be
effective after the holder of the Certificate of Registration or User
Certificate has been given adequate notice and an opportunity to be
heard.
1.13.4.1.7
Penalty for
allowing employee to violate
Code. Any holder of a
Certificate of Registration or User Certificate who knowingly permits an
individual in their employ to violate any provision of this
Code, other than Section 1.13.4.1.6, may be
subject to suspension or revocation of said Certificate of Registration or User
Certificate. Such suspension or revocation shall, where required under the
provisions of M.G.L. 30A, be effective after the holder of the Certificate of
Registration or User Certificate has been given adequate notice and an
opportunity to be heard.
1.13.4.1.8
Penalty for working after expiration. Any person who engages in
any work or trade regulated by this Code, after the expiration
of said, certificate, or registration issued by the State Fire Marshal shall be
subject to a minimum six month prohibition from applying for and holding any
license, certificate, or registration issued by the State Fire Marshal and
shall be required to take and successfully pass any and all examinations
required for such license, certificate, or registration holders, prior to
reinstatement. Such prohibition shall, where required under the provisions of
M.G.L. 30A, be effective after the holder of the expired license, certificate,
or registration has been given adequate notice and an opportunity to be heard
on the sole issue of whether the holder of the expired license, certificate, or
registration engaged in work which requires an active license, certificate, or
registration issued by the State Fire Marshal, pursuant to Section
1.13.
1.13.4.1.9
Failure to appear. Any person who is the subject of an
administrative hearing on their certificate or registration issued by the State
Fire Marshal and who fails to respond to, participate in or appear at a
scheduled hearing or otherwise defaults, shall be subject to an evidentiary
hearing in their absence. The Hearing Officer may assume the truth of the
allegations in the Notice to Suspend or Revoke and impose an
appropriate penalty on the holder of said license, certificate, or
registration. Consistent with 801 C.M.R. § 1.02(10)(d) said person shall,
within ten business days from the date of said notice of administrative action
by the State Fire Marshal, request a rescheduled hearing or the outcome of said
default hearing will be considered final.
1.13.4.1.10
Disruptive person at
hearing. Any person who is the subject of an administrative hearing on
their certificate or registration issued by the State Fire Marshal, their
counsel, witnesses, and other persons present at a hearing shall conduct
themselves in a manner consistent with the standards of decorum commonly
observed in any court. Where such decorum is not observed, the Hearing Officer
may take appropriate action. Appropriate action may include, but is not limited
to, refusal to allow a disruptive person to remain in the hearing and, if such
person is subject to an administrative hearing on their certificate, or
registration, to allow participation by representative only.
1.13.4.1.11
No renewal during pending
actions. No person shall have certificate, or registration renewed by
the State Fire Marshal, if said certificate, or registration has expired and at
the time of application for renewal, there is any administrative, court or
similar action pending pertaining to said certificate, or registration, until
all such matters have been fully resolved.
1.13.4.1.12
No renewal when fines are
outstanding. Any person with a suspended, expired, or otherwise inactive
certificate, or registration issued by the State Fire Marshal shall not have
said certificate, or registration reinstated until any and all outstanding
fines have been paid in full.
1.13.4.1.13
No renewal when inactive
more than one year. Any person with a suspended, expired, or otherwise
inactive license, certificate, or registration for more than a one (1) year
period shall not have said certificate, or registration reinstated until they
have, where applicable, retaken and successfully passed the examination
required for said certificate, or registration.
1.13.4.1.14
Hearing continuance
request. Once an administrative hearing is scheduled, continuances will
be granted only for good cause. To request a continuance, the party seeking the
continuance must submit a written request to the State Fire Marshal at least
seven (7) calendar days before the hearing. The request must include the reason
why (good cause) the party needs to postpone and how long the party has known
the good cause. Emergency requests to continue may be submitted less than seven
(7) calendar days in advance. Such emergency requests shall explain in detail
why the request could not have been filed sooner and shall contain supporting
documentation, where appropriate.
1.13.4.1.15
Penalty for failure to
surrender. Failure to surrender a suspended license, certificate, or
registration issued by the State Fire Marshal within seven (7) calendar days of
said suspension, shall result in continued suspension at the rate of one day
for each day of non-compliance. Surrender shall mean delivering the certificate
or registration in-hand to the Department of Fire Services or via first-class
mail, postmarked within seven (7) calendar days of said suspension.
1.13.4.1.16
Prohibition for applying
during suspension. Any holder of a Certificate of Registration or User
Certificate issued by the State Fire Marshal that is subject to a suspension of
said Certificate of Registration or User Certificate shall be prohibited from
applying for or holding another Certificate of Registration or User Certificate
issued by the State Fire Marshal under the same or different business name
during said suspension period. This temporary prohibition shall also apply to
any individual within the employ of or affiliated with said holder of a
Certificate of Registration or User Certificate.
1.13.4.2
Instances Involving an
Immediate Threat to Public Safety.
1.13.4.2.1 The State Fire Marshal may
immediately suspend or revoke, prior to a hearing, any certificate, or any
rights and privileges granted thereby, issued under this Code or M.G.L. c. 148,
whenever the holder thereof has committed a violation of any law, ordinance or
bylaw relating to the subject matter of M.G.L. c. 148, or any provision of this
Code, the nature of which would give the State Fire Marshal
reason to believe that the continued operation by such holder is and will be so
seriously improper as to constitute an immediate threat to the public
safety.
1.13.4.2.2 Upon such
suspension or revocation, the State Fire Marshal shall forthwith send written
notice thereof to the holder. Such notice shall specify the time and place of
the violation.
1.13.4.2.3 The State
Fire Marshal or his or her designee may order the certificate to be delivered
to him or her forthwith.
1.13.4.2.4
The certificate shall not be reissued unless, upon examination or
investigation, or after a hearing, the State Fire Marshal, or his designee
determines that the certificate may be re-issued.
1.13.4.2.5 Said holder shall be entitled to a
hearing within 30 days of the suspension or revocation.
1.13.5
Servicing
Portable Fire Extinguishers and/or Fixed Fire Extinguishing Systems. [Chapter
13]
1.13.5.1
General. To
service portable fire extinguishers and/or fixed fire extinguishing systems,
both a Certificate of Competency and a Certificate of Registration shall be
required.
1.13.5.1.1 A Certificate of
Competency shall be required for each person servicing fire extinguishers or
systems
1.13.5.1.2 A Certificate of
Registration shall be required for each firm, company, corporation or other
legal entity servicing fire extinguishers or systems.
1.13.5.1.3 Additional Certificate of
Registration shall be required for each business location.
1.13.5.2
Certificate of Competency for
Servicing Fire Extinguishers and Systems.
1.13.5.2.1 An applicant requesting a
Certificate of Competency shall comply with the following;
(1) Submit a completed application in
accordance with Section 1.13.3 for the servicing of portable
fire extinguishers and/or fixed fire extinguishing systems, identifying
applicable type of certificate (restriction(s)) to the State Fire Marshal's
Office.
(2) An application for a
Type 47 and a Type 48 Certificate of Competency shall be accompanied by a
written attestation, enumerating the applicant's technical qualifications,
competency, and experience to charge, recharge, repair, test, inspect and
service engineered or pre-engineered systems.
1.13.5.2.2
Examination for Servicing
Fire Extinguishers.(1) The State Fire
Marshal shall establish a comprehensive written examination covering state
laws, regulations and industry safety standards pertaining to this
Code.
(2) The
applicant shall successfully pass an examination as a prerequisite to the
issuance of a certificate. The examination shall consist of multiple-choice,
fill-in, true-false, or short answer questions, and may include the following
topics:
(a) Diagrams, plans or
sketches;
(b) Portable fire
extinguishers: charging, recharging, servicing, testing, and
inspecting;
(c) Engineered fixed
fire extinguishing systems: charging, recharging, altering, repairing, testing,
inspection, installation, and servicing;
(d) Pre-engineered fixed fire extinguishing
systems; and
(e) Self-service fire
extinguishing systems.
1.13.5.3
Certificate of Registration
for Servicing Fire Extinguishers and Systems.
1.13.5.3.1 An applicant requesting a
certificate for a firm, company, corporation or other legal entity shall submit
a completed application in accordance with Section 1.13.3 for
the servicing of portable fire extinguishers and/or fixed fire extinguishing
systems, identifying applicable type of restriction(s).
1.13.5.4
Service Tags.
1.13.5.4.1 The size, content, design, and
placement of service tags shall be prescribed by the State Fire
Marshal.
1.13.5.4.2 Prior to
printing a service tag, each firm holding a valid certificate of registration
shall forward one sample of the service tag to the State Fire marshal for
approval.
1.13.5.4.3 One service
tag shall be attached to each portable fire extinguisher, engineered or
pre-engineered fixed fire extinguishing system or to a vessel which has been
hydrostatically tested.
1.13.5.4.4
A service tag shall be affixed and indicate the date, initials and certificate
number of the person who conducted the most recent test.
1.13.5.4.5 Any engineered, pre-engineered and
self-service fire suppresion system inspected and found to be in noncompliance
with its listing or manufacturer's specifications shall have a service attached
indicating noncompliance.
1.13.5.4.6
Noncompliance Service
Tags.1.13.5.4.6.1 Installed
noncompliance service tags shall be bright orange, have the words
"Noncompliance" in block letters not less than 1/2 inch in height and be
black in color.
1.13.5.4.6.2 Tags
shall contain the firm name, certificate of registration number, date of
inspection, the reason for noncompliance and the initials and certificate of
competency number of the person who conducted the inspection.
1.13.5.4.7
Theft or Loss of
Service Tags1.13.5.4.7.1 Any incident
involving the loss or theft of service tag(s) must be reported to the State
Fire Marshal and the police department within the jurisdiction where the loss
or theft occurred within 72 hours. Failure to report such loss or theft shall
result in the rebuttable presumption that the holder of the tag performed or
allowed another to perform the services associated with said tag(s). Any person
who unwittingly allows another to use their service tag(s) after a prudent
license-holder would have cause to know of a loss or theft of same, or
misappropriation or misrepresentation of identity, may have their Certificate
of Competency and Certificate of Registration suspended for a minimum of two
years.
Table 1.13.5 Certificates Required
Chapter 13 |
Portable Fire Extinguishers and/or Engineered
or Pre-engineered Fixed Fire Extinguishing Systems or Performing of Hydrostatic
Testing |
Certificate of Registration and
Certificate of Competency |
Activity |
Description |
Types for business entities
[Registration] |
Types for individuals
[Competency] |
For the installation, servicing, inspection, testing
alteration, repair, and recharging.
Note: For hydrostatic testing of cylinders,
see Federal License requirements and DOT
provisions. |
Self-serve Motor Fuel Facilities. |
Type 40 |
Type 41 |
Servicing portable fire
extinguishers. |
Type 42 |
Type 46 |
Servicing engineered fixed fire extinguishing
systems. |
Type 43 |
Type 47 |
Servicing pre-engineered fixed fire extinguishing
systems. |
Type 44 |
Type 48 |
1.13.6
Crowd Managers. [Chapter
20]
1.13.6.1
General. For
an individual to manage crowds of 100 or more in a nightclub, dance hall,
discotheque or bar, a Certificate of Competency shall be required.
1.13.6.2
Certificate of Competency for
Crowd Manager.1.13.6.2.1 An applicant
requesting a Certificate of Competency shall comply with the following:
(1) Submit a completed application in
accordance with Section 1.13.3 to the State Fire Marshal's
Office;
(2) The applicant shall be
21 years of age or older;
(3) The
applicant shall receive training, as required by the State Fire Marshal;
and
(4) The applicant shall
successfully complete the training course as a prerequisite to the issuance of
a certificate.
Table 1.13.6 Certificate Required
Chapter 20 |
Crowd Manager |
Certificate of Competency |
Activity |
Description |
To an individual who will be managing crowds of 100
or more people. |
In a nightclub, dance hall, discotheque, or
bar |
1.13.7
Certificates Required by Chapter
11. In addition to the requirements set forth in
Section
1.13 the specific provisions shall apply to the types of certificates
as provided by
Section 1.13.7 (1)(a) through (c).
(1) Oil Burner Technician and Apprentice.
(a) Certificate of Competency;
(b) Certificate of Completion; and
(c) Certificate of
Compliance.
1.13.7.1*
Oil Burner Technician and Apprentice.
A.1.13.7.1
See M.G.L. c.
148, §§ 10C through 10H regarding, certificates oil burner
installations.
1.13.7.1.1 A Certificate of
Competency issued as an oil burner technician or as an apprentice shall be
issued to the individual.
1.13.7.1.2 The holder of a Certificate of
Competency as an oil burner apprentice, shall not, individually and without
supervision, perform any work or activities for which a Certificate of
Competency is required, but may assist in the performance of such work or
activities so long as the work or activities are performed under direct
supervision by an oil burner technician who holds a valid Certificate of
Competency.
1.13.7.1.3
Application.1.13.7.1.3.1
Renewal. License renewal application forms must be submitted no less
than 30 days prior to the license expiration date.
1.13.7.1.4*
Examination. Except
as provided by
Section 1.13.7.1.5.1, the examination
provisions in
1.13.3.4 shall be required as a prerequisite to
licensure.
A.1.13.7.1.4
See
the following references:
(1) M.G.L. c. 148,
§ 10C Alteration, repair or installation of oil burners; necessity of
certificate; exceptions;
(2) M.G.L.
c. 148, § 10D Certificate as oil burner technician; minimum age;
application; fee; examination; duration of certificate; electrical
work;
(3) M.G.L. c. 148, §
10E, governing apprentice certificates; fee; duration; expiration;
renewal.
1.13.7.1.4.1 The
examination provisions shall not be applicable as a prerequisite to licensure
as an apprentice.
A.1.13.7.1.5
See the
following references:
(1) M.G.L. c. 148,
§ 10C Alteration, repair or installation of oil burners; necessity of
certificate; exceptions;
(2) M.G.L.
c. 148, § 10D Certificate as oil burner technician; minimum age;
application; fee; examination; duration of certificate; electrical
work;
(3) M.G.L. c. 148, §
10E, governing apprentice certificates; fee; duration; expiration;
renewal.
1.13.7.1.5.1 The
examination provisions shall not be applicable as a prerequisite to licensure
as an apprentice.
1.13.7.2
Certificate of
Completion. Except as otherwise provided by
Section
1.12.8.2.1, a Certificate of Completion, as it applies to Chapter 11,
entitled Building Services, shall be used, completed, required and submitted to
the Head of the Fire Department as a precondition before a permit shall be
issued:
(1) For the delivery of and storage of
fuel oil; and
(2) For the operation
of an oil fuel burner.
1.13.7.2.1
The oil burner technician shall be responsible for the submittal of a
Certificate of Completion to the Head of the Fire Department within 72 hours
(excluding Saturday, Sunday and holidays), regarding one or more of the
activities listed in
Sections 1.13.7.2.1 (1) and (2).
(1) Requesting a permit to store fuel
oil
(2) Inspection;
(a) Installation work is completed
(b) Tank replacement is completed
(c) Oil line protection is
completed
(d) Combustion
performance test is completed.
Exception to Section 1.13.7.2.1(2)(d): A
combustion performance test shall not be required when other permitted work,
such as the, upgrading oil fuel lines, or the replacement or removal of an oil
fuel tank or, for the repair or replacement of zone-valves and circulators and
the like are performed.
1.13.7.2.1.1 When the applicable work
described in Section 1.13.7.2.1(2) is approved, a permit shall
be issued for the storage of fuel oil and for the use of the oil fuel
boiler.
1.13.7.3
* Certificate of
Compliance. A Certificate of Compliance is a standard form FP-056
prescribed by the State Fire Marshal and used to document by inspection,
compliance with oil line upgrades.
1.13.7.3.1
A Certificate of Compliance shall be completed and signed by a licensed
technician.
(1) Such signature certifies that
the subject installation is in compliance and no other work activity is
necessary to meet this provision.
(a) Upon
completion, a copy of such certificate shall be given to the owner and Head of
the Fire Department.
(2)
When an oil line needs upgrading as required by Massachusetts General Law, a
permit using form FP-056A shall be used, completed, and issued as prescribed in
1.12.8.2.1.1 thereafter, a Certificate of Compliance shall be
completed and submitted as provided in 1.13.7.3.1.
1.13.7.3.2 The owner shall receive
a copy and submit the Certificate of Completion to the Head of the Fire
Department.
1.13.7.3.3 The Fire
Department Official shall maintain such Certificate of Completion in accordance
with Section 1.11.
1.13.7.4
Fuel Oil Deliveries.
1.13.7.4.1 Fuel oil deliveries shall not
commence, unless the deliverer has verification that a permit has been
obtained. Such verification may be considered to consist of any of the
following:
(1) Verification by the Head of the
Fire Department that such a permit is in effect.
(2) Written verification from the owner or
customer that the permit is either in his or her possession or is posted on the
premises.
(3) Observation that such
a permit is in the possession of the owner or customer, or is posted on the
premises.
1.13.7.4.2 Fuel
oil shall not be delivered to a storage tank by means of a pump or under
pressure, in any case where a tight connection is made between the discharge
line and the tank inlet, unless such storage tank is designed to withstand the
additional stress to which it may be subjected or unless the vent pipe for such
tank is of sufficient size to relieve the tank of any undue pressure in excess
of five psi. The delivery truck operator shall remain at the fill point during
the entire operation.
1.13.8
Cleaning and Inspection of
Commercial Cooking and Exhaust Systems. [Chapter 50]
1.13.8.1
General. To clean and
inspect commercial cooking and exhaust systems the following certificates shall
be required.
1.13.8.1.1.1 A Certificate of
Competency shall be required for each person performing such activity and shall
be issued as either an Unrestricted Type 1 or Restricted Type 2
Certificate.
1.13.8.1.1.2 A Type 1
Unrestricted Certificate of Competency authorizes the holder to clean and
inspect all commercial cooking and exhaust systems.
1.13.8.1.1.3 A Restricted Type 2 Certificate
of Competency authorizes the holder to clean and inspect only those commercial
cooking and exhaust systems which are owned by the certificate holder or their
employer.
1.13.8.1.2 A
Certificate of Registration shall be required for any business entity offering
such activities.
1.13.8.1.2.1 A Type 1
Certificate of Registration authorizes a sole proprietor, company, firm,
corporation, or other legal entity to offer cleaning and inspection of all
commercial cooking and exhaust systems.
1.13.8.1.2.2 A Type 1 Certificate of
Registration is not a substitute for a Certificate of Competency. A Certificate
of Registration, by itself, does not authorize the holder of the Certificate of
Registration to perform the actual activity of cleaning and inspection of
commercial cooking and exhaust systems without a valid Certificate of
Competency.
1.13.8.2
Requirements for Certificate of Competency for Cleaning and Inspection of
Commercial Cooking Systems.
1.13.8.2.1
An applicant requesting a Certificate of Competency shall comply with the
following prior to issuance.
(1) Submit a
completed application on a form as prescribed by the State Fire
Marshal;
(2) Submit a completed
affidavit verifying 500 hours of supervision in the cleaning or inspection of
commercial cooking operations.
(3)
Successfully pass a written examination which tests the applicant's knowledge
of applicable codes.
1.13.8.3
Certificate of Registration
for Cleaning and Inspection of Cooking Systems.
1.13.8.3.1 An applicant requesting a
Certificate of Registration shall submit a completed application in accordance
with
Section 1.13.3 for the cleaning or inspection of
commercial cooking operations to the State Fire Marshal's Office.
Table 1.13.8 Certificates Required
Chapter 50 |
Cleaning and Inspection of Commercial Cooking
and Exhaust Systems |
Certificate of Competency |
Activity |
Type |
For an individual to clean and/or inspect any
commercial cooking and exhaust systems. |
Type 1 |
For an individual to clean and/or inspect only those
commercial cooking and exhaust systems which are owned by him/her or his/her
employer. |
Type 2 Restricted |
For a business entity to clean and/or inspect any
commercial cooking and exhaust systems. |
Type 1 |
1.13.9
Cannon and Mortar.
[Chapter 65]
Table 1.13.9 Certificates Required
Chapter 65 |
Cannon and Mortar |
Certificate of Competency |
Activity |
Description |
Individuals to conduct or engage in any operation or
activity which governs the firing of muzzleloading cannons. |
For patriotic celebrations and reenactments,
including all such cannons ranging from pre-revolutionary war vintage to
present day facsimiles, except any cannon exhibit in which explosives are not
being used. |
1.13.10
Fireworks Display, Special Effects or Proximate Audience Displays.
[Chapter 65]
1.13.10.1
General. To display fireworks and special effects or proximate
audience displays, both a Certificate of Competency and a User Certificate
shall be required.
1.13.10.1.1 A Certificate
of Competency shall be required for the display of fireworks.
1.13.10.1.2 A Certificate of Competency shall
be required for special effects or proximate audience displays.
1.13.10.1.3 A Certificate of Competency shall
be required for each person performing each such activity.
1.13.10.1.4 A User Certificates for the
display of fireworks shall be required for each firm, company, corporation, or
other legal entity.
1.13.10.1.5
Additional User Certificates for the display of fireworks shall be issued
contingent upon multiple business locations.
1.13.10.2 Certificate of Competency for
Fireworks Display.
1.13.10.2.1
Applicants shall comply with the following:
(1) Submit a completed application in
accordance with Section 1.13.3 for the display of fireworks to
the State Fire Marshal's Office.
(2) Provide evidence of active employment for
a period of three years on a crew for professional fireworks displays, and
encompasses a minimum of ten displays.
(3) Submit at least two letters of reference
from holders of valid Certificate of Competency issued by the State Fire
Marshal. At the option of the State Fire Marshal, an alternate requirement may
be permitted to be substituted.
(4)
Provide evidence of having satisfactorily completed a recognized fireworks
safety course, subject to review by the State Fire Marshal, during the past 12
months.
(5) The applicant shall be
21 years of age or older.
(6) Pass
a comprehensive written examination covering state laws, regulations and
industry safety standards pertaining to the display of fireworks and this
Code.
1.13.10.2.2
Renewal of Certificate of
Competency.1.13.10.2.2.1 The applicant
requesting renewal shall comply with the following:
(1) Provide proof of active participation in
at least two fireworks displays during the prior two years;
(2) Provide a notarized statement attesting
that the applicant understands the contents of this Code
pertaining to fireworks displays and M.G.L. c. 148. The statement shall be made
part of the application; and
(3)
Submit a renewal application as provided in Section 1.13.3 to
the State Fire Marshal's Office.
1.13.10.4
User Certificate for
Fireworks. [Chapter 65]1.13.10.4.1
Applicants shall comply with the following:
(1) Submit a completed application in
accordance with Section 1.13.3 for a User Certificate to the
State Fire Marshal's Office; and
(2) Provide evidence of a valid bond in
accordance with M.G.L. c. 148, § 42.
(a)
Supply evidence of valid liability insurance coverage in the form of a
certificate issued by the insurance agency to the State Fire Marshal's Office
listing the name and claims representative, providing general liability in the
amount of $1,000,000 per occurrence and $1,000,000 aggregate coverage;
and
(b) A 30 day cancellation
notice to the State Fire Marshal shall be a condition of the policy;
(3) Provide a notarized statement
affirming that all fireworks materials within the possession, custody, and/or
control of the User Certificate, shall be transported, stored, handled and/or
used in accordance with Chapter 65; and (4) Provide a statement attesting that
the person or firm understands the contents of this Code and
M.G.L. c. 148. The statement shall be made a part of the application.
1.13.10.4.2
Expiration of
Fireworks User Certificate.
1.13.10.4.2.1 A fireworks User Certificate
shall expire upon the expiration of the ATF permit, bond, or the liability
insurance, whichever occurs first.
1.13.10.5
Certificate of Competency for
Special Effects or Proximate Audience Displays. [Chapter 65]
1.13.10.5.1 Applicants shall comply with the
following:
(1) Submit a completed application
in accordance with Section 1.13.3 to the State Fire Marshal's
Office;
(2) Submit evidence of
knowledge and experience particular to the profession of conducting special
effects displays. Such evidence shall include written documentation that the
applicant has worked in at least ten special effects performances within two
years from the date of application, under the direct supervision of a person
who possesses a valid Certificate of Competency, issued by the State Fire
Marshal, for such special effects issued by the Commonwealth or such similar
certificate issued by another state;
(3) Provide evidence of having satisfactorily
completed a recognized fireworks safety course, approved by the State Fire
Marshal, during the past 12 months;
(4) Provide at least two letters of reference
from other pyrotechnic certificate holders within the state. At the option of
the State Fire Marshal, an alternate requirement can be substituted.
(5) The applicant shall be at least 21 years
of age or older; and
(6) Pass a
comprehensive written examination covering state laws, regulations and industry
safety standards pertaining to the display of special effects and this
Code.
1.13.10.5.2 Renewal An applicant requesting
renewal shall comply with all of the following:
(1) Pass a reexamination covering state laws,
regulations and industry safety standards pertaining to the display of special
effects;
(2) Submit proof of
actively participating in at least two displays during the prior two
years;
(3) Provide a statement
attesting that the person understands the contents of this Code pertaining to
special effects and M.G.L. c. 148. The statement shall be made part of the
application; and
(4) Submit a
renewal application as provided in Section 1.13.3.3 to the
State Fire Marshal's Office.
1.13.10.6
Supervision.
Fireworks, special effects and pyrotechnic compositions and devices shall be
ignited and be supervised continuously by the person holding a Certificate of
Competency for the display.
Table 1.13.10 Certificates Required
Chapter
65 |
Fireworks, Special Effects and
Proximate Audience Displays |
Certificate of
Competency |
Activity |
Description |
Individuals to conduct or engage in any activity,
operation or act with the use of fireworks. |
To conduct outdoor, marine or supervised displays of
fireworks. |
Individuals to conduct or engage in any activity,
operation or act with the use of special effects or proximate audience
effects. |
To conduct outdoor/indoor, proximate audience special
effects displays. |
Fireworks User
Certificate |
Activity |
Description |
Companies to conduct or engage in any operation (use
or manufacture) or act for which governs the use of fireworks or special
effects. |
To possess and conduct fireworks or special
effects. |
1.13.11
To Conduct or Engage in Any
Activity, Operation, or Act Dealing with the Use and Manufacture of Explosives.
[Chapter 65]1.13.11.1
General. To conduct or engage in any activity, operation, or act
dealing with the use of explosives, both a Certificate of Competency and a User
Certificate shall be required.
1.13.11.1.1 A
Certificate of Competency shall be required for each person performing
activities prescribed in this section.
1.13.11.1.2 A User Certificate shall be
required for each firm, company, corporation, or other legal entity engaged in
the activities as prescribed in this section.
1.13.11.1.3 Additional user certificates
shall be required to be issued contingent upon multiple places of
business.
1.13.11.2
Certificate of Competency for Explosives. [Chapter 65]
1.13.11.2.1 Applicants shall comply with the
following:
(1) The applicant shall be 21 years
of age or older
(2) Submit a
completed application in accordance with Section 1.13.3 to the
State Fire Marshal's Office;
(3)
Pass a comprehensive written examination covering state laws, regulations and
industry safety standards pertaining to this Code;
(4) Provide evidence of having satisfactorily
completed a recognized safety course, subject to review by the State Fire
Marshal, during the past 12 months; and
(5) Have at least two letters of reference
from other certificate holders within the state. At the option of the State
Fire Marshal, an alternate requirement may be permitted.
1.13.11.2.2
Blasting. [Chapter
65]1.13.11.2.2.1 No blasting operation
shall be conducted at any time, unless a blaster holding a Certificate of
Competency is physically present.
1.13.11.2.2.2 Trainees, helpers, and other
persons shall be permitted to work only under the supervision of a blaster
holding a Certificate of Competency.
1.13.11.2.3
User Certificate for
Explosives. [Chapter 65]1.13.11.2.3.1
The applicant shall comply with the following:
(1) Submit a completed application in
accordance with Section 1.13.3 to the State Fire Marshal's
Office;
(2) Provide evidence of
valid liability insurance coverage in the form of a certificate issued by the
insurance agency to the State Fire Marshal's Office listing the name and claims
representative, providing general liability in the amount of $1,000,000 per
occurrence and $1,000,000 aggregate coverage. A 30-day cancellation notice to
the State Fire Marshal shall be a condition of the policy;
(3) Provide evidence of a valid blasting
bond; and
(4) Provide a statement
indicating that explosive materials shall be kept in magazines which meet the
requirements of Chapter 65 and in accordance with 27 CFR Part 55. Provide a
notarized statement attesting that the person or firm understands the contents
of this Code and M.G.L. c. 148.
1.13.11.2.3.2 A User Certificate shall not be
required for small arms ammunition. Small arms ammunition, as used here, means
any shotgun, rifle, or pistol cartridge and any cartridge or propellant
actuated devices, excluding military ammunition containing bursting charges or
incendiary, tracer, spotting, or pyrotechnic projectiles;
1.13.11.2.3.3 The User Certificate for
explosives shall expire upon the expiration of the ATF permit, bond, or the
liability insurance, whichever occurs first.
Table 1.13.11 Certificates Required
Chapter
65 |
Explosive Use and
Handling |
Certificate of
Competency |
Activity |
Description |
Allows individuals to conduct or engage in any
activity, operation or act dealing with the use of explosives. |
To conduct blasting operations, including: research
and development (R&D), and blasting for the cleaning of
boilers. |
Explosive User
Certificate |
Activity |
Description |
Allows companies to conduct or engage in any
operation (use, handling or manufacture) of explosives. |
To possess and conduct explosive activity or
operation. |
To manufacture explosive materials. |
1.13.12
Certificate of Registration for
On-demand Fueling.
1.13.12.1 An
applicant requesting a Certificate of Registration (CR) shall submit a
completed application in accordance with
Section 1.13.3 to
conduct On-demand Fueling operations to the State Fire Marshal's Office in
accordance with the following:
(1) Provide
evidence of valid liability insurance coverage in the form of a certificate
issued by the insurance agency to the State Fire Marshal's Office listing the
name and claims representative, providing general liability in the amount of
$1,000,000 per occurrence, and $5,000,000 aggregate coverage. A 30-day
cancellation notice to the State Fire Marshal shall be a condition of the
policy.
(2) Provide a notarized
statement attesting that fueling operations shall meet the requirements of
Chapter 42.
(3) Provide a notarized
statement attesting that the applicant understands the contents of this
Code and M.G.L. c. 148.
(4) Provide a copy of the general safety and
emergency response plan.
Table 1.13.12 Certificates Required
Chapter
42 |
On-demand Mobile
Fueling |
Certificate of
Registration |
Activity |
Description |
Companies to conduct the fueling of motor vehicles to
the general public. |
Mobile fueling of vehicles |
1.13.13
Renewal of Certificates.
The following certificates shall be renewed as provided in Table 1.13.12 and
Section 1.13.
Table 1.13.13
Chapter |
Type of Certificate |
Description |
Expiration Date [See
Note 1 and 2] |
Exam Required for Renewal
|
Acronym* |
11 |
Competency Technician |
To alter, repair or install any oil burning equipment
or any of the appurtenances thereto |
Initial licensure 12 months from DOB Every 24 months
after based on DOB |
No, unless failed to renew within 2 yrs. of
expiration |
BU |
11 |
Competency Apprentice |
Can only work under the direct supervision of a
technician regrading oil burning equipment or any of the appurtenances
thereto |
Initial licensure 12 months from DOB Every 24 months
after based on DOB |
No |
OA |
13 |
Registration |
Servicing Self-serve Motor Fuel Fire Suppression
Systems.
Company Type 40 |
two yrs. from date of issue |
No |
CR |
13 |
Registration |
Servicing Portable Fire Extinguishers. Company Type
42 |
two yrs. from date of issue |
No |
CR |
13 |
Registration |
Special Hazards Engineered (Fixed Fire Extinguishing
Systems.)
Company Type 43 |
two yrs. from date of issue |
No |
CR |
13 |
Registration |
Special Hazards Pre-engineered (Fixed Fire
Extinguishing Systems.)
Company Type 44 |
two yrs. from date of issue |
No |
CR |
42 |
Registration |
On-demand Fueling |
two yrs from date of issue |
No |
ODF |
50 |
Competency |
Cleaning of Commercial Cooking Exhaust Systems
Individual Type 2 Restricted |
three yrs. Renewal |
50 |
Competency |
Cleaning/Inspection of Commercial Cooking Exhaust
Systems Individual Type 1 |
on DOB |
No |
HC |
50 |
Registration |
Cleaning/Inspection of Commercial Cooking Exhaust
Systems Company Type 1 |
two yrs. from date of issue |
No |
HCI |
65 |
Competency |
Cannon/Mortar Individual |
five yrs. Renewal on DOB |
No |
CN |
20 |
Competency |
Crowd Manager Individual |
three yrs. from date of issue |
Yes |
MFA |
65 |
Competency |
Special Effects Individual |
two yrs. Renewal on DOB |
Yes |
SE |
User |
Special Effects Company |
one yr. or less dependent on ATF permit, bond and/or
insurance |
No |
PY |
User |
Pyrotechnic Company |
one yr. or less dependent on ATF permit, bond and/or
insurance |
No |
PY |
65 |
User |
Fireworks Company |
No |
PY |
65 |
Competency |
Fireworks Individual |
two yrs. Renewal on DOB |
No |
FW |
65 |
Competency |
Explosives Individual |
two yrs. Renewal on DOB |
No |
BL |
65 |
Registration |
Blasting (Site work) Company |
Based on the Explosive User
Certificate |
No |
BL |
65 |
User |
Blasting (Boiler) Company |
No |
BL |
13 |
Competency |
Servicing Engineered Fixed Fire Extinguishing Systems
Individual Type 47 |
two yrs. Cycle Renewal on DOB |
No |
CC |
13 |
Competency |
Servicing Pre-engineered Fixed Fire Extinguishing
Systems Individual Type 48 |
two yrs. Renewal on DOB |
No |
CC |
13 |
Competency |
Self-serve Motor Fuel Facilities Individual Type
41 |
two yrs. Renewal on DOB |
No |
CC |
13 |
Competency |
Servicing Portable Fire Extinguishers Individual Type
46 |
two yrs.
Renewal on DOB |
No |
CC |
65 |
User |
Explosives Certificate by location |
one yr. or less dependent on ATF permit, and
insurance Bond is waived for R & D Licenses |
No |
EUC |
Blasting Company |
Research and Development Company |
Boiler Cleaning Company |
65 |
User |
Transport Fireworks (Permit by
location) |
one yr. from date of issuance |
No |
TF |
Magazine Explosives (Permit by
location) |
Annually on 3/31 |
No Exam, inspection required |
MP |
Mobile |
Magazine Explosives (Permit by
location) |
Annually on 10/31 |
No Exam, inspection required |
MP |
Permanent |
65 |
User |
Remote Firing Panel |
five yrs. from date of issuance |
No Exam, inspection required |
RF |
65 |
User |
Dense Pack Portable firing trailers |
DPP |
65 |
User |
Sell Explosives (License by location) |
one yr. from date of issuance |
No |
LS |
65 |
User |
Sell Black or Smokeless Powder (License by
location) |
one yr. from date of issuance |
No |
SP |
42 |
User |
Marine Fueling: |
Annually on 12/31 |
No |
MF |
Marine Fuel Barges |
Mobile Marine Fueling |
Fixed Marine Fueling |
Seasonal Marine Fueling Facility |
* Identifier for certificates used in database (MLO)
Note 1. DOB as used here means the date and year
someone was born or such anniversary date.
Note 2. ATF as used here means Bureau of Alcohol,
Tobacco and Firearms and Explosives.
1.14
Plan Review and Approvals.
1.14.1
General.
1.14.1.2 Where permits and plan reviews are
required by this Code, the AHJ shall complete the plan reviews
for new construction, modification, or rehabilitation, of any building,
structure, or facility.
1.14.1.3
Construction documents and shop drawings submitted shall be approved by the AHJ
before work commences and within 30 days of the date of receipt of a completed
application and construction documents, unless extended by the AHJ.
1.14.1.4 Review and approval by the AHJ shall
not relieve the applicant of the responsibility of continued compliance with
this Code.
1.14.1.5 When required by the AHJ, revised
construction documents or shop drawings shall be prepared and submitted for
review and approval to illustrate corrections or modifications necessitated by
field conditions or other revisions to approved plans.
1.14.2
Applicants
Responsibility.1.14.2.1 The applicant
shall be responsible to ensure that the following conditions are met:
(1) The construction documents include fire
protection requirements;
(2) The
shop drawings are correct and in compliance with the applicable codes and
standards; and
(3) The contractor
maintains an approved set of construction documents on site.
1.14.3
AHJ
Responsibility.1.14.3.1 It shall be
the responsibility of the AHJ to promulgate policies and procedures that govern
the following:
(1) Criteria to meet the
requirements of Sections 1.12 and 1.13; and
(2) Review all of documents and related
information within the established time frames for the purpose of acceptance or
providing reasons for non-acceptance.
1.14.4
Explosives Manufacturing.
1.14.4.1
Plans.
1.14.4.1.1 Explosives manufacturing requires
a plan drawn to scale showing the arrangement of the various buildings and
magazines of the manufactory and the egress therefrom, their relative location
to other buildings and property lines and shall be submitted to the Head of the
Fire Department and State Fire Marshal indicating the following:
(1) The location of the
manufactory;
(2) The name of the
owner and/or occupant;
(3) The kind
and maximum quantities of the explosives, raw materials, and finished products
and the manner in which they are to be kept or stored;
(4) The nature of the work to be carried on
in each building; and
(5) A fire
safety analysis conducted by a registered professional engineer.
1.14.5
Marine Fueling Facility.1.14.5.1
General.1.14.5.1.1 Prior to
conducting any construction or alteration activity to a new or existing fixed
marine fueling facility, a registered design professional shall prepare and
submit three complete stamped and scaled sets of plans and specifications to
the Head of the Fire Department and the State Fire Marshal.
1.14.5.1.2 One set of plans shall be marked
State Fire Marshal's office copy, a second set of plans shall be marked Head of
Fire Department copy, and the third set of plans marked owner's copy. Such
marking for each set of plans shall be in bold and located on the lower right
hand legend.
1.14.5.1.3 All
designs, blueprints, plans, and specifications shall comply with the provisions
of this
Code and any other applicable state and federal
regulations. The Head of the Fire Department and the State Fire Marshal's
Office must approve the design submission or modification before any
construction is commenced. The packet of plans and specifications shall include
the following:
(1) The design review fee
required by the Head of the Fire Department and the State Fire Marshal's
Office;
(2) A cover letter
providing an overview of the planned work, the location of the work, and the
legal name and address of the facility owner, operator, and person(s) or
company who will be conducting the work;
(3) A copy of the current and valid
registration or copy of the license to store flammables (Form FP-2) issued
under M.G.L. c. 148, § 13 or a current and valid permit if a license is
not applicable under M.G.L. c. 148, § 13;
(4) Current permit (existing facilities
only);
(5) Scaled design plans
indicating the locations of all piers, storage tanks, piping systems, hoses,
dispensing nozzle locations, equipment, signage, path of the electrical static
grounding systems, fire access roadway(s), travel from the closest fire
apparatus to the foot of the marine wharf, the location and type of water
standpipe system, the location of the nearest hydrant, location of the piping
system, flexible hose, couplings, control valves, and swing and swivel joints,
and for mobile fueling facilities, the designated location(s) that the fuel
truck shall park to dispense fuel. A notation on the plan legend shall indicate
the location and type of fire extinguishing systems, fuel dispensing nozzles,
and the maximum number of dispensing nozzles which can be operated
simultaneously;
(6) A statement
that the blueprints, plans, and specifications of the installation comply with
the requirements of the provisions of this Code and any other
applicable state or federal regulation;
(7) A clear indication of fire access
roadways and appropriate signage as directed by the Head of the Fire Department
to allow for local enforcement of fire lane designation; and
(8) A detailed drawing of the entire marine
wharf, and floats showing the fueling location, tie up area(s), and all of the
berthing areas.
1.15
Technical Assistance.
1.15.1
General.
1.15.1.1 As permitted by other sections of
this Code, the AHJ shall be permitted to require a review by
an approved independent third-party with expertise in the matter, to be
reviewed at the submitter's expense.
1.15.1.2 The independent reviewer shall
provide an evaluation and, if appropriate, recommend necessary changes of the
proposed design, operation, process, or new technology to the AHJ.
1.15.1.3 The AHJ shall be authorized to
require design submittals to bear the stamp of a registered design
professional.
1.15.1.4 The AHJ
shall make the final determination as to whether the provisions of this
Code have been met.
1.16
Notice of Violations and
Penalties.1.16.1
General.
1.16.1.1 Any person who mutilates, destroys,
or removes posted orders or notices without the authorization of the AHJ shall
be deemed in violation of this Code.
1.16.2
Criminal Enforcement.
Whenever the AHJ has reason to believe that a violation of this
Code has occurred, written notification of said violation
shall be issued in accordance with the provisions of M.G.L. c. 148.
1.16.3
Alternative Civil Enforcement
Option. As an alternative to initiating criminal proceedings in a court
of law under the provisions of M.G.L. c. 148, the AHJ may initiate the
alternative civil code enforcement option as provided in M.G.L. c. 148A, by
issuing the standardized notice of violation form as prescribed by M.G.L. c.
148A. The provisions of
Section 1.16.3 may only be utilized by
the Head of the Fire Department or his or her designee if the jurisdiction has
designated a municipal hearings officer in accordance with M.G.L. c. 148A.
1.16.3.1 Any order or notice issued pursuant
to this Code shall be served upon the owner, operator, occupant, or other
person responsible for the condition or violation in accordance with the
provisions of M.G.L. c. 148 or, if applicable, M.G.L. c. 148A, if the
alternative civil enforcement option is utilized.
1.16.4
Penalties.
1.16.4.1 Any person who fails to comply with
the provisions of this Code or who fails to carry out an order
made pursuant to this Code or violates any condition attached
to a permit, approval, or certificate shall be subject to penalties in
accordance with M.G.L. c. 148 or, if applicable, M.G.L. c. 148A.
1.16.4.2
Reserved
1.16.4.3
Reserved
1.16.4.4
Reserved
1.16.4.5 Failure to comply with the time
limits of an abatement notice or other corrective notice issued by the AHJ
shall, unless otherwise specified, result in a new and separate offense for
each day that such violation continues.
1.17.1
Misrepresentation. Any
attempt to misrepresent or otherwise deliberately or knowingly design, install,
service, maintain, operate, sell, represent for sale, falsify records, reports,
or applications; or other related activity in violation of the requirements
prescribed by this
Code shall be a violation of this
Code.
1.17.1.1 The
installation or use, in any building, of any device or object that reasonably
appears to be a smoke detector, sprinkler head, carbon monoxide alarm, heat
detector, or any similar device, used for life safety or fire protection, that
is in fact, neither designed nor capable of performing such life safety or fire
protection function, shall be prohibited.
1.17.2 Such violations shall be cause for
immediate suspension or revocation of any related approvals or permits
issued.
1.17.3 Such violations
shall be subject to any other criminal or civil penalties provided by the laws
or other applicable regulations of the Commonwealth of Massachusetts.
Chapter 2
Referenced Standards.
2.1
General.
Add:
(3)
Where the requirements of a reference code or standard, called for within a
Chapter of this Code is deleted, replaced, or revised, the
source reference code or standard shall be deemed deleted, replaced or revised
as such.
2.2
NFPA
70 Publication. Replace with the following:
NFPA 70, The National Electrical Code,
codified as
527 CMR
12.00: Massachusetts Electrical Code
(Amendments).
2.2
NFPA
Publications. Replace with the following:
NFPA 241, Standard for Safeguarding Construction,
Alteration, and Demolition Operations, 2022 edition.
2.2
NFPA Publications. Add:
NFPA 855, Standard for the Installation of Stationary
Energy Storage Systems, 2020 edition.
2.3.1
ANSI Publications. Add:
ANSI Z21.11.2, Gas-fired Room Heaters, Volume II,
Unvented Room Heaters, 2013 edition.
ANSI Z-358.1, American National Standard for Emergency
Eyewash and Shower Equipment.
ANSI Z49, Safety in Welding, Cutting, and Allied
Processes, 2012 edition.
2.3.7
ASTM Publications. Add:
ASTM D 975-11b, Standard Specification for Diesel Fuel
Oils.
ASTM D1265, Standard Practice for Sampling Liquefied
Petroleum (LP) Gases, Manual Method.
ASTM D5305, Standard Test Method for Determination of
Ethyl Mercaptan in LP-gas Vapor.
2.3.7
ASTM Publications. Replace
with the following:
ASTM D6751-11b, Standard Specification for Biodiesel
Fuel Blend Stock (B100) for Middle Distillate Fuel, 2019.
2.3.7
ASTM
Publications. Add:
ASTM D 7462-11, Standard Test Method for Oxidation
Stability of Biodiesel (B100) and Blends of Biodiesel with Middle Distillate
Petroleum Fuel (Accelerated Method).
2.3.19
UL Publications. Add:
UL 217, Standard for Smoke Alarms,
8th edition
UL 268, Smoke Detectors for Fire Alarm
Systems, 7th edition.
ANSI/UL 521, Standard for Heat Detectors for Fire
Protective Signaling Systems, 1999 edition.
ANSI/UL 539, Standard for Single and Multiple Station
Heat Alarms, 2009 edition.
2.3.22
U.S. Government
Publications. Add:
Code of Federal Regulations (CFR):
Title 21, United States Code, Chapter 9, Federal Food,
Drug, and Cosmetics Act.
Title 29, Code of Federal Regulations, 1910.119, Occupational
Safety and Health Administration (OSHA) Process Safety Management of
Highly Hazardous Materials. Regulated hazardous materials which are
listed in 29 CFR
1910.119: Appendix A and described in
29 CFR
1910.119(a)(1)(ii).
Title 29, Code of Federal Regulations, Part 1910.1450,
Occupational Safety and Health Administration (OSHA) Occupational
Exposure to Hazardous Chemicals in Laboratories.
Title 29, Code of Federal Regulations, 1910.252 Subpart Q -
Welding, Cutting and Brazing
Title 33, Code of Federal regulations, Part 126,
Handling of Dangerous Cargo at Waterfront Facilities.
Title 40, Code of Federal Regulations, Part 60
Standards of Performance for New Stationary Sources.
Title 40, Code of Federal Regulations, Part 68, EPA (United
States Environmental Protection Agency) Chemical Accident Prevention
Provisions. Regulated hazardous materials included in
40 CFR
68.130 "List of Substances" with threshold
quantities of regulated substances listed in the tables in
40 CFR
68.130.
Title 49, Code of Federal Regulations,
Transportation.
Title 46, Code of Federal Regulations, Part 194,
Handling, Use, and Control of Explosives and Other Hazardous
Materials.
2.3.23
Other Publications. Add:
American Association of State Highway and Transportation
Officials (AASHTO). Uniform Traffic Control Devices (MUTCD)
Guidelines.
APA Standard 87-1.
California - Technical Bulletin 117-2013 (TB 117-2013)
Requirements, Test Procedure and Apparatus for Testing the Smolder
Resistance of Materials Used in Upholstered Furniture.
California - Technical Bulletin 133-1991 (TB133-1991)
Flammability Test Procedure for Seating Furniture for Use in Public
Occupancies, amended 2019.
IAMPO Uniform Mechanical Code.
IME Safety Library Publication No. 20, Safety Guide for
the Prevention of Radio Frequency Radiation Hazards in the Use of Commercial
Electric Detonators (Blasting Caps).
STI SP 001, Standard for the Inspection of Aboveground
Storage Tanks. Transport Canada (TC), Transportation of
Dangerous Goods Regulations.
2.3.24
Massachusetts
Regulations. Add:
Code of Massachusetts Regulations (CMR) Publications:
105 CMR: Department of Public Health
248 CMR: Board of State Examiners of Plumbers and Gas
Fitters (Plumbing Code).
257 CMR
2.00: Certification of Operators of Wastewater
Treatment Facilities. Department of Environmental Protection:
310 CMR
7.00: Air Pollution Control.
310 CMR
30.00: Hazardous Waste.
310 CMR
80.00: Underground Storage
Tanks.
522 CMR: Board of Boiler Rules.
524 CMR 36: Personnel Hoists and Employee Elevators on
Construction and Demolition Sites
527 CMR
1.00: Comprehensive Fire Safety Code
Massachusetts (this Code).
527 CMR
12.00: Massachusetts Electrical
Code.
528 CMR: Bureau of Pipe Fitters and Refrigeration
Technicians. 780 CMR: Massachusetts State Building Code
(Building Code).
2.3.25
(M.G.L) Massachusetts General
Law.
M.G.L. c. 21E: Massachusetts Oil and Hazardous Material
Release Prevention and Response Act.
M.G.L. c. 48: Fires, Fire Departments and Fire
Districts.
M.G.L. c. 22D: Department of Fires
Services.
M.G.L. c. 148: Fire Prevention.
M.G.L. c. 148A: Code Enforcement
Officer.
M.G.L. c. 141: Supervision of
Electricians.
M.G.L. c. 142: Supervision of Plumbing.
M.G.L. c. 143, § 3L: Regulations Relative to
Electrical Wiring and Fixtures; Notice of Electrical
Installation.
M.G.L. c. 143, § 96: Specialized Codes Rules or
Regulations.
Chapter 3
Definitions.
3.2.2 Replace with
the following:
3.2.2*
Authority Having Jurisdiction (AHJ) An organization, office, or
individual responsible for enforcing the requirements of a code or standard, or
for approving equipment, materials, an installation, or a procedure.
(See Enforcement, 1.6, 1.7.1 Administration, 1.7.1 and
Official Interpretations, 1.7.3.1)
3.3.14.2 Replace with the
following:
3.3.14.2
Control
Area. A building or portion of a building, enclosed and bounded by
exterior walls, fire walls, fire barriers and roofs, or a combination thereof,
or an outdoor area within which hazardous materials are allowed to be stored,
dispensed, used, or handled in quantities not exceeding the maximum allowable
quantities (MAQ).
3.3.29 Replace
with the following:
3.3.29
Building. A combination of any materials, whether portable or
fixed, having a roof, to form a structure for the shelter of persons, animals
or property. For the purpose of this definition "roof" shall include an awning
or any similar covering, whether or not permanent in nature. The word
"building" shall be construed where the context allows as though followed by
the words "or part or parts thereof".
3.3.56.1 Replace with the
following:
3.3.56.1
Building Code. referenced in Sections 2.3.22 and
1.1.
3.3.56.2 Replace with the
following:
3.3.56.2
Massachusetts Electrical Code. referenced in Sections 2.2 and
2.3.22.
3.3.56.3 Replace with the
following:
3.3.56.3
Mechanical Code. The Massachusetts State Building
Code as referenced in Section 2.3.22.
3.3.56.4 Replace with the
following:
3.3.56.4
Plumbing Code referenced in Section 2.3.22.
3.3.56.5 Add:
3.3.56.5
Fire
Code as referenced in Section 2.3.22.
3.3.146.12 Replace with the
following:
3.3.146.12
Oxidizing Gas. A gas that can support and
accelerate combustion of other materials.
3.3.153 Replace with the following:
3.3.153
Handling. The deliberate
transport by any means to a point of storage use, or processing.
3.3.168 Replace with the following:
3.3.168
Incident Commander (IC).
The individual responsible for all incident activities, including the
development of strategies and tactics and the ordering and the release of
resources. The IC has overall authority and responsibility for conducting
incident operations and is responsible for the management of all incident
operations at the incident site.
3.3.187.12 Replace with the
following:
3.3.187.12
Physical Hazard Material. A chemical for which
there is evidence that it is a combustible liquid, compressed gas, cryogenic,
explosive, flammable gas, flammable liquid, flammable solid, organic peroxide,
oxidizer, pyrophoric or unstable (reactive) or water-reactive
material.
3.3.187.15 Replace with
the following:
3.3.187.15
Unstable (Reactive) Material. A material, other
than an explosive, which in the pure state or as commercially produced, will
vigorously polymerize, decompose, condense or become self-reactive and undergo
other violent chemical changes, including explosion, when exposed to heat,
friction or shock, or in the absence of an inhibitor, or in the presence of
contaminants, or in contact with incompatible materials. Unstable (reactive)
materials are subdivided and defined as follows:
Class 1. Materials that in themselves are normally
stable, but which can become unstable at elevated temperatures and
pressure.
Class 2. Materials that in themselves are normally
unstable and readily undergo violent chemical change, but do not detonate. This
class includes materials that can undergo chemical change with rapid release of
energy at normal temperatures and pressures, and that can undergo violent
chemical change at elevated temperatures and pressures.
Class 3. Materials that in themselves are capable
of detonation or of explosive decomposition or explosive reaction, but which
require a strong initiating source or which must be heated under confinement
before initiation. This class includes materials that are sensitive to thermal
or mechanical shock at elevated temperatures and pressures.
Class 4. Materials that in themselves is readily
capable of detonation or explosive decomposition or explosive reaction at
normal temperatures and pressures. This class includes materials that are
sensitive to mechanical or localized thermal shock at normal temperatures and
pressures.
3.3.187.16
Replace with the following:
3.3.187.16
Water-Reactive
Material. A material that explodes; violently reacts; produces
flammable, toxic or other hazardous gases; or evolves enough heat to cause
self-ignition or ignition of nearby combustibles upon exposure to water or
moisture. Water-reactive Material are subdivided and defined as follows:
Class 1. Materials that may react with water with
some release of energy, but not violently.
Class 2. Materials that may form potentially
explosive mixtures with water.
Class 3. Materials that react explosively with
water without requiring heat or confinement.
3.3.205.1.6 Add:
3.3.205.1.6
Unclassified
Detonable. Organic peroxides that are capable of detonation. These
peroxides pose an extremely high explosion hazard through rapid explosive
decomposition.
3.3.224 Replace with
the following:
3.3.224
Process or Processing. A sequence of operations in which the sequence
can be inclusive of physical operations such as heating, cooling, mixing,
distilling, compressing, and pressurizing, and chemical operations, such as
polymerization, oxidation, reduction, and other chemical reaction processes.
The sequence can involve, but is not limited to: preparation, separation,
combination, purification, or any actions that cause a change in state, energy
content, or chemical composition.
3.3.230 Replace with the following:
3.3.230
Pyrophoric. A chemical
with an autoignition temperature in air, at or below a temperature of 130°F
(54.4°C).
3.3.259.2 Replace with
the following:
3.3.259.2
Flammable Solid. A solid
substance, other than a substance defined as a blasting agent or explosive,
that is liable to cause fire resulting from friction absorption or moisture,
spontaneous chemical change, or retained heat from, manufacturing or
processing, or which has an ignition temperature below 212°F (100°C),
or that burns so vigorously and persistently when ignited that it creates a
serious hazard. A chemical shall be considered a flammable
solid as determined in accordance with the test method of CPSC
16 CFR; Part 1500.44, if it ignites and burns with a self-sustained flame at a
rate greater than 0.1 inch (2.5 mm) per second along its major axis.
3.3.275 Replace with the following:
3.3.275
Structure. A combination
of materials assembled at a fixed location to give support or shelter, such as
a building, framework, retaining wall, tent, reviewing stand, platform, bin,
fence, sign, flagpole, mast for radio antenna or the like. The word "structure"
shall be construed, where the context allows, as though followed by the words
"or part or parts thereof'.
3.3.278.11 Replace with the
following:
3.3.278.11
Fire
Protection System. Any fire alarm device or system or fire-extinguishing
device or system, or combination thereof, that is designed and installed for
detecting, controlling, or extinguishing a fire or otherwise alerting
occupants, or the fire department, or both, that a fire has occurred. A fire
protection system shall include any wiring, equipment, and systems used to
detect, suppress, or control smoke, fire, and carbon monoxide, or any
combination thereof.
3.3.279.8
Add:
3.3.279.8
Underground
Storage Tank (UST). As defined and regulated by
310 CMR
80.00: Underground Storage Tanks (UST)
Systems.
3.5
Add:
3.5.
Additional
Massachusetts Definitions.
3.5.1
Boatyard. A facility used for constructing, repairing, servicing,
hauling from the water, storing (on land and in water), and launching of
boats.
3.5.2
Cannabis.
The plant or any product derived from the plant, of the family cannabaceae;
also known as marijuana or hemp.
3.5.3
Certificate. A written
document for the purpose of granting permission to conduct or engage in any
operation or act for which certification is required by way of one or more of
the following:
3.5.3.1
Certificate of
Competency. A written document issued by the State Fire Marshal to a
person who has passed an examination for a particular profession which allows
that person to be in charge of and responsible for the regulated
activity.
3.5.3.2
Certificate
of Registration. A written document issued by the State Fire Marshal to
a person, firm or corporation for the purpose of granting permission to conduct
or engage in servicing fire extinguishing systems.
3.5.3.3
Explosives Users
Certificate. A certificate issued to a firm or company, indicating the
rebuttable presumption of statutory and regulatory compliance with responsible
levels of liability insurance and bonds required by M.G.L. c. 148, §§
19, 20 and 20A, explosive storage magazines, and a general knowledge of the
requirements of explosive regulations in the use or handling of
explosives.
3.5.3.4
Fireworks
User's Certificate. A certificate which allows a person, firm,
corporation or other legal entity to use or handle fireworks.
Chapter 4
General Requirements. Chapter 4 Delete in its entirety.
Chapter 5
Performance Based
Option. Chapter 5 Delete in its entirety and replace with the following
sections.
5.1*
General.
5.1.1
Application. The
requirements of this Chapter shall apply to facilities designed to the
performance-based option permitted by the Building Code and
this Code.
5.1.2
Goals and Objectives. The performance-based design shall meet the
goals and objectives of this Code in accordance with the
Building Code or this Code.
5.1.3*
Plan Submittal
Documentation. When a performance based design is submitted to the AHJ
and the Building Official for review and approval, the owner shall document, in
an approved format, each performance objective and applicable scenario,
including any calculation methods or models used in establishing the proposed
design's fire and life safety performance.
5.1.4*
Independent Review. The
AHJ shall be permitted to require an approved, independent third party to
review the proposed design and provide an evaluation of the design to the A111
AHJ at the expense of the owner.
5.1.5
Final Determination. The
AHJ and the Building Official shall make the final determination as to whether
the performance objectives have been met.
5.1.6*
Operations and Maintenance
Manual. An approved Operations and Maintenance (O&M) Manual shall be
provided by the owner to the AHJ and shall be maintained at the facility in the
fire command center.
5.1.1 through
5.7.14 Delete
Chapter 6
Classification of
Occupancy. Chapter 6 Delete in its entirety.
Chapter 10
General Requirements.
10.1.2 Delete.
10.1.3 Replace with the following:
10.1.3
Building Code. All new
construction shall comply with this
Code and the
Building Code.
10.1.4.1
Replace with the following:
10.1.4.1 Where structural elements have
visible damage, the AHJ shall notify the Building Official.
10.1.4.2 through 10.1.5
Delete.
10.3.4.1 Replace with the
following:
10.3.4.1 In any building
or structure, whether or not a physical alteration is needed, a change from one
use or occupancy classification to another shall comply with the
Building Code.
10.4.2.1 Add:
10.4.2.1
Overcrowding.
Overcrowding or admittance of any person beyond the established posted occupant
load shall be prohibited. The AHJ, upon finding overcrowded conditions or
obstructions in aisles, passageways or other means of egress, or any condition
which constitutes a hazard to life and safety shall cause the performance,
presentation, spectacle or entertainment to be stopped until the area posted
occupant load is reestablished or the obstruction or hazardous condition is
removed.
10.5.1 Replace
with the following:
10.5.1
Where Required. Emergency egress and relocation drills conforming
to the provisions of this Code shall be conducted as specified
by the provisions of Chapter 20 of this Code. Drills shall be
designed in cooperation with the local authorities.
10.5.2
Drill Frequency.
Emergency egress and relocation drills, where required by Chapter 20 of this
Code shall be held with sufficient frequency to familiarize
occupants with the drill procedure and to establish conduct of the drill as a
matter of routine. Drills shall include suitable procedures to ensure that all
persons subject to the drill participate.
10.6.2 Delete.
10.6.4 Delete.
10.7 Add:
10.7
Tampering with Fire Safety
Equipment.
See M.G.L. c. 266 and M.G.L. c. 148, §
27A.
10.7.1 through 10.7.3
Delete.
10.8.1 Replace with the
following:
10.8.1
Where
Required. Emergency action plans shall be provided for high-rise, health
care, ambulatory health care, residential board and care, assembly, day care
centers, special amusement buildings, hotels and dormitories, detention and
correctional occupancies, educational, underground and windowless structures,
facilities storing or handling materials covered by Chapter 60, special use and
occupancy as defined in 780 CMR, or where required by the AHJ.
10.10.1.1 Replace with the
following:
10.10.1.1 Fires for
cooking and recreational purposes shall comply with the provisions of M.G.L. c.
48, § 13 and the rules and regulations of the State Forester and
regulations of the Department of Environmental Protection.
10.10.1.2 through 10.10.1.4
Delete.
10.10.3. Replace with the
following:
10.10.3.
Outdoor
Fires and Incinerators.
10.10.3.1
Outdoor fires shall comply with the provisions of M.G.L. c. 48, § 13 and
the rules and regulations of the State Forester, and regulations of the
Department of Environmental Protection. See
310
CMR 7.07.
10.10.3.2 Delete.
10.10.4.1 Replace with the
following:
10.10.4.1 Add:
10.10.4.1
Bonfires and the Burning of
Christmas Trees. Permits where required, for bonfires and the burning of
Christmas trees shall comply with
Section 1.12.
10.10.4.1.1. Add:
10.10.4.1.1
Ceremonial Bonfires.
The city council of a city with the approval of its mayor, or the board of
selectmen or town council of a town, may authorize the fire department of such
city or town to issue not more than one permit in any one year for a ceremonial
bonfire. Such bonfires shall mark the observance of a significant municipal,
state or national event, and such ceremonial bonfire shall be under the
continuous supervision of the fire department. Only wood which has not been
painted, impregnated, or otherwise treated with any foreign substance shall be
permitted to burn in ceremonial bonfires. No bonfire shall burn for more than
12 hours. (M.G.L. c. 111, § 142H.)
10.10.4.1.2 Add:
10.10.4.1.2
Bonfires from July
2nd to July 6th.
Any civic, fraternal, veteran, community or business organization may build and
ignite bonfires under the supervision and control of the fire department of the
city or town in which such burning takes place during the period from July
2nd through July 6th.
(M.G.L. c. 111, § 142I.)
10.10.4.1.3 Add:
10.10.4.1.3
Burning of Christmas
Trees. Any person may burn Christmas trees during the period from
December 26th through January
7th, provided that such burning is under the
supervision and control of the fire department. (M.G.L. c. 111, §
142G.)
10.10.4.1.4 Add:
10.10.4.1.4 Burning hours shall be prescribed
by the AHJ.
10.10.4.2
through 10.10.5.2 Delete.
10.10.6 Replace with the following:
10.10.6
Appliances - Cooking
Equipment10.10.6.1
General. Cooking appliances shall be kept clean during and cleaned
after each use. Cooking appliances shall never be left unattended after the
cooking appliance is kindled. Cooking appliances shall be stored only after the
appliance is cleaned; the appliance is cool to the human touch and; the fuel is
disconnected and removed from the appliance. Cooking appliances shall not be
altered, used, kindled, placed, or stored in a manner that is not established
by the manufacturer's instructions of the appliance and its
equipment.
10.10.6.2
Terms. As used in Chapter 10, the enclosed terms shall have the
following meaning assigned to them.
(1)
Appliance (cooking). Utilization equipment, generally other than
industrial, that is normally built in standardized sizes or types and is used,
installed or connected as a unit to perform one or more functions such as
grills, ranges, cook top units, wall ovens, and chimineas or similar such
appliances.
(2)
Balcony. A structure attached to a building with no exterior
stairs other than through the attached building.
(3)
Deck (including porches, and
patios). A structure attached to a building where constructed above
grade has exterior stairs extending to grade.
(4)
Equipment (cooking). The
component of an appliance, such as the hose, burner, heating element,
electronic controls, igniters, heat exchanger, container or regulator that is
designed specifically for the purpose and constructed with approved safety
standards and tested by a recognized product testing agency.
See Chapter 3, for the term Listed in Section
3.2.6*.
(5)
Grade (as it
applies to balconies and decks). On earth; or on blocks, slab or of
other approved material placed on earth and elevated not greater than 30 inches
from earth.
(6)
Permanent. Fastened in place, and cannot be easily moved without
requiring the disconnection of fasteners, piping, and fittings.
(7)
Solid Fuel. Includes wood,
charcoal, pellet fuels, and any other non-gaseous fuel but not including fuel
generation or co-generation of electric energy.
10.10.6.3 Replace with the
following:
10.10.6.3
Solid
Fuel, Gaseous Fuel, and Electric Cooking and Heating Appliances Use and Storage
on Balconies and Decks or under Overhangs and Structures.
10.10.6.3.1 All cooking and heating
appliances shall be permitted to be used, kindled, or stored on a balcony or
deck unless specifically prohibited or restricted below.
10.10.6.3.2 No solid fuel cooking and heating
appliances shall be permitted to be used, kindled, or stored on any
balcony.
10.10.6.3.3 No gaseous
fuel cooking and heating appliances shall be used, kindled, or stored on any
balcony located above grade, unless permitted to be permanently installed
pursuant to its equipment listings.
10.10.6.3.4 No cooking or heating appliances
shall be used, installed, kindled or stored on any fire escape
balcony.
10.10.6.3.5 No cooking or
heating appliances shall be used, installed, kindled or stored on any balcony
or deck where the balcony or deck is enclosed by a roof, walls, other than the
wall of the attached building, or any covering that would prevent air
circulation, unless a sprinkler system is installed in accordance with the
Building Code, or such appliance is permitted by the
manufacturer's instructions and equipment listings.
10.10.6.3.6 No equipment of any cooking and
heating appliances shall be permitted to be used or stored under any overhang;
less than ten ft. (3 m) from a building; unless a sprinkler system is installed
in accordance with the Building Code; or it is permitted by
the manufacturer's instructions and equipment listings. The storage of any
cooking or heating appliances under the overhang or ten ft. (3 m) from a
building shall be permitted only when its fuel is not present within or near
any cooking or heating appliance, unless such appliance is permanently
installed.
10.10.6.3.7 All
appliances that are permanently installed shall be approved by the specialized
code official.
10.10.6.4
Add:
10.10.6.4
LP-gas
Containers (cylinders) 1-lb or Greater, Use, Placement at Dwellings.
10.10.6.4.1
10.10.6.4.4
Add:
10.10.6.4.1 Containers shall
only be transported using exterior means independent from the attached
building.
10.10.6.4.2 Containers
shall not be placed inside or pass through any building.
10.10.6.4.3 Containers shall not be stored or
obstruct ingress or egress of any building.
10.10.6.4.4 Containers having water
capacities greater than 2.7 lb (1 kg) [nominal one lb (0.5 kg) LP-Gas capacity]
shall not be located on decks or balconies of dwellings of two or more living
units above the first floor, unless the deck or balcony is served by exterior
stairways.
10.10.6.5
Add:
10.10.6.5 Table 10.10.6.5
shall be permitted to be used as guidance for the Sections
10.10.6.3.1
through
10.10.6.4.
Table 10.10.6.5 Appliances Used or Stored for Cooking or
Heating
Balcony.
See
10.10.6.2(2) |
Deck, Porch, Patio.
See
10.10.6.2(3) |
*NOT Permitted under overhangs,
roofs or enclosed in by walls or within 10' of a
building1; unless sprinklered pursuant to the
Building Code. |
Fuel |
Gaseous Fuels |
Solid Fuels |
Electric |
Gaseous Fuels |
Solid Fuels |
Electric |
Type of Appliance
|
Cooking and Heating Appliance |
Cooking and Heating Appliance |
Cooking and Heating Appliances |
Cooking and Heating Appliances |
Cooking and Heating Appliance |
Cooking and Heating Appliances |
Grade |
Permitted*
See 10.1.7; 10.10.6.3.4 and
10.10.6.4 |
Not Permitted
See 10.10.6.3.2 |
Permitted See 10.1.7 and
10.10.6.3.1 |
Permitted*
See 10.1.7; 10.10.6.3.5 and
10.10.6.3.6 |
Permitted*
See 10.1.7; 10.10.6.3.5 and
10.10.6.3.6 |
Permitted
See 10.1.7; and
10.10.6.3.1 |
Above Grade |
Not Permitted, unless permanently installed*
See 10.1.7; 10.10.6.3.3; 10.10.6.3.5
and 10.10.6.4 |
10.10.8.1 Delete.
10.11.3.1 Replace with the
following:
10.11.3.1 Enclosed
stairs serving three or more stories and existing enclosed stairs serving five
or more stories shall be maintained in accordance with the
Building
Code approved at the time of construction and maintenance.
10.11.3.1.1 through 10.11.3.2.2
Delete.
10.11.3.3 Replace
with the following:
10.11.3.3
Stairway Tread Marking. Where new contrasting marking is applied
to stairs, such marking shall be maintained in accordance with the provisions
of the
Building Code.
10.11.3.3(1) through (4)
Delete.
10.11.3.4
Delete.
10.11.4 Add:
10.11.4
Inner Courts Specialized
Construction.
10.11.4.1 Any inner court
not protected by a roof shall have a parapet or guard at least 42 inches
high.
10.11.4.2 Where a roof is
provided over an inner court it shall be constructed as prescribed by the
Building Code.
10.11.4.3 Where a skylight is provided it
shall support a minimum of 40 lbs. per square foot, or shall have a parapet or
guard at least 42 inches high.
10.12 Replace with the following:
10.12
Vacant Buildings and
Premises.
10.12.1 Replace with the
following:
10.12.1 Every person
owning or having charge or control of any vacant building, premises, or portion
thereof shall remove all combustible storage, waste, refuse, and vegetation and
shall lock, barricade, or otherwise secure the building or premises to prohibit
entry by unauthorized persons pursuant to M.G.L. c. 143, §§ 6 through
14 and the
Building Code.
10.12.1.1 Delete.
10.12.2 through 10.12.2.2
Replace with the following:
10.12.2
All fire protection systems shall be maintained in service in vacant buildings.
10.12.2.1 With the approval of the AHJ, fire
protection and fire alarm systems in vacant buildings shall be permitted to be
removed from service as provided in M.G.L c. 148, § 27A.
10.12.2.2 When required by the AHJ, other
systems or components pertaining to fire protection shall be maintained as
provided in M.G.L c. 148, § 27A.
10.12.4 through 10.12.4.9
Add:
10.12.4 Any owner of a
building who has been notified that said building shall be made safe or secure
under the provisions of the
Building Code, shall:
(1) Remove all materials determined by the
Head of the Fire Department or Building Official to be dangerous in case of
fire.
(2) Secure all floors
accessible from grade utilizing one of the following methods so long as such
method is approved by the Head of the Fire Department and Building Official in
writing:
(a) Secure all window and door
openings in accordance with the U.S. Fire Administration, Arson Prevention
Initiative Board-up Procedures continuously until such time as the building is
reoccupied; or
(b) Provide 24-hour
watchman services, continuously until such time as the building is reoccupied;
or
(c) Provide a monitored intruder
alarm system at the perimeter of all floors accessible from grade, continuously
until such time as the building is reoccupied.
10.12.4.1 Said owner, as the case may be,
shall notify the Building Official that the approved method chosen to secure
the building has been incorporated.
10.12.4.2 Said owner shall allow the Building
Official to enter the building for an inspection to ascertain that the building
is secured and made safe. Said owner shall allow the Head of the Fire
Department to enter the building.
10.12.4.3 The Building Official shall be
supplied with records of maintenance and operation if the provisions of
Section 10.12.4(2)(b) or (c) are used as provided in the
Building Code.
10.12.4.4 The owner shall maintain any
existing fire alarms or sprinkler systems, unless written permission is
obtained from the Head of the Fire Department in accordance with M.G.L. c. 148,
§ 27A to shut off or disconnect said alarms or systems.
10.12.4.5 The owner shall maintain utilities,
unless written permission is obtained from the Building Official to disconnect
said utilities. Permission to disconnect utilities shall not be granted if it
will result in inadequate heat to prevent freezing of an automatic sprinkler
system or inadequate utilities to maintain any other protection
systems.
10.12.4.6 The requirements
of Section 10.12.4 do not prevent a Building Official from
ordering or taking expeditious, temporary security measures in emergency
situations pending the completion of the requirements of Section
10.12.4.
10.12.4.7 For the
purposes of Section 10.12.4.6, an "emergency situation" shall
be defined as: an unexpected incident, which by its very nature may present a
threat to public safety personnel who may be required to affect a rescue effort
or conduct fire extinguishment operations.
10.12.4.8 Upon refusal or neglect of said
owner to comply with such notice, any Building Official acting under the
authority of the Building Code, shall cause to be secured all
window and door openings accessible from grade in accordance with the U.S. Fire
Administration, Arson Prevention Initiative Board-up Procedures or other
equivalent procedure approved by the Head of the Fire Department, continuously
until such time as the building is reoccupied.
10.12.4.9 Any building which has been made to
conform to the provisions of Section 10.12.4 during vacancy may be reoccupied
under its last permitted use and occupancy classification, provided that any
systems which were disconnected or shut down during the period of vacancy are
restored to fully functional condition and subject to the Building
Code and M.G.L. c. 40A. The Building Official shall be notified in
writing prior to reoccupancy. If said building is changed in use or occupancy
or otherwise renovated or altered it shall be subject to the applicable
provisions of the Building Code.
10.12.5 through 10.12.5.5
Add:
10.12.5 Any building
determined to be especially unsafe in case of fire, under the provisions of the
Building Code shall be identified and caused to be marked by
the Building Official, with the cooperation of the Head of the Fire Department,
to indicate the degree of hazard.
10.12.5.1 In
marking such buildings, the following symbols shall be used:
[\]This symbol shall mean that interior hazards exist to such a
degree that interior operations shall be conducted with extreme caution. This
symbol shall not in any way limit the discretion of the on scene Incident
Commander in directing operations that the Incident Commander deems
necessary.
[X]This symbol shall mean that exterior or interior hazards
exist to such a degree that consideration should be given to conduct operations
from the exterior only. This symbol shall not in any way limit the discretion
of the on scene Incident Commander in directing operations that the Incident
Commander deems necessary.
10.12.5.2 Markings shall be applied on the
front of the building at or above the second floor level, where practical,
between openings such that they are visible from the street. Markings may be
applied to the sides or the rear of a building if the Head of the Fire
Department deems such placement necessary. Markings shall also be applied in a
conspicuous place near every entrance, and on penthouses. Markings shall not be
applied over doors, windows, or other openings where they may be obscured by
smoke or fire.
10.12.5.3 Markings
shall be a minimum of 24 inches by 24 inches. Markings shall either be on a
placard with a reflective background or painted with a reflective paint of
contrasting color directly on the surface of the building. Stripes and borders
outside of the marking shall be a minimum of two inches wide.
10.12.5.4 All markings shall bear a date as
to when applied or the date of the most recent inspection.
10.12.5.5 Prior to receiving a mark, all
buildings shall be inspected thoroughly by the Head of the Fire
Department.
10.13.3. Add:
10.13.3
The Use of Mulch.
10.13.3.1 through 10.13.10.4.2
Add:
10.13.3.1 Mulch shall not be
newly applied within 18 inches of any combustible portion of any building
[
See Figure 10.13.3.4.1(a)].
10.13.3.1.1
Section
10.13.3.1 shall not apply to any building regardless of the existence
of fire separations, containing six dwelling units or less.
10.13.3.2 Mulch, as used here,
shall mean any type of forest material that is produced for the purpose
spreading or application over the surface of the soil as a protective cover, to
retain moisture, reduce erosion, provide nutrients, and suppress weed growth,
seed germination and for general landscaping purposes.
Figure 10.13.3.1(a) Mulch Application
Click to
view image
10.14 Replace with the following:
10.14 Outdoor Events, Carnivals, and Fairs.
10.14.1 Delete.
10.14.4 Delete.
10.14.6 Replace with the following:
10.14.6
Smoke and Carbon Monoxide
Detection. A minimum of one single station smoke alarm and CO detector
shall be located within each sleeping area in all stock or equipment trailers
when they are used for sleeping purposes.
10.14.12.1 Delete.
10.16 Replace with the following:
10.16
Storage.
10.16.1.1 Add:
10.16.1.1 A person shall not store in any
building or upon any premises more than 2,500 cubic feet gross volume of
combustible empty packing cases, boxes, barrels or similar containers; or
rubber tires, baled cotton, rubber, cork or other similarly combustible
material without having obtained a permit from the Head of the Fire
Department.
10.16.1.2
Add:
10.16.1.2
Permits. Permits, where required, shall comply with
Section 1.12.1.05: continued
10.16.2 Replace with the following:
10.16.2 The storage of combustible or
flammable material shall be confined to approved storage areas.
10.16.2.1 Add:
10.16.2.1
Permits. Permits,
where required, shall comply with Section 1.12.
10.16.3 Replace with the
following:
10.16.3
Inside
Storage. Storage in buildings and structures shall be orderly, shall not
be within two feet of the ceiling, and shall be located so as not to obstruct
egress from the building.
10.16.4
Replace with the following:
10.16.4
Outside Storage. The outside storage of combustible or flammable
materials shall not be more than 20 feet in height and shall be compact and
orderly. Such storage shall be located as not to constitute a hazard and no
less than 25 feet from any other building on the site or from a lot
line.
10.17 through
10.17.2 Delete.
10.19.6
Replace with the following:
10.19.6
Attic, Under-floor, and Concealed Spaces. Attic, under-floor, and
concealed spaces used for storage of combustible materials shall comply with
the protection from hazards requirements for storage rooms in the
Building Code.
10.20 through 10.20.1.5
Delete.
10.21 Add:
10.21
Fumigation and Thermal
Insecticidal Fogging. Any substance which by itself or in combination
with any other substance emits or liberates a gas, fume or vapor used for the
destruction or control of insects, fungi, vermin, germs, rats or other pests.
10.21.1 Add:
10.21.1
Permit. Permits, where
required, shall comply with Section 1.12.
10.21.2 Add:
10.21.2
Fumigating Operations.
Any building being so fumigated requiring a permit shall post at all entrances
a warning sign of the fumigant hazard as described in Section
10.21.3.5.
10.21.3
Add:
10.21.3
Fire Safety
Requirements.
10.21.3.1
General. Any person conducting fumigation and thermal insecticidal
fogging in any building, ship, vessel or enclosed space shall comply with the
following fire protection and safety requirements.
10.21.3.2 Add:
10.21.3.2
Sources of Ignition.
All fires, open flames and similar sources of ignition shall be eliminated from
the space under fumigation or thermal insecticidal fogging.
10.21.3.3 Add:
10.21.3.3
Electricity.
Electricity shall be shut off, except that circulating fans that are to be used
shall be designed and installed so as not to create an ignition hazard.
Electrical equipment shall be designed and installed in accordance with
Massachusetts Electrical Code.
10.21.3.4 Add:
10.21.3.4
Notification. The Head
of the Fire Department shall be notified in writing at least 24 hours before
any building or structure is to be closed in connection with the use of any
toxic or flammable fumigant. Such notification shall give the location of the
building, structure, ship or enclosed space to be fumigated or fogged as well
as its character and use, the fumigants or insecticides to be used, the person
or persons in charge of the operation and the date and time when fumigation or
fogging will be started. Notice of any fumigation or thermal insecticidal
fogging shall be served with sufficient advance notice to the occupants of any
building or other enclosed space involved in the operation to enable them to
evacuate the premises.
10.21.3.5
Add:
10.21.3.5
Warning
Signs. Suitable warning signs indicating the danger, type of chemical
involved and recommended precautions, shall be posted on all doors and
entrances to the premises and upon all gangplanks and larders from the deck,
pier or land to the ship. Such notice is to be printed in red ink on white
background. Letters in the signs are to be at least two inches in height and
shall state the date and time of the operation, the name of the operator in
charge, together with a warning to the effect that the premises so occupied
shall be vacated at least one hour before the operation is started and shall
not be reentered until the danger signs have been removed by the proper
authorities.
10.21.3.6
Add:
10.21.3.6
Watchman. During the period fumigation is in progress, except when
fumigation is conducted in a gastight vault or tank, a capable, alert watchman
or watchmen shall remain on duty at the entrance or entrances to the building,
ship or enclosed space fumigated until after the fumigation is completed and
until the premises are properly ventilated and again safe for human occupancy.
Sufficient watchmen shall be provided to prevent any person from entering the
building, ship or enclosed space under fumigation without being
observed.
10.21.3.7 Add:
10.21.3.7
Thermal Insecticidal Fogging
Liquids. Thermal insecticidal fogging liquids with a flash point below
100EF 38EC shall not be used.
10.21.3.8 Add:
10.21.3.8
Fire Protection
Systems. Fire Protection system devices shall be adequately protected by
covering or other means to isolate insecticidal fogging liquids from rendering
a fire system device inoperable. (M.G.L. c. 148, § 27A)
10.22 Add:
10.22
Canine Guards.
10.22.1 Add:
10.22.1
Permit. Permits, where
required, shall comply with Section 1.12.
10.23 through 10.23.4.3.1
Add:
10.23
Emergency Wash
Stations.
10.23.1 Every school, college
and university laboratory newly constructed or renovated, or any room used for
similar purposes wherein corrosives or flammable liquids are handled or where
open flame devices are used, shall be equipped with one or more Emergency Wash
Systems.
10.23.2 Emergency Wash
Systems shall include Drench/Deluge Showers, Handheld Body/Face Washers and
Deck Mounted Drench Hoses. The permanently mounted showers shall be located as
close to the main door of the laboratory as possible (to provide an escape
route), but shall not be located greater than 50 feet from an experimental
area.
10.23.3 The Drench/Deluge
Showers, Handheld Body/Face Washers and Deck Mounted Drench Hoses shall be
installed in accordance with ANSI Z-358.1 and
Board of State Examiners
of Plumbers and Gas Fitters. Each existing laboratory not equipped
with an Emergency Wash System shall be equipped with at least one approved Fire
Blanket, and a sign that reads:
"In Case of Clothing Fire STOP, DROP and ROLL"
10.23.4 The location of the
Emergency Wash System Stations and Fire Blankets shall be clearly indicated by
signs of contrasting color, either RED and WHITE or GREEN and WHITE. The signs
shall be at least 70 square inches in area bearing the words "EMERGENCY WASH
STATION", or "SAFETY SHOWER" or "FIRE BLANKET".
10.23.4.1 Every wash station shall be tested
by the owner of the building or his or her designee twice annually (every six
months) for proper flow and operation. The owner shall, upon request, provide
the fire department with the test result (including, but not limited to): date
of test, station operation, system malfunctions, and the name of the person
performing the test.
10.23.4.2 Each
student shall be advised of the location and proper use of the above emergency
safety equipment by the teacher, instructor, or person in charge of the class
before the first experiment is conducted.
10.23.4.3 Each student shall also be
instructed in the proper procedure for the extinguishment of clothing fires at
least twice during the course, as directed by the Head of the Fire Department.
10.23.4.3.1 The installation and operation of
each safety device noted above shall be in order before the commencement of any
class conducting laboratory experiments.
10.24 Add:
10.24
Maintenance, Inspection, and
Testing.
10.24.1 through
10.24.3 Add:
10.24.1
Whenever or wherever any device, equipment, system, condition, arrangement,
level of protection, fire-resistive construction, or any other feature is
required for compliance with the provisions of this Code, such
device, equipment, system, condition, arrangement, level of protection,
fire-resistive construction, or other feature shall thereafter be continuously
maintained. Maintenance shall be provided in accordance with this
Code, the Building Code and applicable NFPA
requirements, or requirements developed as part of a performance-based
design.
10.24.2 No existing life
safety feature shall be removed or reduced where such feature is a requirement
for new construction. [
101:4.6.12.2]
10.24.2.1 Existing life safety features
obvious to the public, if not required by this Code, shall be
either maintained or removed as provided in M.G.L. c. 148, §
27A.
10.24.3 Any device,
equipment, system, condition, arrangement, level of protection, fire-resistive
construction, or any other feature requiring periodic testing, inspection, or
operation to ensure its maintenance shall be tested, inspected, or operated as
specified elsewhere in this Code and the Building
Code.
Chapter 11
Building Services.
11.1 through
11.1.2.3 Delete.
11.1.6 through
11.1.6.3.4 Delete.
11.1.7.3
through 11.1.7.3.1 Delete.
11.2 through 11.3.7
Delete.
11.5.1.1.1 Add:
11.5.1.1.1
Terms. As used in
Chapter 11, the enclosed terms shall have the following meaning assigned to
them.
11.5.1.1.1.1 through
11.5.1.1.3.1 Add:
11.5.1.1.1.1
Gravity Feed
Burner. A burner which receives its fuel oil supply by static head
pressure due to elevation of the supply source.
11.5.1.1.1.2
Post Purge Control.
An electrical control that is designed to allow the powerventer or burner to
operate after the burner flame has shut off, thus purging the vent system and
heating appliance of combustion gases.
11.5.1.1.2 This Section shall not apply to
fuel oil burners installed in steam boilers of nine horsepower and over and
operated above 15 psi, but shall apply to the fuel oil storage.
11.5.1.1.3
Unsafe Heating
Appliances. The Head of the Fire Department shall order the sealing
(preventing the use) of any existing stove, oven, furnace, incinerator, boiler
or any other heat producing device or appliance found to be defective or in
violation of code requirements for existing appliances after giving 24 hours
notice to this effect to any person, owner, firm, agent or operator in charge
of same. However, the Head of the Fire Department shall seal any device or
appliance without notice when inspection shows the existence of an immediate
fire hazard or when imperiling human life. The sealed defective appliance shall
remain withdrawn from service until all necessary repairs or alterations have
been made.
11.5.1.1.3.1
Unauthorized
Seal Removal. No person or user, firm or agent shall continue the use of
any device or appliance which has been sealed or ordered sealed, unless written
authority to remove said seal is given by the Head of the Fire
Department.
11.5.1.10.5
through 11.5.1.10.10.5 Add:
11.5.1.10.5
General
Requirements.
(1)
Installation. All fuel oil burners and all equipment in connection
therewith shall be installed and maintained in accordance with the
manufacturer's installation and operation manual. Chimneys, connectors, direct
vent systems and power-venters shall also be installed in accordance with the
Building Code.(a) A person
holding a certificate of competency as an oil burner technician may connect or
disconnect for the purpose of repair or replacement, any device or control
required by this Code to be part of an oil burner
installation, or being an integral part of the oil burning equipment, at the
connection on such device, control or part to be repaired or replaced,
notwithstanding any contrary provision of M.G.L. c. 141.
(b) Any person licensed as an electrician
under M.G.L. c. 141 may do any electrical work in connection with the
alteration, repair, or installation of oil burning equipment without being
certified as an oil burner technician.
(2)
Automatic Shut Off. An
approved automatic means to prevent abnormal discharge of fuel oil shall be
provided for any fuel oil burner for which a competent attendant will not be
constantly on duty in the room where the burner is located.
(3)
Exposure to Fire. If any oil
tank, oil burner, oil burner control or wiring related to an oil burner has
been exposed to fire and is suspected of being damaged, the entire installation
shall be made inoperative by the Head of the Fire Department who shall so
notify the owner or occupant of the building or structure. Said installation
shall not be operated until approved by the Head of the Fire
Department.
(4)
Tank
Removal. Unless otherwise provided for in Chapter 66, a permit shall be
obtained, in accordance with Section 1.12.8.2, from the Head
of the Fire Department for the removal of a fuel oil storage tank. Any person
removing a fuel oil storage tank from inside a building for a purpose other
than replacement or repair, shall remove all fill and vent pipes.
(5)
Fuel Oil. The grade of fuel
oil used for any fuel oil burner shall be one which tests and experience have
been shown to be suitable for use with that burner, but in no case shall the
grade of fuel oil be heavier than that for which the burner has been designed
or adjusted.
(6)
Gravity Feed
to Burners. Gravity feed shall be used only with a burner arranged to
prevent abnormal discharge of oil at the burner by automatic means specifically
approved for the burner in which it is used.
(7)
Fuel Oil Delivery. Fuel oil
shall not be delivered to any storage tank, unless the deliverer has knowledge
that a permit has been obtained in accordance with
Section
1.12.8.2.
(a) Fuel oil shall not be
delivered to a storage tank by means of a pump or under pressure in any case
where a tight connection is made between the discharge line and the tank inlet,
unless such storage tank is designed to withstand the additional stress to
which it may be subjected or unless the vent pipe for such tank is of
sufficient size to relieve the tank of any undo pressure in excess of five psi.
The delivery truck operator shall remain at the fill point during the entire
operation.
(8) Fuel oil
equal to the maximum capacity of the storage tank may be delivered without such
a permit being in effect whenever an oil burner installation is first made,
provided that an application has been made in accordance with
1.12.8.2.
(9)
Connection. Cross connection of oil supply and return lines to two
or more supply tanks to the same burner shall be acceptable and shall be made
by a pipe no smaller than 1/2 inch iron pipe or 1/2 inch O.D.
tubing.
(10) Two supply tanks may
be provided with a single fill and a single vent provided:
(a) The fill and vent pipes are not connected
to the same tank;
(b) The crossover
pipe is a minimum two inch diameter with swing joints and a ground joint union;
and
(c) The vent to the outside is
a minimum two-inch diameter.
(11) Tanks shall be mounted on a continuous
concrete slab extending eight inches beyond the perimeter of the tank or
tanks.
11.5.1.10.5.1
Permit. Permits, where required, shall comply with Section
1.12.
11.5.1.10.6
Unenclosed Tanks:
Installation Inside Buildings. When tanks are installed inside garages
or other areas subject to vehicular impact, physical barriers shall be
provided. The physical barrier shall consist of substantial pipes, or similar
barriers.
11.5.1.10.7
Tanks
Installations Outside of Buildings.
(1)
Tanks installed outside of buildings shall be mounted on a continuous concrete
slab at least four inches in thickness and extending eight inches beyond the
perimeter of the tank or tanks.
(2)
Tanks installed outside of buildings shall be securely supported by rigid
noncombustible supports to prevent settling, sliding or lifting.
11.5.1.10.8
Fill and Vent
Piping.
(1) Vent pipes shall terminate
outside of buildings at a point not less than two feet (0.6 m) measured
vertically or horizontally from any building opening.
(2) Outer ends of vent pipes shall terminate
in a weatherproof vent cap or fitting or be provided with a weatherproof hood.
All vent caps shall have a minimum free open area equal to the cross sectional
area of the vent pipe and shall not employ screens finer than four mesh. Vent
pipes shall terminate at least three feet from grade to avoid being obstructed
with snow and ice. Vent pipes from tanks containing heaters shall be extended
to a location where oil vapors discharging from the vent will be readily
diffused. If the static head with a vent pipe filled with oil exceeds ten psi
(70 kPa), the tank shall be designed to withstand the maximum static head which
will be imposed.
(3) A fixed sash
window shall not be considered an opening for the purpose of this
Section.
11.5.1.10.9
Oil Gauging. All storage tanks in which a constant level of oil is
not maintained by an automatic pump shall be equipped with a method of
determining oil level. On cross connected tanks provided with a single fill and
single vent, the gauge shall be installed on the tank vented to the
outside.
11.5.1.10.10
Oil
Burners, Light Fuel Oil Type.
11.5.1.10.10.1
Oil Supply and Return
Lines.
(1) All threaded joints and
connections shall be made tight with suitable lubricant or pipe compound.
Teflon tape shall not be used. Unions requiring gaskets or packings, right or
left couplings, and sweat fittings employing solder having a melting point of
less than 500°F (260°C) shall not be used in oil lines. Compression
type fittings shall not be used.
Exception: Mechanical connections on tubing of the
flare type or gaugeable, two ferrule, swage type fittings are
acceptable.
(2) Oil
supply lines shall be rigidly secured in place and protected from injury and
shall be protected against corrosion. All new oil supply lines in direct
contact with concrete or earth shall be enclosed with a continuous nonmetallic
sleeve that extends out of the concrete or earth a minimum of four inches on
each end. Perimeter lines may be placed in an outer protective covering, in
addition to the continuous nonmetallic sleeve, when subject to physical
damage.
(3) A person holding a
certificate of competency as an oil burner technician may connect or disconnect
for the purpose of repair or replacement, any device or control required by
this Code to be part of an oil burner installation, or being
an integral part of the oil burning equipment, at the connection on such
device, control or part to be repaired or replaced, notwithstanding any
contrary provision of M.G.L. c. 141.
(4) Any person licensed as an electrician
under M.G.L. c. 141 may do any electrical work in connection with the
alteration, repair or installation of oil burning equipment without being
certified as an oil burner technician.
(5) On existing installations, whenever a
burner, boiler, furnace or tank is replaced, the oil supply line shall either
be replaced or enclosed with a continuous sleeve as for new installations or a
listed oil safety valve shall be installed at the tank end of the oil supply
line in accordance with the manufacturer's instructions.
(6) An oil safety valve and continuous
nonmetallic sleeve is not required when:
(a)
The oil supply and return lines are not in direct contact with concrete, earth
or any floor surface.
(b) When the
burner is located above the oil supply tank and the entire oil supply line is
connected to, and above the top of the tank.
(7) Every owner of a residential property
defined as a one- to four-dwelling unit used for living or sleeping (M.G.L. c.
148, § 38J) with oil supply and return lines not enclosed with a
continuous nonmetallic sleeve or equipped with a listed oil safety valve, shall
either replace the line and enclose it with a continuous sleeve as for new
installations or shall have a listed oil safety valve installed at the tank end
of the supply line in accordance with the manufacturer's
instructions.
(8) Nothing in this
Code shall prohibit overhead installation of oil supply and
return lines or cross connection of oil supply lines from multiple
tanks.
(9) Oil supply lines and
return lines to tanks exposed to freezing temperatures shall be connected to
the top of the tank. This shall not apply to gravity feed oil burners using #1
fuel oil, range oil or kerosene.
(10) Oil supply lines shall be properly
reamed and joints and connections shall be made oil tight.
11.5.1.10.10.2
Oil Pumps and
Valves.
Only readily accessible hand operated, fusible, spring loaded
valves of an approved automatic type shall be installed in the oil supply line,
one near each burner and one close to each supply tank so as to automatically
stop the flow of oil in case of fire. Manual opening and ball spring check
valves shall not be permitted.
11.5.1.10.10.3
Oil Burner
Controls.
(1) Each fully automatic oil
burner having a firing rate of no more than 20 gallons per hour shall be
equipped with a type of approved primary safety control which shall shut off
the oil supply to the burner within 15 seconds if ignition is not established
or in the event of flame failure after combustion has been established. Once
combustion is established and in the event of flame failure, the oil supply
shall be shut off to the burner within 3 seconds nominal unless the ignition is
reenergized in not less than 0.8 seconds after flame extinguishment occurs. The
installation of intermittent (formerly called constant) ignition primary safety
controls shall not be permitted.
(2) Each automatically fired, low-pressure
steam heating boiler shall have an automatic low-water fuel cutoff, which may
be a combined feeder/cutoff device. Each automatically fired hot water heating
boiler with heat input greater than 200,000 btus per hour shall have a listed
automatic low water fuel cutoff which has been designed for hot water service,
so located as to automatically cut off the fuel supply when the surface of the
water falls to the lowest safe permissible water level established by the
boiler manufacturer. Each automatically fired, high-pressure steam boiler,
except miniature boilers, shall have at least two automatic low-water fuel
cutoff devices. Each low-water fuel cutoff or combined feeder/cutoff device
shall be labeled and listed to UL 353 as a safety control and/or UL 60730-2-15
as a protective control. All non-residential boiler installations shall comply
with the Board of Boiler Rules specialized codes 522 CMR.
11.5.1.10.10.4
Certificate and License
Requirements for Repair or Replacement of Oil Burner Equipment. In
accordance with M.G.L. c. 148, § 10D, a person holding a certificate as an
oil burner technician may connect or disconnect for the purpose of repair or
replacement, any device or control required by rules and regulations of the
board to be a part of an oil burner installation, or being an integral part of
the oil burning equipment, at the connection on such device, control or part to
be repaired or replaced, notwithstanding any contrary provision of M.G.L. c.
141. Any person licensed as an electrician under said M.G.L. c. 141 may do any
electrical work in connection with the alteration, repair or installation of
oil burning equipment without being certified as an oil burner technician.
(1) Oil burners electrically controlled,
driven and/or operated shall be supplied from a separate branch circuit located
at the service disconnect panel, or at branch circuit subpanel. This circuit
shall be clearly marked for the equipment it controls.
(2) All protective, control and emergency
devices shall be series connected from the electrical distribution panel,
through the emergency switch, through the thermal switch, to the service switch
in the ungrounded line conductors. The burner controls shall be installed in
the ungrounded supply conductors of the circuit and shall not exceed 150 volts
to ground.
(3) A control (service
switch) to start and stop a light fuel oil burner shall be installed at a
location where the operator can view the fire. The switch shall be located at a
maximum of three feet from the burner.
(4) An electrical thermal switch fused to
break the ungrounded conductor in the main circuit at 165EF, shall be installed
in the main power line within six feet over the top of the burner boiler or
burner furnace.
(5) If the ceiling
above the burner boiler or burner furnace exceeds 12 feet in height, an
additional thermal switch shall be installed at a height of ten feet and
connected in series with the lower switch.
(6) Electrical equipment shall not obstruct
clear access to clean out and service panels.
11.5.1.10.10.5
Certificates.
Certificates, where required, shall comply with Section
1.12.8.51.
11.5.2.1 Replace with the
following:
11.5.2.1 The use of
unvented kerosene burners and oil stoves is prohibited by M.G.L. c. 148, §
25B.
11.5.2.2 through
11.5.2.3 Delete.
11.5.3.1 Delete
11.5.4
Vents Delete
11.6.2 Replace with the following:
11.6.2
Installation and
Maintenance. Rubbish chutes and laundry chutes shall be installed and
maintained in accordance with NFPA 82,
Standard on Incinerators and
Waste and Linen Handling Systems and Equipment, unless such
installations are approved existing installations, which shall be permitted to
be continued in service.
11.7.3.2 Delete.
11.7.5.1.1 through 11.7.5.1.2.2
Add:
11.7.5.1.1 A fuel quality test
shall be performed at least annually using tests approved by ASTM
standards.
11.7.5.1.2 Diesel fuel
shall be tested in accordance with ASTM D 975-11b,
Standard
Specification for Diesel Fuel Oils, or ASTM D 6751-11b,
Standard Specification for Biodiesel Fuel Blend Stock (B100) for Middle
Distillate Fuels, as approved by the engine manufacturer, using ASTM D
7462-11,
Standard Test Method for Oxidation Stability of Biodiesel
(B100) and Blends of Biodiesel with Middle Distillate Petroleum Fuel
(Accelerated Method).11.7.5.1.2.1
Where diesel fuel is found to be deficient in accordance with testing required
in Section 11.7.5.1.2, the fuel shall be reconditioned or
replaced, the supply tank shall be cleaned internally, and the engine fuel
filter(s) shall be changed.
11.7.5.1.2.2
After the restoration of
the fuel and tank in 11.7.5.1.2.1, the fuel shall be retested every 6 months
until experience indicates the fuel can be stored for a minimum of one year
without degradation beyond that allowed in 11.7.5.1.2.
11.8.6 through
11.8.9 Add:
11.8.6
Smoke control systems shall be maintained to ensure to a reasonable degree that
the system is capable of controlling smoke for the duration required. The
system shall be maintained in accordance with the manufacturer's instructions
and the Building Code.
11.8.7 A routine maintenance and operational
testing program shall be initiated immediately after the smoke control system
has passed the acceptance tests. A written schedule for routine maintenance and
operational testing shall be established.
11.8.8 A written record of smoke control
system testing and maintenance shall be maintained on the premises. The written
record shall include the date of the maintenance, identification of servicing
personnel, and notification of any unsatisfactory condition and the corrective
action taken, including parts replaced.
11.8.9 Dedicated smoke control systems shall
be operated for each control sequence semiannually. The system shall also be
tested under standby power conditions.
11.9 through 11.9.6
Delete.
11.10.1.1 Delete.
11.10.2 Replace with the following:
11.10.2 Two-way radio communication
enhancement systems, when required, shall be maintained in accordance with
Chapter 24 of NFPA 72: National Fire Alarm and Signaling Code.
11.10.3 Delete.
11.12.2 through 11.12.2.1.4.6
Delete.
11.12.2.1.6 through
11.12.2.1.6.3 Delete.
Chapter 12
Features of Fire
Protection.
12.1 Replace with the
following:
12.1
General. This chapter shall apply to existing, permanent, or
temporary buildings.
12.2 through
12.2.2 Delete.
12.3.1 through
12.3.2.2 Delete.
12.3.3.1
Replace with the following:
12.3.3.1 Required fire-resistive
construction, including fire barriers, fire partition, fire walls, exterior
walls due to location on property, fire-resistive requirements based on type of
construction, draft-stop partitions, and roof coverings, shall be maintained as
constructed or permitted under the Building Code.
12.3.3.3 through 12.3.3.3.2
Delete.
12.4.1 Replace
with the following:
12.4.1
*The installation and maintenance of assemblies and devices used
to protect openings in walls, floors, and ceilings against the spread of fire
and smoke within, into, or out of buildings shall comply with
Section
12.4 and NFPA 80,
Standard for Fire Doors and Other Opening
Protectives and with the
Building Code.
12.4.2.4 through 12.4.2.7
Delete.
12.5.1 through
12.5.6.2.1 Delete.
12.5.7 through 12.5.9.2
Delete.
12.6.2.1*
Smoldering Ignition of Upholstered Furniture.
(3)
The requirements of California
Technical Bulletin 117-2013:
Requirements, Test Procedure and
Apparatus for Testing the Smolder Resistance of Materials Used in Upholstered
Furniture.
12.6.3.3 Add:
12.6.3.3 Seating shall not be purchased,
leased or rented for use in a particular occupancy, unless labeled or
identified by the manufacturer.
12.6.3.3.1
through 12.6.3.5.1(3) Add:
12.6.3.3.1 The following shall be exempt:
(1) Cushions and pads intended solely for
outdoor use.
(2) Any article which
is smooth surfaced and contains no more than 1/2 inch of filling material,
provided that such article does not have a horizontal surface meeting vertical
surface.
(3) Articles manufactured
solely for recreational use or physical fitness purposes, such as weight
lifting benches, gymnasium mats or pads, side horses and similar
articles.
12.6.3.4 Add:
12.6.3.4 For spaces not protected by an
approved sprinkler system, stackable molded plastic seating shall comply with
ASTM E 1822 as modified. The test shall consist of a single chair, or
prototypes thereof.
12.6.3.5
Add:
12.6.3.5
Labeled
Furniture12.6.3.5.1 through
12.6.3.5.1(2) Add:
12.6.3.5.1 The manufacturer shall affix a
label to each article of regulated furniture that indicates:
(1) The article of furniture is composed of
materials that meet the performance test.
(2) The nationally recognized testing
laboratory and standards or publications as provided in this
Code.
12.6.3.5.2 Add:
12.6.3.5.2 The label shall be stitched or
adhered onto each piece of regulated furniture.
12.6.3.6 Add:
12.6.3.6
Documentation of
Furniture.
12.6.3.6.1 Add:
12.6.3.6.1 The building manager shall
maintain documentation of furniture within the building.
12.6.3.6.2 Add:
12.6.3.6.2 The documentation shall be made
available to the AHJ upon request.
12.6.3.6.3 through 12.6.3.8.3(5)
Add:
12.6.3.6.3 The documentation
shall include:
(1) The quantity and type of
each article of furniture.
(2)
Certification that the furniture items meet the performance
requirements.
(3) The nationally
recognized testing laboratory that conducted the tests.
(4) Descriptions of the upholstery cover
fabric for each type of furniture within the inventory area, if the furniture
is upholstered. The description of the upholstery cover fabric shall be
provided by the fabric company or the chair manufacturer, and shall include
fiber content, fabric type, fabric company name, and either a photo of the
fabric for identification, or an actual fabric swatch, clearly labeled, at
minimum size 2 in. x 2 in.
(5) Fire
retardant treatment maintenance and compliance documentation, if applicable.
Table 12.6.9.1.1 Replace with the
following:
Table 12.6.9.1.1 Provisions for Christmas Trees by
Occupancy
Occupancy |
No Tree Permitted
|
Cut Trees Permitted Sprinkler
System Required |
Cut Trees Permitted W/O
Sprinkler System |
Balled Tree
Permitted |
Ambulatory health care |
X |
Apartment Buildings |
X Within the unit |
X Within the unit |
X Within the unit |
Assembly |
X |
Board and care |
X |
Business |
X |
X With Automatic Sprinklers |
Daycare |
X |
Detention and correctional |
X |
Dormitories |
X |
Educational |
X |
Health care |
X |
Hotels |
X |
Industrial |
X |
X With Automatic Sprinklers |
Lodging and rooming |
X |
Mercantile |
X |
X With Automatic Sprinklers |
12.7.1
12.7.6.2.4
Delete.
Chapter 13
Fire Protection Systems.
13.1.1
Replace with the following:
13.1.1
For alarms and systems regulated by this
Code the AHJ shall
have the authority to require that construction documents for all fire
protection systems be submitted for review and approval and a permit be issued
prior to the installation, rehabilitation, or modification in accordance with
Section 1.14. Further, the AHJ shall have the authority to require that full
acceptance tests of the systems be performed in the AHJ's presence prior to
final system certification.
13.1.1.1.2* No
person shall shut off, disconnect, obstruct, remove, and/or impair a fire
protection system or carbon monoxide protection system without first obtaining
a written permit pursuant to
Section 1.12 as required by the
AHJ. [13.1.8 and 13.7.2.2]
A.13.1.1.1.2
See M.G.L. c. 48, § 27A. Except as hereinafter provided, no person
shall shut off, disconnect, obstruct, remove or destroy, or cause or permit to
be shut off, disconnected, obstructed, removed or destroyed, any part of any
sprinkler system, water main, hydrant or other device used for fire protection
or carbon monoxide detection and alarm in any building owned, leased or
occupied by such person or under his control or supervision, without first
procuring a written permit so to do from the head of the fire department of the
city or town wherein such building is situated, which permit such head is
hereby authorized to issue subject to such terms and conditions as, in his
judgment, protection against fire and the preservation of the public safety may
require. This section shall not prevent the temporary shutting off or
disconnection or partial removal of such a system, main, hydrant or other
device for the purpose of making necessary repairs or preventing freezing or
other property damage; provided, however, that the head of the fire department
is notified immediately of such emergency action. The head of the fire
department shall also be notified when the system, main, hydrant or other
device is placed back in service. Violation of this section shall be punished
by imprisonment for not more than one year or by a fine of not more than one
thousand dollars, or both. The supreme judicial and superior courts shall have
jurisdiction in equity to enforce compliance with the provisions of this
section.
13.1.10 Replace with the following:
13.1.10 No person shall shut off, disconnect,
obstruct, remove, and/or modify a fire protection system or carbon monoxide
protection system without first procuring a written permit in accordance with
Section 1.12 from the AHJ. The AHJ shall be notified when any
fire protection system is out of service and on restoration of
service.
13.2.1.1 Delete.
13.2.2 through
13.2.2.5(3)
Delete.
13.3.1.1 Replace with the
following:
13.3.1.1 Automatic
sprinklers shall be installed and maintained in full operating condition in
accordance with this Code and the applicable standard or
document for such system referenced in Chapter 2.
13.3.1.4 Delete.
13.3.2.1 Delete.
13.3.2.7.1 through
13.3.2.21.1.2
Delete.
13.3.2.21.1.3 Replace with the
following:
13.3.2.21.1.3
High-rise Buildings. See M.G.L. c. 148,
§§ 26A and 26A1/2.
13.3.2.21.1.4 through
13.3.2.21.4.2 Delete.
13.3.2.22.1 Delete.
13.3.2.22.3 through 13.3.2.23
Delete.
13.3.2.23.1 Replace with
the following:
13.3.2.23.1
See M.G.L. c. 148, § 26.
13.3.2.24 through 13.3.2.29
Delete.
13.4.2 through
13.4.2.2 Delete.
13.6.1.1.3
Add:
13.6.1.1.3
Certificates. Certificates, where required, shall comply with
Section 1.13.
13.7
through 13.7.4.5.6 Delete this Section and Replace with the
following:
13.7.
Smoke Alarms
and Detectors, Permits, Massachusetts General Laws, Primary Power Sources, and
Carbon Monoxide Protection Systems.
13.7.1 For systems regulated by this
Code, the AHJ shall have the authority to require construction
documents for all fire protection and carbon monoxide systems to be submitted
for review and approval and a permit to be issued prior to the installation,
rehabilitation, or modification. Further, the AHJ shall have the authority to
require that full acceptance tests of the systems shall be performed in the
AHJ's presence prior to final system certification.
13.7.2
Permits. Permits, where
required, shall comply with
Section 1.12.
13.7.2.1 For installations described in
Section 13.7 governed by permits issued, the applicable code
shall be determined based on the date of issuance stated on the
permit.
13.7.2.2 No person shall
shut off, disconnect, obstruct, remove, and/or impair a fire protection system
or carbon monoxide protection system without first procuring a written permit
pursuant to Section 1.12 as required by the AHJ.
13.7.3
Massachusetts General
Laws.
13.7.3.1 For the purpose of
compliance with M.G.L. c. 148, §§ 26E and 26F, smoke alarms shall be
installed in accordance with the applicable requirements of Section
13.7.
13.7.4
Smoke Detection.
13.7.4.1
General. Where fire warning equipment is required by this
Code to be installed in a building, such equipment shall be
installed in accordance with Massachusetts Electrical Code,
NFPA 72: National Fire Alarm and Signaling Code and
Section 13.7.
13.7.4.2 Low voltage system batteries for
smoke detectors shall be maintained in accordance with applicable Sections of
NFPA 72: National Fire Alarm Signaling Code by the owner,
landlord or superintendent.
13.7.4.3
Heat Detection.
13.7.4.3.1 The Head of the Fire Department
shall be permitted to require the installation and interconnection of heat
alarms/detectors in unheated open porches with stairways. Where such heat
alarm/detector is required, it shall be listed for such use.
13.7.5
Primary
Power Source.
13.7.5.1 Smoke
alarms/detectors, and carbon monoxide alarms shall be permitted to have battery
power as a primary source, unless otherwise prohibited by applicable laws,
codes, or standards.
13.7.5.1.1
Nonrechargeable, Nonreplaceable Battery Power Alarms/Detectors.
(1) Photoelectric technology shall be
required for smoke alarms and detectors.
(2) A silence button shall be required on
each smoke alarm, or detector device; within its control panel.
(3) Each smoke alarm and detector device
shall be equipped with a nonrechargeable battery.
(4) Each smoke alarm and detector device
shall be equipped with a nonreplaceable battery.
(5) All power requirements for all smoke
alarms and detectors shall be met for at least ten years of battery life,
including weekly testing.
(6) All
power requirements for combination alarms with smoke/carbon monoxide shall be
capable of powering the unit for its service life, including testing.
(7) Household fire warning systems and smoke
detectors shall receive their power in accordance with NFPA 72:
National Fire Alarm and Signaling Code.
13.7.5.1.2
Battery Powered with Network
Technology (wireless) Alarms/Detectors.
(1) Photoelectric technology shall be
required for smoke alarms/detectors.
(2) All power requirements for all alarms and
detectors are met for at least one year of battery life, including weekly
testing.
13.7.5.1.3
Other Technologies and Nonrequired Devices.
13.7.5.1.3.1 Where devices in
Sections 13.7.5.1.1 and
13.7.5.1.2 have been
installed, and placed, alarms and detectors having other technologies and or
additional devices shall be permitted as provided in
Sections
13.7.5.1.3.1(1) and (2).(1) Other
technologies that are part of the same unit shall be permitted with
photoelectric technology.
(2)
Non-required devices shall be permitted to be connected with required devices
or installed within the same or different space, area, or location as provided
in Table 13.7A, Table 13.7C and Table 13.7D, provided such devices have been
installed in accordance with their applicable listings and have been tested,
inspected and maintained pursuant to Section 10.24.
13.7.5.1.4
Types
of Device.
13.7.5.1.4.1 The following
types of device shall be required:
(1) A
single station or multiple station alarm;
(2) Detector;
(3) A device as one unit with one or more
technologies; and
(4) Types of
devices listed in Sections 13.7.5.1.4.1(1) through (3) shall
be pursuant to Table 13.7B.
13.7.5.1.4.2
Device
Requirements.
13.7.5.1.4.2.1 The
following device requirements shall comply with the following:
(1) Devices shall be placed pursuant to Table
13.7A and Table 13.7C as applicable.
(2) Single station or multiple station alarms
shall meet standard ANSI/UL217: Standard for Safety Smoke
Alarms as provided in Table 13.7B.
(3) Smoke detectors shall meet standard
ANSI/UL268: Smoke Detectors for Fire Alarm Signaling Systems
as provided in Table 13.7B.
(4)
Devices provided in Sections 13.7.5.1.4.1(1) through (3) with an integrally
mounted heat detector shall meet the following standards as provided in Table
13.7B as applicable
(a) Standard ANSI/UL 521:
Heat Detectors for Fire Protective Signaling Systems that
covers heat detectors for fire protective signaling systems
(b) Standard ANSI/UL 539: Single and
Multiple Station Heat Alarms that covers heat-actuated, single and
multiple station heat alarms
(5) A combination device as a single unit
with two or more technologies shall meet the following standards as provided in
Table 13.7B and as provided below:
(a) ANSI/UL
217: Standard for Safety Smoke Alarms and ANSI/UL 2034:
Standard for Single and Multiple Station Carbon Monoxide
Alarms for combination alarms with smoke/carbon monoxide
technologies;
(b) ANSI/UL 268:
Smoke Detectors for Fire Alarm Signaling Systems and ANSI/UL
2075: Standard for Safety Gas and Vapor Detectors and Sensors
for combination detectors with smoke/carbon monoxide technologies.
(6) A device shall be permitted to
be a single or multiple station alarm or detector with smoke and or heat
detection and or carbon monoxide and or intrusion technologies within the same
unit provided all of the conditions listed below in
Sections
13.7.5.1.4.2.1(6)(a) and
(b) for alarms or
(b) and
(c) for detectors are met:
(a) Combination devices with two or more
technologies that are incorporated into one unit shall have simulated voice and
tone alarm features which clearly distinguishes between two or more events such
as carbon monoxide and smoke.
(b)
Fire alarm signal shall take precedence, even when a non-fire alarm signal is
initiated first.
(c) Combination
detectors shall be permitted to satisfy requirements for both smoke and carbon
monoxide detection required by this Code when listed in
accordance with UL 268: Standard for Safety Smoke Detectors for Fire
Alarm Systems and UL 2075: Standard for Safety Gas and Vapor
Detectors and Sensors.
(7) Such combination devices shall include
both simulated voice and tone alarm features which clearly distinguishes
between carbon monoxide and smoke notification, unless such system employs the
following:
(a) Each such combination device
produces a distinctive audile and visual alarm signal for smoke and carbon
monoxide, in accordance with NFPA 72: National Fire Alarm Signaling
Code;
(b) A control unit
or annunciator is installed displaying a distinctive alphanumeric message
(digital or embossed) for smoke and carbon monoxide;
(c) Where such control unit or annunciator is
installed it shall be located in an accessible area within each dwelling unit
and be visible at all times; and
(d) For transient residential and
institutional structures, such control unit or annunciator shall be located at
the constantly attended location and shall be monitored.
13.7.6
Carbon Monoxide
Detection.
13.7.6.1
General. For the purposes of M.G.L. c. 148, § 26FU, carbon
monoxide detection shall be provided and installed in accordance with
NFPA 72: National Fire Alarm Signaling Code and
Section 13.7.6.
13.7.6.2 Every owner, superintendent or
landlord of every structure that employs carbon monoxide alarm protection by
utilizing one or more of the carbon monoxide protection technical options
listed in
Section 13.7.7 equipped with a voice or annunciator
as provided in
Section 13.7.6.5.1 shall prepare a written
emergency plan that is in effect and available to all personnel. The plan shall
be presented to and approved by the Head of the Fire Department.
(1) The plan shall include at a minimum:
(a) The development of a policy and procedure
as a means to immediately communicate the alarm to the fire
department;
(b) An evacuation plan;
and
(c) A list of emergency contact
phone numbers of responsible parties.
(2) An annual review by the owner,
superintendent or landlord of the plan with all employees, who shall be kept
informed in respect to their duties and responsibilities under the
plan;
(3) Systems installed in
accordance with Section 13.7.6.5.1 shall include information
within each room indicating evacuation procedures in the event of an alarm
condition.
13.7.6.3
Annually, the owner, superintendent or landlord of every structure shall submit
to the Head of the Fire Department an updated emergency plan, record of
inspection, maintenance and testing on a form prescribed by the State Fire
Marshal.
13.7.6.4
Terms. As used in Chapter 13, the enclosed terms shall have the
following meaning assigned to them.
13.7.6.4.1
Adjacent Spaces. Any area, space, room, or dwelling unit located
directly next to, below, or above any area space, room, or dwelling unit that
contains fossil fuel burning equipment or enclosed parking. It shall not
include closets, bathrooms, cabinets, or similar areas used for storage or
utility purposes and temporarily occupied for activities relating to such
storage or utility use.
13.7.6.4.2
Centralized Fossil Fuel Burning Equipment. A central heating
plant, hot water heater, a combustion driven generator or fire pump, central
laundry equipment, roof mounted air handling unit or similar equipment that
emits carbon monoxide as a by-product of combustion and does not allow for air
exchange between centralized fossil fuel burning equipment and dwelling units
or common areas.
13.7.6.4.3
Combination Device. A device that employs more than one technology
within the same unit such as smoke and carbon monoxide.
13.7.6.4.4
Carbon Monoxide
Device. A device intended for the purpose of detecting carbon monoxide
gas and alerting occupants either by a distinct audible signal comprising an
assembly that incorporates a sensor, control components and an alarm
notification appliance in a single unit (alarm) or through a connection to an
alarm control unit (detector).
13.7.6.4.5
Daycare Facility. A
facility licensed by the Commonwealth under M.G.L. c. 15D, §§ 5, 6,
and 7 or under the Department of Early Education and Care as a Child Care
Center, School Aged Child Care Program, or Family Child Care Home, including
Large Family Child Care and Family Child Care Plus. (606 CMR 7.00:
Standards for the Licensure or Approval of Family Child Care; Small
Group and School Age and Large Group and School Age Child Care
Programs.)
13.7.6.4.6
Dwelling Unit. As used in Table 13.7D, Dwelling Unit means a
single unit providing facilities for living and sleeping and used for
residential purposes, unless specifically identified otherwise.
13.7.6.4.7
Enclosed Parking. A
structure or an area or room, or floor or level thereof, enclosed within an
overall building or structure or attached thereto that is designed or used for
the parking of vehicles and does not comply with the minimum exterior wall
opening requirements in the Building Code.
13.7.6.4.8
Fossil Fuel Burning
Equipment. Any device, apparatus, or appliance which is designed or used
to consume fuel of any kind in which such equipment emits carbon monoxide as a
by-product of combustion.
13.7.6.4.9
Habitable. An area or
space such as a cellar, basement, or attic that is designed, used, or equipped
with furnishing for living purposes.
13.7.6.4.10
Intermittent Ignition
Device. A device which ignites an automatic gas appliance to begin
normal operation thereof and which is activated only at the time such automatic
gas appliance is to be so ignited.
13.7.6.4.11
Institutional
Structures. Any dwelling, building, or structure classified as use group
I-1 through I-3, as defined in the Building Code and those
unclassified occupancies that have the same characteristics as I-1 through I-3.
Where there is a dispute regarding use group classification of a structure, a
determination shall be made by the municipal or state building inspector having
jurisdiction.
13.7.6.4.12
Residential Structures. Any dwelling, building, or structure
classified as use group R-1 with less than six dwelling units or R-2 through
R-5, as defined in the Building Code and those unclassified
occupancies that have the same characteristics as an R-1 with less than six
dwelling units or R-2 through R-5. Where there is a dispute regarding use group
classification of a structure, a determination shall be made by the municipal
or state building inspector having jurisdiction.
13.7.6.4.13
Roof Mounted Fossil Fuel
Burning Equipment. Any fossil fuel burning equipment mounted on top of a
structure that is used to condition any medium through heating or
cooling.
13.7.6.4.14
Transient Residential Structures. Any dwelling, building, or
structure classified as use group R-1 with six or more dwelling units, as
defined in the Building Code and those unclassified
occupancies that have the same characteristics as R-1 with six or more dwelling
units. Where there is a dispute regarding use group classification of a
structure, a determination shall be made by the municipal or state building
inspector having jurisdiction.
13.7.6.5
Carbon Monoxide
Requirements. A carbon monoxide device shall be installed as provided in
Section 13.7.6 and Table 13.7D and placed in the following
locations:
(1) On every habitable level of a
dwelling unit with or without a sleeping area.
(2) In habitable portions of basements,
cellars, and attics.
(3) Within the
immediate vicinity of a sleeping area but within ten feet measured in any
direction from the door to the sleeping area (bedroom).
(4) In each level of each dwelling unit in
transient residential and institutional structures, with fossil fuel burning
equipment or enclosed parking.
(5)
One carbon monoxide alarm shall be installed in each room used by children for
sleeping, learning, or participating in early education and care activities in
daycare facilities.
(6) Carbon
monoxide protection in Family Child Care Homes, Large Family Child Care and
Family Child Care Plus facilities shall comply with Sections 13.7.6.5
(1), (2), and (3).
13.7.6.6
Voice or Annunciators.
13.7.6.6.1 Smoke and carbon monoxide
technologies shall be permitted to be installed as one unit as a combination
device. Combination devices shall include both simulated voice and tone alarm
features which clearly distinguishes between carbon monoxide and smoke
notification, unless such system employs the following:
Each combination device initiates a distinctive audile and
visual alarm signal for smoke and carbon monoxide, in accordance with NFPA 72:
National Fire Alarm Signaling Code and;
(1) Within each dwelling unit, a control unit
or annunciator is installed displaying a distinctive alphanumeric message
(digital or embossed) for smoke and carbon monoxide and;
(2) Where such control unit or annunciator is
installed it shall be located in an accessible area within each dwelling unit
and be visible at all times.
(3)
For transient residential and institutional structures, such control unit or
annunciator shall be located at the constantly attended location and shall be
monitored.
Table 13.7A
Smoke Alarms and Detectors
Device, Placement, Power Supply, Type and Wiring
Household Fire Warning
For one and not more than two dwelling units
Pre-1975- Dwellings-
Pursuant to M.G.L. c. 148, §§ 26E and
26F1,2
(Not substantially altered to constitute
new) |
Device |
(1) Smoke alarms/detectors installed shall require
photoelectric technology. |
Placement |
(2) Smoke alarms/detectors shall be placed:
(a) on every habitable level
(b) on the basement level
(c) on the ceiling of each stairway leading to the
floor above, but not within each stairway, at the base of each stairway,
including stairways to an unfinished/unheated basement/cellar
(d) on ceiling outside of each separate sleeping
area
(e) in common areas on ceilings |
Power Supply |
(3) Smoke alarms/detectors pursuant to M.G.L. 148,
§ 26E:
(a) shall be permitted to have either battery or,
primary power pursuant to M.G.L. c.148, § 26E for their power supply;
and
(b) Smoke alarms/detectors that do not include a
secondary power source and have a battery as its primary power source shall
meet the power provisions and conditions as provided in Section
13.7.5 |
Type of Device |
(4) Types of device shall be permitted to be a single
station or multiple station alarm or detector. See Section
13.7.5.1.3 |
Type of Technology |
(5) Technology
(a) Photoelectric shall be required, see
Sections 13.7.5.1.1 and 13.7.5.1.2
(b) Other types of technologies with required
photoelectric technology. See Section 13.7.5.1.3 |
Wiring |
(6) Non-interconnected smoke alarms/detectors shall
be permitted within the dwelling unit.
(7) Smoke/Heat alarms/detectors:
(a) in a single family dwelling unit shall be
permitted to be interconnected in basements
(b) in a two-family dwelling unit shall be
interconnected in common areas and in basements |
NOTE 1. A dwelling, as used here, means one or
more units providing facilities for cooking, sanitary, living, sleeping or
eating.
NOTE 2. For compliance with M.G.L. c. 148, §
26F in existing buildings,
527
CMR 1.05: 1.1 may be applicable.
Table 13.7B
Listings for Smoke and Carbon Monoxide Detectors and
Alarms
Smoke and Carbon Monoxide alarms and detectors
shall be listed as provided below. |
Smoke Alarm and Detector |
Heat Detection |
Carbon Monoxide Smoke Alarms and
Detectors |
ANSI/UL 217 covers electrically operated single and
multiple station smoke alarms. |
ANSI/UL 539 covers heat-actuated, single and multiple
station heat alarms. |
ANSI/UL 2034 covers electrically operated single and
multiple station carbon monoxide (CO) alarms. |
ANSI/UL 268 covers smoke detectors for fire
protective signaling systems. |
ANSI/UL 521 covers heat detectors for fire protective
signaling systems. |
ANSI/UL 2075 covers toxic and combustible gas and
vapor detectors and sensors. |
Combination smoke/carbon monoxide alarms shall be
listed and labeled in accordance with ANSI/UL 217 and ANSI/UL 2034. |
Combination smoke/carbon monoxide detectors shall be
listed and labeled in accordance with ANSI/UL 268 and ANSI/UL 2075. |
Table 13.7C
Smoke Alarms and Detectors
Device, Placement, Power Supply, Type and Wiring
Household Fire Warning
For three or more dwelling units, but less than six
Pre-1975-Dwellings-
Pursuant to M.G.L. c. 148, §§ 26E and
26F1,2
(Not substantially altered to constitute
new) |
Device |
(1) Smoke alarms/detectors shall require
photoelectric technology. |
Placement |
(2) Smoke alarms/detectors shall be placed:
(a) on every habitable level
(b) on the basement level
(c) on the ceiling of each stairway leading to the
floor above, but not within the stairway, at the base of each stairway,
including stairways to an unfinished/unheated basement/cellar
(d) on ceiling outside of each separate sleeping
area.
(3) Smoke alarms/detectors shall be placed in common
areas on the ceiling.
(4) Heat alarms/detectors required by Section
13.7.4.3 shall be placed:
(a) in open porches with stairs on the ceiling
(b) in common areas on the ceiling. |
Power Supply |
(5) Smoke alarms/detectors pursuant to M.G.L. 148,
§ 26E:
(a) shall be permitted to have either battery or,
primary power pursuant to M.G.L. c. 148, § 26E for their power supply for
alarms/detectors:
(b) Smoke alarms/detectors that do not include a
secondary power source and have a battery as its primary power source shall
meet the power provisions and conditions as provided in
13.7.5
(c) Common halls and basements shall have their power
supply by primary power pursuant to M.G.L. c. 148, § 26E. |
Type of Device |
(6) Types of device shall be permitted to be a single
station or multiple station alarm or detector. See Section
13.7.5.1.3. |
Type of Technology |
(7) Technology
(a) Photoelectric shall be required, see
Sections 13.7.5.1.1 and 13.7.5.1.2
(b) Other types of technologies with required
photoelectric technology. See Section 13.7.5.1.3 |
Wiring |
(8) Non-interconnected smoke alarms/detectors shall
be permitted to be within the dwelling unit.
(9) Smoke/Heat alarms/detectors shall be
interconnected in common areas and in basements |
NOTE 1. A dwelling, as used here, means one or
more units providing facilities for cooking, sanitary, living, sleeping or
eating.
NOTE 2. For compliance with M.G.L. c. 148, §
26F in existing buildings,
527
CMR 1.05: 1.1 may be applicable.
Table 13.7D
Carbon Monoxide Detection Requirements for
Dwellings1
Device |
(1) Carbon Monoxide Devices. |
Placement |
(2) Carbon monoxide devices shall be installed in the
following locations:
(a) on every level of a dwelling unit with or without
a sleeping area;
(b) in habitable portions of basements, cellars and
attics;
(c) installed within the immediate vicinity of a
sleeping area but within ten feet measured in any direction from the door to
the sleeping area [bedroom];
(d) on every level in every dwelling unit of
transient or institutional structures with fossil-fuel burning equipment or
enclosed parking garage;
(e) in each room used for sleeping or learning in
daycare facilities; and (f) in locations (d) through (e) for Family Child Care
Homes, Large Family Child Care, and Family Child Care Plus
facilities. |
Power Supply |
(3) Carbon monoxide devices shall be powered as
follows:
(a) Battery powered, wireless appliances or an A/C
(alternating current) plug-in with battery backup in accordance with NFPA 72
shall be installed in day care facilities and residential structures.
(b) A/C primary power source with battery backup in
compliance or wireless systems with secondary power in compliance with NFPA 72
shall be installed in transient residential or in institutional
structures.
(c) Carbon Monoxide alarms that do not include a
secondary power source and have a battery as its primary power source shall
meet the power provisions and conditions as provided in Section
13.7.5. |
Type of Device |
(4) Single or multiple station smoke alarms/detectors
or combination smoke and carbon monoxide technologies in one unit shall be
permitted per Sections 13.7.5.1.3 and
13.7.5.1.4. |
Technical Options |
(5) In lieu of providing carbon
monoxide protection within each level of each dwelling unit, it shall be
permitted to use one or more of the carbon monoxide protection technical
options as provided in Section 13.7.7. However,
notwithstanding the use of any alternative compliance option, carbon monoxide
protection shall also be installed in any dwelling unit that contains fossil
fuel burning equipment. |
Wiring |
(6) Non-interconnected carbon monoxide alarms and
detectors shall be permitted to be within the dwelling unit. |
NOTE 1. A dwelling, as it is used, here shall mean
a single unit providing facilities for living and sleeping and used for
residential purposes.
13.7.7
Technical Options. In
lieu of providing carbon monoxide alarm protection within each
level of each dwelling unit, it shall be permitted to use one or more of the
carbon monoxide protection technical options as described in
Section
13.7.7. However, notwithstanding the use of any alternative compliance
option, carbon monoxide alarm protection shall also be installed in any
dwelling unit that contains fossil fuel burning equipment.
(1)
Type A. Carbon monoxide
protection shall provide visual and audible notification in the rooms or areas
containing the fossil fuel burning equipment. Such protection shall be
monitored in accordance with NFPA 72: National Fire Alarm Signaling
Code. Such method of monitoring is to be determined at the discretion
of the building owner. In accordance with NFPA 72, the retransmission of the
signal shall be at the discretion of the Head of the Fire Department.
(2)
Type B. Carbon monoxide
protection for areas or rooms of centralized fossil fuel burning equipment
consisting of kitchen appliances equipped with an intermittent ignition device
shall comply with the Fuel/Gas Plumbing Code and NFPA 54: National Fuel
Gas Code. A written certification shall be submitted to the Head of
the Fire Department from a registered professional engineer licensed by the
Commonwealth, certifying that the kitchen appliances meet Fuel/Gas Plumbing
Code and said NFPA 54.
(3)
Type C. Carbon monoxide protection for areas or rooms with
centralized fossil fuel burning equipment which employ an automatic integrated
shutdown device which shall be directly connected to the fossil fuel burning
equipment and an A/C primary power source with battery backup in compliance
with NFPA 72:
National Fire Alarm Signaling Code or low
voltage or wireless systems in compliance with NFPA 72 that will cause a shut
down to the fossil fuel burning equipment upon activation of a carbon monoxide
device. The device must also provide an audible or visual alarm in the
immediate area of the device and fossil fuel burning equipment. The fossil fuel
burning equipment must be manually restarted after activation. A sign shall be
mounted in the vicinity of the device with a minimum of one inch high letters
in contrasting color with the following statement: "If the carbon monoxide
device has activated, do not restart the equipment until serviced by a
qualified technician".
Exception: Such shut down requirement shall not be
applicable to systems that are part of an emergency or standby system required
by any municipal, state or federal law or regulation, provided the carbon
monoxide detection system shall be monitored in accordance with NFPA 72:
National Fire Alarm Signaling Code.
(4)
Type D. Carbon monoxide
protection for adjacent spaces of structures, areas or rooms considered
enclosed parking, shall employ listed carbon monoxide alarm protection meeting
AN SI/UL 2075: Standard for Safety Gas and Vapor Detectors and
Sensors or a low voltage or wireless system. Such installation shall
provide a visual or audible alarm in the rooms or areas containing the fossil
fuel burning equipment. Such protection shall be monitored in accordance with
NFPA 72: National Fire Alarm Signaling Code. Such method of
monitoring is to be determined at the discretion of the building owner. In
accordance with NFPA 72, the retransmission of the signal shall be at the
discretion of the Head of the Fire Department.
(5)
Type E. Carbon monoxide
protection for enclosed parking shall employ, in the enclosed parking either:
(a) An automatic mechanical ventilation
system that automatically operates upon detection of carbon monoxide in
accordance with the Building Code, without exception or
reduction and provides for a supervisory alarm at 50 parts per million (ppm) in
accordance with NFPA 72: National Fire Alarm Signaling Code.
Such method of monitoring is to be determined at the discretion of the building
owner in accordance with NFPA 72 and the retransmission of the signal shall be
at the discretion of the Head of the Fire Department; or
(b) The enclosed parking has continuous
mechanical ventilation at a minimum rate in accordance with the
Building Code without exception or reduction. Such system
shall employ a sensor to ensure the minimum airflow as designed is operating
through the system. The sensor shall monitor direct airflow and shall be
connected to the fire alarm panel as a supervisory alarm in accordance with
NFPA 72: National Fire Alarm Signaling Code. A registered
professional engineer licensed by the Commonwealth shall provide written
certification to the Head of the Fire Department that the subject enclosed
parking meets the requirements of Type (E).
(6)
Type F. Carbon monoxide
protection for roof mounted fossil fuel burning equipment that circulate air
from said unit to common areas only, shall be equipped with the following: A
duct carbon monoxide gas detection device shall be installed on the discharge
side of the roof mounted air handling unit or the common areas on the floor
closest to the initial supply discharge from the roof mounted air handling
unit. All such devices shall be installed in accordance with the manufacturer's
instructions. The carbon monoxide gas detection device shall automatically
alarm upon detection of carbon monoxide at 50 parts per million (ppm) and
provide for a supervisory alarm in accordance with NFPA 72:
National
Fire Alarm Signaling Code. Such method of monitoring is to be
determined at the discretion of the building owner in accordance with NFPA 72,
and the retransmission of the signal shall be at the discretion of the Head of
the Fire Department. Upon activation of the carbon monoxide detection device
and supervisory alarm, the roof mounted fossil fuel burning equipment shall
shutdown until manually reset.
Exception: Such shut down requirement shall not be
applicable to systems that are part of an emergency or standby system required
by any municipal, state or federal law or regulation.
(7)
Type G. Carbon
monoxide protection for roof mounted fossil fuel burning equipment that do not
circulate air to any common area or dwelling unit. (Reserved)
(8)
Type H. Carbon monoxide
protection for certain institutional structures that contain fossil fuel
burning equipment that circulates air to patient rooms, inmate rooms or common
areas. Carbon monoxide protection for certain institutional structures
classified as either use group I-2 or I-3, that contains fossil fuel burning
equipment that circulates air to dwelling units occupied by patients or inmates
may be equipped with type H protection if the following conditions are met:
(a) Such structure contains dwelling units
occupied by a person or persons who are not capable of self preservation due to
age, mental disability, medical condition, incarceration, restraint, or
security; and
(b) The occupants are
under constant supervision on a 24-hour basis.
13.7.7.1 Type H protection shall include a
duct carbon monoxide gas detection device which shall be installed downstream
of air filters, ahead of any branch connections in air supply systems of the
fossil fuel air handling unit. All such devices shall be installed in
accordance with the manufacturer's instructions. The carbon monoxide gas
detection device shall automatically alarm upon detection of carbon monoxide at
50 parts per million (ppm) and provide for a supervisory alarm in accordance
with NFPA 72: National Fire Alarm Signaling Code. Such method
of monitoring is to be determined at the discretion of the building owner in
accordance with NFPA 72 and the retransmission of the signal shall be at the
discretion of the Head of the Fire Department. Upon activation of the carbon
monoxide detection device and supervisory alarm, the fossil fuel burning
equipment shall shutdown until manually reset.
13.7.8 Fire alarm systems required by the
Building Code shall be monitored.
Exception: Single and multiple station smoke alarms
required by the Building Code in other than Groups R-1 and R-2 with more than
16 units. Smoke detectors in Group I-3 occupancies automatic sprinkler systems
and single- and multi-station smoke in three through five family dwellings.
Smoke detectors in patient sleeping rooms in occupancies in Group
I-2.
13.7.8.1 In all cases,
central stations and those operating approved remote/proprietary station fire
alarm system supervising stations shall retransmit alarm signals within 90
seconds of receipt, to the fire department having jurisdiction.
13.7.8.2 Identical control diagrams showing
all devices in the system and identifying their location and function shall be
maintained current and kept on file with the AHJ and shall be kept on site,
adjacent to the fire alarm panel in a format and manner approved by the
AHJ.
13.7.8.3 A copy of the final
report required by the Building Code shall be filed with the
fire code official and the building code official and an identical copy shall
be maintained in an approved location at the building.
13.7.8.4 All signs required to identify fire
protection equipment, equipment rooms and equipment locations shall be
constructed of durable materials, be permanently installed, and be readily
visible. Letters and numbers shall contrast with the sign back ground, shall be
at least two inches in height, and shall have an appropriate width-to-height
ratio to permit the sign to be read easily from a distance of ten feet. The
sign and location shall be approved by the AHJ.
13.7.8.5
A-2 Nightclub Use as of
January 1, 2007: New Construction, Change of Use, or Substantial
Modification. The activation of any "fire protection system" element
(signaling system, detection, sprinklering,
etc.) shall
automatically:
(1) Cause immediate
illumination of all areas and components of the required means of egress, and
additionally;
(2) Cause immediate
full activation of all other house lighting; and
(3) Cause immediate stopping of any and all
sounds and visual distractions (public address systems, entertainment and dance
lighting, music, etc.) that conflict/compete with the fire
protective signaling system. [See the Building
Code] [See Chapter 1, of this Code,
Section 1.1.4 for maintaining these
provisions]
13.8 Replace as follows:
13.8
Other Fire Protection
Systems.
Where other fire protection systems are required to be
installed by the provisions of this Code, or are installed
with the approval of the AHJ as an alternative or equivalency, the design and
installation of the system shall comply with the appropriate standards listed
in Table 13.8.1. The system shall be tested and maintained in accordance with
Section 10.24.
13.8.1
through 13.8.2 Delete
13.10 through 13.10.10.2
Add:
13.10
Inspection,
Testing, and Maintenance.
13.10.1
Application. The inspection, testing, and maintenance of single-
and multiple-station alarms, fire alarm systems and household fire warning
systems shall comply with the requirements of this section.
13.10.1.1 Procedures that are required by
other parties and that exceed the requirements of this section or NFPA 72:
National Fire Alarm Signaling Code shall be
permitted.
13.10.1.2 The
requirements of Section 13.10 shall apply to both new and
existing systems.
13.10.2
Purpose.
13.10.2.1 The purpose
for initial and reacceptance inspections is to ensure compliance and to ensure
installation is in accordance with this
Code, and other
required installation standards.
13.10.2.2 The
purpose for periodic inspections is to assure that obvious damages or changes
that might affect the alarm system operability are visually
identified.
13.10.3
Deficiencies.
13.10.3.1
Responsibilities.
13.10.3.1.1
Tenants.
13.10.3.1.1.1 Tenants shall ensure that each
alarm installed in the tenant's rental unit remains functional and is not
disabled.
13.10.3.1.1.2 Tenants or
occupants shall not cause or disable any such alarm system or part
thereof.
13.10.3.1.1.3 If at any
point the tenant believes that the alarm is not functional or malfunctioning,
the tenant shall provide notice to the owner, landlord, superintendent or other
owner's designated representative.
13.10.3.2
Owner, Landlord,
Superintendent or Other Owner's Designee.
13.10.3.2.1 Every owner, superintendent,
landlord or designee shall, at a minimum, maintain, test, repair, or replace,
if necessary, every alarm upon renewal of any lease term for any dwelling unit
or on an annual basis, whichever is more frequent.
13.10.3.2.1.1 Such testing shall be
documented by the person performing such inspection on a form designated by
State Fire Marshal.
13.10.3.2.2 When repairs or alterations or
additions are made to an existing alarm and system the owner, landlord,
superintendent or other owner's designated representative shall be responsible
for inspection, documentation of the actual repair or alternation and the
testing of the alarm and system.
13.10.3.2.3 A written agreement shall be
required documenting delegation of responsibilities provided in this
section.
13.10.3.2.4 Where the
building or system owner, landlord, superintendent or other owner's designated
has delegated any responsibilities or an inspection, testing, repair or
alternation has been completed, a copy of the written delegation and the report
required by Sections 13.10.3.2.3 and
13.10.3.2.2 shall be provided to the AHJ upon
request.
13.10.3.2.5 Occupant
notification shall be required whenever an alarm system configured for
releasing service is being serviced or tested.
13.10.3.2.6 The owner, landlord,
superintendent or other owner's designated representative shall not cause or
disable any such alarm system or part thereof.
13.10.4
Inspection.
13.10.4.1 For the purpose of compliance with
M.G.L. c. 148, § 26F1/2 or to confirm compliance with M.G.L. c.148,
§ 26F, a visual inspection of smoke or carbon monoxide alarms and
detectors shall be performed in accordance with Table 13.10.4, or more often if
required by this Code or the AHJ.
13.10.4.2 The inspection maintenance for fire
alarm and fire detection systems shall be in accordance with NFPA 72.
Table 13.10.4 Visual Inspection
Component |
Initial Acceptance
|
Periodic Frequency |
Method |
Reference |
1. All equipment |
X |
Sale and Transfer |
Ensure there are no changes that affect equipment
performance. Inspect for building modifications, occupancy changes, changes in
environmental conditions, device location, physical obstructions, device
orientation, physical damage, and degree of cleanliness. |
10.24
13.7.1 |
2. Batteries and compartment |
X |
Sale and Transfer |
Inspect for corrosion or leakage. Verify tightness of
connections. |
10.24
13.7.1 |
3. Device |
X |
Sale and Transfer |
Inspection for expiration date of smoke
alarm |
10.24
13.7.1 |
4. Common Area |
X |
Annually Sale and Transfer |
Inspection for compliance |
10.24
13.7.1 |
13.10.5
Testing.
13.10.5.1
Initial Acceptance
Testing.
13.10.5.1. All new
alarms and systems required by this Code shall be inspected
and tested in accordance with the requirements of this section.
13.10.5.2
Periodic Testing.
13.10.5.2.1 The owner, landlord,
superintendent or other owner's designee shall, for any existing, new, or
modified alarm and system test every alarm and system in accordance with its
listing when requested by the AHJ.
13.10.6
Testing and Frequency.
13.10.6.1 Every owner, superintendent, or
landlord shall, at a minimum, maintain, test, repair, or replace, if necessary,
every alarm upon renewal of any lease term for any dwelling unit or on an
annual basis, whichever is more frequent. See Section
13.10.3.1 for responsibilities.
13.10.6.2 Unless otherwise permitted by other
sections of this Code, testing shall be performed in
accordance with the schedules in Table 13.10.4 or more often if required by the
AHJ.
13.10.6.3 Alarms shall be
replaced when they fail to respond to operability tests.
13.10.6.4 The testing, for fire alarm and
fire detection systems shall be in accordance with NFPA 72: National
Fire Alarm and Signaling Code.
13.10.7
Replacement of Single- and
Multiple-station Alarms.
13.10.7.1
Alarms shall not remain in service longer than ten years from the date of
manufacture, unless otherwise provided by the manufacturer's published
instructions.
13.10.7.2 Combination
smoke/carbon monoxide alarms shall be replaced when the end-of-life signal
activates or ten years from the date of manufacture, whichever comes first,
unless otherwise provided by the manufacturer's published
instructions.
13.10.7.3 Other than
provided in Section 13.7.5.1.1 where batteries are used as a
source of energy for smoke alarms or combination smoke/carbon monoxide alarms
or single- and multiplestation smoke alarms, the batteries shall be replaced in
accordance with the alarm equipment manufacturer's published
instructions.
13.10.7.4 The owner,
landlord, superintendent or other owner's designated representative shall be
responsible to repair, replace or for the modification of an alarm and
system.
13.10.8
Maintenance.
13.10.8.1 Maintenance of
an alarm and system shall be conducted according to the manufacturer's
published instructions and deficiencies shall be corrected as applicable in
Section 10.24.
13.10.8.2 The maintenance for fire alarm and
fire detection systems shall be in accordance with NFPA 72: National
Fire Alarm and Signaling Code.
13.10.9
Records.
13.10.9.1
Permanent Records.
13.10.9.1.1 The owner, landlord,
superintendent or other owner's designated representative shall be responsible
for maintaining records for the life of the alarm and system, for
examination.
13.10.10
Inspection, Testing, and
Maintenance Records.
13.10.10.1 Records
shall be retained until the next test and for one year thereafter.
13.10.10.2 Records shall be on a medium that
will survive the retention period. Paper or electronic media shall be
permitted.
Chapter
14
Means of Egress.
14.1 Replace with the following:
14.1
Application. Means of
egress in new and existing buildings shall comply with this Code
and the Building Code.
14.2 through
14.2(2) Replace
with the following:
14.2
Exit Access
Corridors. Corridors used as exit access shall be separated from other
parts of the building in accordance with the Building
Code.
14.3
Replace with the following:
14.3
Exits.
14.3.1 Where the
Building Code requires an exit to be separated from other
parts of the building, the separating construction shall meet the requirements
of the Building Code.
14.3.1 through 14.3.1(12)
Delete
14.4.3
Replace with the following:
14.4.3
Impediments to Egress. Any device or alarm installed to restrict
the improper use of a means of egress shall be designed and installed so that
it cannot, even in case of failure, impede or prevent emergency use of such
means of egress, unless otherwise provided in the Building
Code.
14.4.4
Add:
14.4.4
Exterior Egress. Any
fire escape or exterior stairway found to be in a state of deterioration or
determined to be unsafe by the Head of the Fire Department shall be repaired
immediately. Depending on the structural condition, a load test of any fire
escape shall be conducted before it is returned to service.
14.5.1.1 through
14.5.1.1*(7)
Replace with the following:
14.5.1.1 *
Swinging-type Door Assembly Requirement. Any door assembly in a
means of egress shall be of the side-hinged or pivoted-swinging type, and shall
be installed to be capable of swinging from any position to the full required
width of the opening in which it is installed.
14.5.1.1(1) through 14.5.1.1(7)
Delete
14.5.1.2 Replace
with the following:
14.5.1.2
Door Leaf
Swing Direction.
Door leaves required to be of the side-hinged or
pivoted-swinging type shall swing in the direction of egress travel as required
by the Building Code.
14.5.1.2(1) through 14.5.12(3)
Delete
14.5.1.3.1 Replace
with the following:
14.5.1.3.1 During its
swing, any door leaf in a means of egress shall leave not less than one half of
the required width of an aisle, a corridor, a passageway, or a landing
unobstructed and shall project not more than 7 in. (180 mm) into the required
width of an aisle, a corridor, a passageway, or a landing, when fully
open.
14.5.1.3.1(1) and
(2) Delete.
14.5.1.4 Replace with the following:
14.5.1.4
Screen Door Assemblies and
Storm Door Assemblies. Screen door assemblies and storm door assemblies
used in a means of egress shall be subject to the requirements for direction of
swing in accordance with the Building Code.
14.5.1.5.2(1) through (4)
Delete.
14.5.2.2
Delete.
14.5.2.4 Delete.
14.5.2.6.1 Replace with the following:
14.5.2.6.1 Where permitted by the
Building Code, key operation shall be permitted, provided that
the key cannot be removed when the door leaf is locked from the side from which
egress is to be made.
14.5.2.6.2(1) Replace with the following:
(1) This alternative is permitted by the
Building Code for the specific occupancy.
14.5.2.6.3 Delete.
14.5.2.7 Replace with the following:
14.5.2.7*
Stair Enclosure
Re-entry. Every door assembly in a stair enclosure shall meet the
requirements of the Building Code.
14.5.2.7(1) through (3)
Delete
14.5.2.7.1 through
14.5.2.7.2 Delete
14.5.2.7.3 Replace with the
following:
14.5.2.7.3 Signage on
the stair door leaves as provided in the
Building Code shall
be required as follows:
(1) Door assemblies
allowing re-entry shall be identified as such on the stair side of the door
leaf.
(2) Door assemblies not
allowing re-entry shall be provided with a sign on the stair side indicating
the location of the nearest door opening, in each direction of travel, that
allows re-entry or exit.
14.5.2.10 Replace with the following:
14.5.2.10 *On doors required to release all
latching and all locking devices of the door leaf with not more than one
releasing motion in accordance with 14.5.2.3.2, devices shall
not be installed in connection with any door assembly where such devices
prevent or are intended to prevent the free use of the leaf for purposes of
egress.
14.5.3.1.1
Replace with the following:
14.5.3.1.1
Approved, delayed-egress electrical locking systems shall be permitted to be
installed on door assemblies low- and ordinary-hazard in accordance with the
Building Code, protected throughout by an approved, supervised
automatic fire detection system in accordance with
Section
13.7 or an approved, supervised automatic sprinkler system in
accordance with
Section 13.3, provided that the following
criteria are met:
(1) The delay of the
delayed-egress electrical locking system shall deactivate allowing unobstructed
egress upon loss of power controlling the lock or locking mechanism.
(2)* An irreversible process shall release
the electrical lock in the direction of egress within 15 seconds, or 30 seconds
where approved by the AHJ, upon application of a force to the release device as
required by the Building Code.
(3)* A readily visible, durable sign that
conforms to the visual characters requirements of ICC A117.1, Accessible and
Usable Buildings and Facilities, shall be located on the door leaf adjacent to
the release device in the direction of egress, and shall read as follows:
(a) PUSH UNTIL ALARM SOUNDS, DOOR CAN BE
OPENED IN 15 SECONDS, for doors that swing in the direction of egress
travel
(b) PULL UNTIL ALARM SOUNDS,
DOOR CAN BE OPENED IN 15 SECONDS, for doors that swing against the direction of
egress travel
(4) The
egress side of doors equipped with delayed-egress electrical locking system
shall be provided with emergency lighting in accordance with the
Building Code
PUSH UNTIL ALARM SOUNDS
DOOR CAN BE OPENED IN 15 SECONDS
(5) Hardware for new installations shall be
listed in accordance with UL 294, Access Control System Units.
[101:7.2.1.6.1.1]
14.5.3.1.2 Delete.
14.5.3.2.1* Replace with the
following:
14.5.3.2.1 Where
permitted by the Building Code, door assemblies in the means
of egress shall be permitted to be equipped with an approved entrance and
egress access control system, provided that all of the following criteria are
met:
14.5.3.4 Delete.
14.5.3.5.4 Delete.
14.5.4.1* A door leaf normally required to be
kept closed shall not be secured in the open position at any time and shall be
self-closing or automatic-closing in accordance with 14.5.4.2,
unless otherwise permitted by the Building
Code.
14.5.4.2 In any
building doors shall be permitted to be automatic-closing, provided that all of
the following criteria are met:
14.5.4.3 Delete.
14.6.1.2 Replace with the
following:
14.6.1.2 Inside stairs,
other than those serving as an exit or exit component, shall be protected in
accordance with Section 8.6 of the Building
Code.
14.6.1.3 through
14.6.2.3 Delete.
14.7.1 Delete.
14.7.2 through 14.7.2(2) Delete.
14.7.4.1 Replace with the
following:
14.7.4.1 The width of an
exit passageway shall be sized to accommodate the aggregate required capacity
of all exits that discharge through it as required by the
Building
Code.
(1)* Where an exit passageway
serves occupants of the level of exit discharge as well as other stories, the
capacity shall not be required to be aggregated.
(2) As provided in Chapters 36 and 37 of
NFPA, an exit passageway in a mall structure shall be permitted to accommodate
occupant loads independently from the mall concourse and the tenant
spaces.
14.7.4.2
Delete.
14.8.1.2 Delete.
14.8.1.2
Table Delete
14.8.1.3.1 Delete
14.8.1.4 through 14.8.1.6
Delete
14.8.2.1 Replace with the
following:
14.8.2.1 The width of
means of egress shall be in accordance with the Building
Code.
14.8.2.2 through
14.8.2.3 Delete
14.8.3.1
Table Delete.
14.8.3.4.1 through
14.8.3.4.1(2) Replace with the following:
14.8.3.4.1 The width of any means of egress
shall be in accordance with the
Building Code.
14.8.3.4.1.1 Delete.
14.8.3.4.1.3 Delete.
14.9.1.1 Delete
14.9.1.2 Replace with the following:
14.9.1.2 The number of means of egress from
any story or portion thereof, shall be as follows;
(1) Occupant load more than 500 but not more
than 1000 - not less than 3
(2)
Occupant load more than 1000 - not less than 4
(3) Or as otherwise allowed by the
Building Code.
14.9.1.3 Replace with the
following:
14.9.1.3 Accessible
means of egress shall be in accordance 521 CMR: Architectural Access
Board and the Building Code.
14.9.1.4 through 14.9.1.6.3
Delete.
14.10.1.1.1* Replace with
the following:
14.10.1.1.1* Where exits are
not immediately accessible from an open floor area, continuous passageways,
aisles, or corridors leading directly to every exit such areas shall be
maintained.
14.10.1.1.2
Replace with the following:
14.10.1.1.2 Exit
access corridors shall provide access to not less than two approved exits,
unless otherwise provided by the Building
Code.
14.10.1.1.3 Delete.
14.10.1.2 Replace with the
following:
14.10.1.2 Corridors
shall provide exit access without passing through any intervening rooms other
than corridors, lobbies, and other spaces permitted to be open to the corridor,
unless otherwise provided in the
Building Code.
14.10.1.2.1 Replace with the following:
14.10.1.2.1 * Exit access shall be arranged
so that there are no dead ends in corridors, unless permitted by, and limited
to the lengths specified in the Building
Code.
14.10.1.2.2 Replace with the
following
14.10.1.2.2 Approved
existing corridors that require passage through a room to access an exit shall
be permitted to continue to be used, provided that all of the following
criteria are met:
(1) The path of travel is
marked in accordance with Section 14.14.
(2) Doors to such rooms shall comply with the
Building Code.
14.10.1.3 Replace with the
following
14.10.1.3 Remoteness
shall be provided in accordance with the Building Code.
14.10.1.3.1 through 14.10.1.4.2
Delete
14.10.1.5 Replace
with the following
14.10.1.5 Exit
access from rooms or spaces shall be permitted to be through adjoining or
intervening rooms or areas, provided that such rooms or areas are accessory to
the area served. Foyers, lobbies, and reception rooms constructed as required
for corridors shall not be construed as intervening rooms. Exit access shall be
arranged so that it is not necessary to pass through any area identified under
Protection from Hazards in the Building Code.
14.10.2 Replace with the following:
14.10.2
Impediments to Egress.
14.10.2.1 * Replace with the following:
14.10.2.1 * Access to an exit shall not be
through kitchens, storerooms other than as provided in the
Building
Code, restrooms, workrooms, closets, bedrooms, or similar spaces, or
other rooms or spaces subject to locking, unless passage through such rooms or
spaces is permitted by the
Building Code.
14.10.2.2.1 Replace with the
following:
14.10.2.2.1 Hangings or
draperies shall not be placed over exit doors or located so that they conceal
or obscure any exit.
14.10.2.2.2
through 14.10.4.9 Delete.
14.11.1 Replace with the following:
14.11.1 *
Exit Termination.
Exits shall terminate directly, at a public way.
14.11.1.1 through 14.11.1.5
Delete.
14.11.2 Replace
with the following:
14.11.2
Exit Discharge Through Interior Building Areas. Exits shall be
permitted to discharge through interior building areas, provided that all of
the following are met:
14.11.2 (1)
through 14.11.2(2) Delete.
14.11.2 (4) through (4)(b)iii. Delete.
14.11.3.1 through 14.11.3.3
Delete.
14.11.4 Replace
with the following:
14.11.4
Components of Exit Discharge. Doors, stairs, ramps, corridors,
exit passageways, bridges, balconies, escalators, moving walks, and other
components of an exit discharge shall comply with the Building
Code.
14.11.6 Delete.
14.12.1.1 Replace with the
following:
14.12.1.1 * Illumination
of means of egress shall be provided in accordance with the Building
Code. For the purposes of this requirement, exit access shall include
only designated stairs, aisles, corridors, ramps, escalators, and passageways
leading to an exit. For the purposes of this requirement, exit discharge shall
include only designated stairs, aisles, corridors, ramps, escalators, walkways,
and exit passageways leading to a public way.
[101:7.8.1.1]
14.14.8.1 through
14.14.8.2
Delete
14.14.8.3.1 Replace with the
following:
14.14.8.3.1 Any door,
passage, or stairway that is neither an exit nor a way of exit access and that
is located or arranged so that it is likely to be mistaken for an exit shall be
identified as required by the Building Code
14.15 Replace with the following:
14.15
Emergency Escape and
Rescue.
14.15.1 Replace with the
following:
14.15.1 Escape and
rescue openings shall comply with the Building Code.
14.15.2 Replace with the following:
14.15.2 Where approved on, the emergency
escape and rescue openings, security bars, grates, grilles, or similar devices
shall be equipped with approved release mechanisms that are releasable from the
inside without the use of a tool, a key, special knowledge, or force greater
than that which it takes for normal operation of the door or window.
Chapter 17
Wildland
Urban Interface.
Chapter 17 Delete in its entirety.
Chapter 18
Fire Department Access and
Water Supply.
18.1 Replace with the
following:
18.1
General
Scope. Fire department access and water supplies shall comply with this
chapter. The provisions of this chapter shall not apply to any city, or town
which has accepted the provisions of M.G.L. c. 41, § 81 et. seq. or
similar laws which provide local jurisdiction over fire department access and
water supply. In the absence of any such laws, fire department access and water
supply shall comply with this chapter.
18.1.1.3 Add:
18.1.1.3 This chapter shall apply to new one-
or two-family dwellings, not provided with adequate frontage and located behind
an existing building that has frontage. For purposes of this section, adequate
frontage shall mean at least 20 feet or more abutting a public way.
18.1.1.3.1 Existing and new one- and
two-family detached dwellings, not located behind a building with adequate
frontage, and their accessory structures such as garages, carports, and sheds
shall be exempt from the provisions of Section 18.2.3.
18.1.1.4 Add:
18.1.1.4 The fire apparatus access road plans
must include an analysis and evaluation of fire apparatus maneuvers throughout
the access roads created by swept path analysis and turn simulation
software.
18.1.1.5 Add:
18.1.1.5 The fire apparatus access plans
shall bear the seal and signature of the responsible registered professional
engineer.
18.1.1.6 Add:
18.1.1.6 Nothing in this Section shall reduce
the requirements established by cities or towns under M.G.L. c. 40A and
planning and zoning bylaws.
18.1.3.1 Replace with the
following:
18.1.3.1
Fire
Apparatus Access. Plans, where required, for fire apparatus access roads
shall be submitted to the fire department for review and approval prior to
construction.
18.2.2.1.1 Add:
18.2.2.1.1 Approval of access roads shall be
subject to the AHJ and capable of supporting the imposed loads of fire
apparatus and shall be provided with an all-weather driving surface and shall
be maintained as provided.
18.2.2.3 Replace
with the following:
18.2.2.3
Access Maintenance. The owner or occupant of a structure or area,
with required fire department access as specified in Section 18.2.2.1 or
18.2.2.2, shall notify the AHJ when the access is modified.
18.2.3.1.3*(1) through
18.2.3.1.3*(4) Delete.
18.2.3.1.3* Replace with the
following:
18.2.3.1.3* (6) Other
detached buildings having an area not exceeding 400
ft.2
18.2.3.1.4 Replace with the
following:
18.2.3.1.4 When fire
department access roads cannot be installed due to location on property,
topography, waterways, nonnegotiable grades, or other similar conditions, the
AHJ shall be permitted to accept alternatives proposed by the owner of the
building to allow additional fire protection features, up to and including the
installation of an approved fire sprinkler system installed in accordance with
the
Building Code, cistern(s), additional fire hydrant(s), or
similar devices or systems.
18.2.3.2 Replace
with the following:
18.2.3.2
Access to Buildings and Facilities.
18.2.3.2.1.1 Add:
18.2.3.2.1.1 Where a new building, not
provided with adequate frontage, is to be located behind an existing building
that has frontage, a fire department access road shall extend to within 25 feet
of at least one exterior door that can be opened from the outside and that
provides access to the interior of the building.
18.2.3.2.1.1.2 Where a townhouse as defined
in the Building Code, is protected with an approved automatic
sprinkler system that is installed in accordance with NFPA 13D or NFPA 13R, as
applicable, the distance in Section 18.2.3.2.1 shall be
permitted to be increased to 150 ft. (46 m).
18.2.3.2.2.1 When buildings are protected
throughout with an approved automatic sprinkler system that is installed in
accordance with NFPA 13: Standard for the Installation of Sprinkler
Systems the distance in Section 18.2.3.2.2 shall be
permitted to be increased to 250 feet.
18.2.3.2.2.2 Except new one- or two-family
dwellings, and townhouses, not provided with adequate frontage and located
behind an existing building that has frontage.
18.2.3.5.1.1 Replace with the
following:
18.2.3.5.1.1 Fire
department access roads shall have an unobstructed width of not less than 20
feet (6.1 m). Fire department access roads constructed in the boulevard-style
shall be allowed where each lane is less than 20 feet but not less than tem
feet when they do not provide access to a building or structure.
18.2.3.5.2.1 Add:
18.2.3.5.2.1 Permeable drivable surfaces,
that meet loading of Section 18.2.3.4.2, are allowed when
approved by the AHJ. When approved, the permeable surfaces shall be identified
by a method acceptable to the AHJ.
18.2.3.5.3.1 Replace with the
following:
18.2.3.5.3.1 The minimum
inside turning radius of a fire department access road shall be 25 feet. The
AHJ shall have the ability to increase the minimum inside turning radius to
accommodate the AHJ's apparatus.
18.2.3.5.6.1 Replace with the
following:
18.2.3.5.6.1 The
gradient for a fire department access road shall not exceed 10%, unless
approved in writing by the AHJ.
18.2.3.5.8 Add:
18.2.3.5.8
Travel in the Opposing
Lane. The use of the opposite travel lane is prohibited in the design of
all new fire apparatus access roads.
Delete:
18.2.4.2.3 through
18.5.4.4.
Chapter 19
Combustible Waste
and Refuse.
19.3 Add:
19.3
Special Hazards, Rubbish.
19.3.1
Spontaneous Combustion.
Substances subject to spontaneous heating or ignition, such as oily or greasy
rags, or other materials or combinations of materials, shall not be deposited
in combustible containers or so kept or stored as to ignite combustible
material.
19.3.1.1 Such substances shall not
be mixed with combustible rubbish or stored in the same containers.
19.3.1.2 Materials subject to spontaneous
ignition shall be kept in listed metal receptacles equipped with self-closing
hinged covers designed to guard against the hazard of spontaneous
combustion.
19.3.1.3 Contents shall
be emptied every night and disposed of properly.
19.3.1.4
Hot Waste. Hot coals,
cinders, hot scrap metal, and similar substances shall not be deposited in
combustible containers, or kept or stored so as to ignite combustible
material.
19.3.2.1 Such substances
shall not be mixed with combustible rubbish or stored in the same
containers.
19.3.2.2 Such
substances shall be kept, handled, or stored inside buildings only in
noncombustible receptacles approved by the Head of the Fire Department for that
purpose and location.
19.3.2.3 Such
substances shall be kept, handled, or stored outside of building locations so
that they cannot ignite buildings on the premises or adjacent premises and will
not endanger people.
19.3.3 Containers which require mechanical
assistance to be moved, shall be marked with the name and telephone number of
the company or person from which emergency service to expedite movement of the
container can be obtained.
19.3.4
Waste storage rooms shall not contain boilers or furnaces used for the central
heating of buildings, nor shall rooms with boilers or furnaces be used for
waste storage of any kind.
Chapter 20
Occupancy Fire
Safety.
20.1.1 Replace with the
following:
20.1.1
Application. New and existing assembly occupancies shall comply
with Section 20.1.
20.1.1.2 Delete.
20.1.3.1 Replace with the
following:
20.1.3.1
General. Interior finish shall be in accordance with the
Building Code.
20.1.3.2 through 20.1.3.3
Delete.
20.1.3.5 through
20.1.3.5.4 Delete
20.1.4.1.1*
Replace with the following:
20.1.4.1.1* Special amusement buildings,
regardless of occupant load, shall meet the requirements for assembly
occupancies, in addition to the requirements of Section 20.1.4
and the Building Code.
20.1.4.2* through
20.1.4.6
Delete.
20.1.4.7.2 Delete.
20.1.4.2.1.1 Replace with the
following:
20.1.4.2.1.1 Exit
marking shall be in accordance with the Building
Code.
20.1.4.2.1.2
Delete
20.1.4.2.2 and
20.1.4.2.2.1 Delete
20.1.4.3 Replace with the
following:
20.1.4.3
Interior
Finish. Interior finish shall be in accordance with the Building
Code.
20.1.4.4.2.2 and
20.1.4.4.3 Delete.
20.1.4.5.2 through 20.1.4.5.2
Delete
20.1.5.1.2 Delete
20.1.5.1.3 Replace with the
following:
20.1.5.1.3
Inspection of Door Openings. Door openings shall be inspected by
the owner or their representative and be in an operable condition at all
times.
20.1.5.4.5 Add:
20.1.5.4.5 Upholstered furniture shall be
tested in accordance with the provisions of Section
12.6.3.
20.1.5.5.2 through
20.1.5.5.3 Delete.
20.1.5.5.4.1
through 20.1.5.5.4.3 Delete.
20.1.5.5.4.2 Delete.
20.1.5.5.4.3 Delete.
20.1.5.5.4.4 Replace with the
following:
20.1.5.5.4.4 Exhibit
booth construction materials shall be limited to the following:
(1) Flame-retardant materials complying with
one of the following:
(a) They shall meet the
flame propagation performance criteria contained in Test Method 1 or Test
Method 2, as appropriate, of NFPA 701.
(b) They shall exhibit a heat release rate
not exceeding 100 kW when tested in accordance with NFPA 289 using the 20 kW
ignition source.
20.1.5.5.4.7 through 20.1.5.5.4.4.7.3
Delete.
20.1.5.6.1 A nightclub, dance hall,
discotheque or bar with an occupant load of 100 or more, shall be provided with
a minimum of one trained crowd manager. Where the occupant load exceeds 250,
additional trained crowd managers or crowd manager supervisors shall be
provided at a ratio of 1 crowd manager or crowd manager supervisor for every
250 occupants.
20.1.5.6.1.1 Add:
20.1.5.6.1.1 A nightclub, dance hall,
discotheque or bar shall be defined as:
(1)
Any facility classified as a A-2 or A-3 use group under the Building
Code, which is principally designed or used as a nightclub, dance
hall, discotheque, or bar; or
(2)
Any facility that features entertainment by live band or recorded music
generating above normal sound levels and has a specific area designated for
dancing.
20.1.5.6.1.2 A
crowd manager is not required for:
(1) A
temporary structure erected at the same location for no more than ten days in
any calendar year; or
(2) A
facility that features fixed seating, such as a theatre, auditorium, concert
hall or similar place of assembly; or
(3) A facility used for organized private
function where:
(a) Each guest has a seat and
table for dining purposes; and
(b)
Attendance for each event is limited by pre-arrangement between the facility
operator and the private event organizers; and
(c) The legal capacity of the facility
provides not less than 15 square feet (net) per occupant.
20.1.5.6.2 Replace with
the following:
20.1.5.6.2 The crowd
manager and crowd manager supervisor shall receive training as required by the
State Fire Marshal. The State Fire Marshal shall develop a reasonable method to
confirm, on a three-year basis, that a crowd manager has completed the training
in regards to their responsibility.
20.1.5.6.2.1 Add:
20.1.5.6.2.1
Certificates.
Certificates where required, shall comply with Section
1.13.
20.1.5.6.3
Replace with the following:
20.1.5.6.3 A crowd manager shall be 21 years
of age or older, shall be the owner or operator of the business or under the
direct control and supervision of said owner or operator and shall be
responsible for all of the following:
(1)
Maintaining clear paths of egress, assuring that the facility does not exceed
its occupant load limit, initiating a fire alarm if necessary, directing
occupants to exits;
(2) Assuring
general fire and life safety awareness of employees and occupants, including
assuring that exit announcements are made in accordance with Section
20.1.5.8.3; and
(3)
Accurately completing the safety plan checklist required by Section
20.1.5.6.4.
20.1.5.6.4 Replace with the
following:
20.1.5.6.4
Fire
and Building Safety Checklist.
(1) The
crowd manager shall be responsible for the completion of the Fire and Building
Safety Checklist, as prescribed by the State Fire Marshal, on each day of
operation prior to opening the facility to patrons.
(2) This checklist shall include, but not be
limited to, the routine safety check of existing fire protection systems, fire
extinguishers, signage, interior finish, exits, unobstructed egress, crowd
control procedures and building occupancy limits.
(3) The original completed checklists shall
be kept on the premises for at least one year and shall be subject to
inspection by the AHJ.
20.1.5.6.4.1
Add:
20.1.5.6.4.1
Certificates. Certificates where required, shall comply with
Section 1.13.
20.1.5.7 Delete.
20.1.5.8.2 Delete.
20.1.5.8.3*(4) Delete
20.1.5.8.3*(5) Add:
(5) Nightclubs, dance halls, discotheques or
bars.
20.1.5.10
through 20.1.5.10.2.3 Delete.
20.1.5.11 through 20.1.5.12.2
Delete
20.1.5.13 Replace:
20.1.5.13
Integrated Fire Protection
and Life Safety Systems. Integrated fire protection and life safety
systems shall be tested in accordance with the Building
Code.
20.2.2 through
20.2.2.5 Delete
20.2.1
Replace with the following:
20.2.1
Application. New and existing educational occupancies shall comply
with Section 20.2.
20.2.2 through
20.2.2.5 Delete.
20.2.3.2 through 20.2.3.3.4
Delete.
20.2.4.2.1*
Replace with the following:
20.2.4.2.1 Emergency egress drills shall be
conducted in accordance with the applicable provisions of
Section
20.2.4.2.20.2.4.2.1.1 Add:
20.2.4.2.1.1 The responsible school official
in charge of the school or the school system, shall formulate a plan for the
protection and evacuation of all persons in the event of fire, and shall
include alternate means of egress for all persons involved. Such plan shall be
presented to and approved by the Head of the Fire Department.
20.2.4.2.1.2 Add:
20.2.4.2.1.2 The responsible school official
in charge of the school or the school system shall see that each class
instructor or supervisor shall receive proper instructions on the fire drill
procedures specified for the room or area in which that person carries out
their duties before they assume such duties.
20.2.4.2.1.3 Add:
20.2.4.2.1.3 Every student in all schools
shall be advised of the fire drill procedure or shall take part in a fire drill
within three days after entering such school.
20.2.4.2.1.4 Add:
20.2.4.2.1.4 The Head of the Fire Department,
or person designated by him or her, shall visit each school at least four times
each year for the purpose of conducting fire drills and questioning the
teachers and supervisors. These drills shall be conducted without advance
warning to the school personnel other than the person in charge of the school
at the time.
20.2.4.2.1.5
Add:
20.2.4.2.1.5
Records. A record of all fire exit drills shall be kept on the
premises and persons in charge of such occupancies shall file written reports
at least twice a year with the Head of the Fire Department giving the following
information:
(1) Time of drill;
(2) Date of drill;
(3) Weather conditions when occupants were
evacuated;
(4) Number of occupants
evacuated;
(5) Total time for
evacuation; and
(6) Other
information relevant to the drill.
20.2.4.2.1.6 Add:
20.2.4.2.1.6
Evacuation. Fire
exit drills shall include the complete evacuation of all persons from the
building.
20.2.4.2.1.7
Add:
20.2.4.2.1.7 A drill of the
multi-hazard evacuation plan, required by the provisions of St. 2000, c. 159,
§ 363, shall be permitted to be substituted for one of the fire drills
required by 20.2.4.2.
20.2.4.2.2 through 20.2.4.2.3
Delete.
20.2.4.3.2 through
20.2.4.3.3 Delete.
20.2.4.4.2 Replace with the
following:
20.2.4.4.2 Upholstered
and molded plastic seating furniture shall be tested in accordance with the
provisions of 12.6
20.2.4.4.3 Replace with the
following:
20.2.4.4.3 Paper
materials displayed in educational use occupancies shall be permitted on walls
only in accordance with the following:
(1) In
classrooms, paper materials displayed shall not exceed 20% of the total wall
area.
(2) Paper materials displayed
shall be attached directly to the walls and shall not be permitted to cover an
egress door or be placed within five feet of an egress door, unless approved by
the AHJ. When determining wall areas, the door and window openings shall be
included unless:
(a) Paper materials are
displayed in fully enclosed viewing cabinets with glass or polycarbonate
viewing panels or covered with glass or polycarbonate sheet material in
accordance with the Building Code;
(b) Flame retardant paper material is used
for display.
(3) Paper
material displays shall be permitted to cover up to 50% of the total wall area
in classrooms that are fully sprinklered in accordance with Chapter
13.
20.2.4.4.4
Add:
20.2.4.4.4
Exit Access
Passageways, Assembly Areas, and Corridors. Paper materials shall be
permitted on walls only in accordance with the following:
(1) Paper materials displayed shall not
exceed 10% of the surface area of any wall;
(2) Such paper material shall be positioned
in such manner to avoid concentration of materials to reduce flame spread in
the event of a fire;
(3) In no
event shall any one grouping exceed a maximum horizontal measurement of 12 feet
and a maximum vertical measurement of six feet. Groups of paper material shall
be allowed as long as there is space between each group equal to the horizontal
width of the largest adjacent group;
(4) Paper material used for display shall be
attached directly to the walls and shall not be permitted to cover an egress
door or be placed within five feet of an egress door, unless approved by the
AHJ or unless:
(a) Paper materials are
displayed in fully enclosed viewing cabinets with glass or polycarbonate
viewing panels or covered with glass or polycarbonate sheet material in
accordance with the Building Code.
(b) Flame retardant paper material is used
for display.
(5) Paper
material displays may cover up to 50% of the total wall area in classrooms that
are fully sprinklered in accordance with Chapter 13.
20.2.4.4.5 Add:
20.2.4.4.5
Exits and Enclosed Exit
Stairs. Displayed paper materials shall not be permitted in exits and
enclosed exit stairs.
20.2.4.4.6
Add:
20.2.4.4.6 This Section shall
not prohibit the posting of exit signage or evacuation plans in accordance with
this Code.
20.2.4.4.7 Add:
20.2.4.4.7 The provisions of Section
20.2.4.4.3 or 20.2.4.4.4 shall not be applicable to
any election materials required by law to be posted during any local, state or
federal election.
20.2.4.5 Replace
with the following:
20.2.4.5
Unvented Fuel-fired Heaters. Unvented fuel-fired heaters, other
than gas space heaters in compliance with 248 CMR shall not be used in
accordance with the following:
(1)
Prohibited Installations. Unvented room heaters shall not be
installed in bathrooms or bedrooms.
(2)
Listing and Installation.
Unvented room heaters shall be listed in accordance with ANSI Z21.11.2,
Gas-fired Room Heaters - Volume II, Unvented Room Heaters, and
shall be installed in accordance with the manufacturer's installation
instructions.
20.2.4.5.1
Add:
20.2.4.5.1
Permit. Permits, where required, shall comply with Section
1.12.
20.3.1
Replace with the following:
20.3.1
Application. New and existing day-care occupancies shall comply
with
Section 20.2.20.3.1.1
through
20.3.1.4 Delete.
20.3.1.5.1 through 20.3.1.5.3
Delete.
20.3.2
Delete.
20.3.2.1 Replace with the
following:
20.3.2.1
Unvented
Fuel-fired Heaters. Unvented fuel-fired heaters, other than gas space
heaters in compliance with 248 CMR, shall not be used in accordance with the
following:
(1)
Prohibited
Installations. Unvented room heaters shall not be installed in bathrooms
or bedrooms.
(2)
Listing and
Installation. Unvented room heaters shall be listed in accordance with
ANSI Z21.11.2, Gas-fired Room Heaters - Volume II, Unvented Room
Heaters, and shall be installed in accordance with the manufacturer's
installation instructions.
20.3.2.1.1 Add:
20.3.2.1.1
Permit. Permits,
where required, shall comply with Section 1.12.
20.3.2.4 through 20.3.2.4.6
Delete.
20.3.3.1 Replace
with the following:
20.3.3.1
General. Interior finish shall be in accordance with the
Building Code.
20.3.3.2 through 20.3.4.2.3.6
Delete.
20.4.1 Replace
with the following:
20.4.1
Application. New and existing health care occupancies shall comply
with Section 20.4.
20.4.2.5.7.1* Replace with the
following:
20.4.2.5.7.1* Soiled
linen or trash collection receptacles shall not exceed 32 gal (121 L) in
capacity and shall meet the following requirements:
(1) The average density of container capacity
in a room or space shall not exceed 0.5 gal/ft2
(20.4 L/m2).
(2) A capacity of 32 gal (121 L) shall not be
exceeded within any 64 ft2 (6
m2) area.
(3) Mobile soiled linen or trash collection
receptacles with capacities greater than 32 gal (121 L) shall be located in a
room protected as a hazardous area when not attended.
(4) Container size and density shall not be
limited in hazardous areas.
20.4.2.5.7.2* Replace with the
following:
20.4.2.5.7.2* Containers
greater than 64 gal (242 L) used solely for recycling clean waste or for
patient records awaiting destruction shall be permitted to be excluded from the
limitations of 20.4.2.5.7.1 where all the following conditions are met:
(1) Each container is limited to a capacity
of 96 gal (363 L) except as permitted by 20.4.2.5.8 (2), (3)
or (4).
(2)
Containers for combustibles shall be labeled and listed as meeting the
requirements of FM Approval 6921, Approval Standard for Containers for
Combustible Waste; however, such testing, listing, and labeling shall
not be limited to FM Approvals.
(3)
Containers with capacities greater than 96 gal (363 L) shall be located in a
room protected as a hazardous area when not attended.
(4) Container size shall not be limited in
hazardous areas.
20.4.2.6* Replace with the
following:
20.4.2.6*
Portable
Space-Heating Devices. Portable space-heating devices shall be
prohibited in all health care occupancies, unless both of the following
criteria are met:
(1) Such devices are
permitted to be used only in nonsleeping staff and employee areas.
(2) Such devices are listed and labeled for
use as a freestanding, movable heater in accordance with UL 1278, Movable and
Wall- or Ceiling-Hung Electric Room Heaters
(3) The heating elements of such devices do
not exceed 212°F (100°C)
20.4.3.1 Replace with the
following:
20.4.3.1
General. Interior finish shall be in accordance with the
Building Code.
20.4.3.2 through 20.4.3.5.3
Delete.
20.5.1 Replace with the
following:
20.5.1
Application. New and existing residential board and care
occupancies shall comply with Section 20.5.
20.5.2.3.6 Replace with the
following:
20.5.2.3.6 Residents who
cannot meaningfully assist in their own evacuation or who have special health
problems shall not be required to actively participate in the drill
Subsection 20.4.2 shall apply in such instances.
20.5.2.5.1 Replace with the
following:
20.5.2.5.1 New
draperies, curtains, and other similar loosely hanging furnishings and
decorations in board and care facilities shall comply with
20.5.2.5.1.1 and 20.5.2.5.1.2.
20.5.3 through 20.5.3.3.2
Delete.
20.6.1 Replace with the
following:
20.6.1
Application. New and existing ambulatory health care centers shall
comply with Section 20.6.
20.6.2.5.5.1 Replace with the
following:
20.6.2.5.5.1 Soiled
linen or trash collection receptacles shall not exceed 32 gal (121 L) in
capacity, and the following also shall apply:
(1) The average density of container capacity
in a room or space shall not exceed 0.5 gal/ft2
(20.4 L/m2).
(2) A capacity of 32 gal (121 L) shall not be
exceeded within any 64 ft2 (6
m2) area.
(3) Mobile soiled linen or trash collection
receptacles with capacities greater than 32 gal (121 L) shall be located in a
room protected as a hazardous area when not attended.
(4) Container size and density shall not be
limited in hazardous areas.
20.6.2.5.5.2* Replace with the
following:
20.6.2.5.5.2* Containers
greater than 64 gal (242 L) used solely for recycling clean waste or for
patient records awaiting destruction shall be permitted to be excluded from the
requirements of 20.6.2.5.5.1 where all the following conditions are met:
(1) Each container shall be limited to a
maximum capacity of 96 gal (363 L), except as permitted by 20.6.2.5.5.2
(3) or (4)
(2) Containers for combustibles shall be
labeled and listed as meeting the requirements of FM Approval 6921, Approval
Standard for Containers for Combustible Waste; however, such testing, listing,
and labeling shall not be limited to FM Approvals.
(3) Containers with capacities greater than
96 gal (363 L) shall be located in a room protected as a hazardous area when
not attended.
(4) Container size
shall not be limited in hazardous areas
20.6.2.6 Replace with the
following:
20.6.2.6
Portable
Space-Heating Devices. Portable space-heating devices shall be
prohibited in all ambulatory health care occupancies, unless both of the
following criteria are met:
(1) Such devices
are used only in nonsleeping staff and employee areas.
(2) Such devices are listed and labeled for
use as a freestanding, movable heater in accordance with UL 1278, Movable and
Wall- or Ceiling-Hung Electric Room Heaters.
(3) The heating elements of such devices do
not exceed 212°F (100°C)
20.6.3 through 20.6.3.4
Delete
20.7.1 Replace with the
following:
20.7.1
Application. New and existing detention and correctional
occupancies shall comply with Section 20.7
20.7.2.1.1 Replace with the
following:
20.7.2.1.1 Detention and
correctional facilities, or those portions of facilities having such occupancy,
shall be provided with 24-hour staffing.
20.7.2.1.1.1 Add:
20.7.2.1.1.1
For Use Condition III, Use
Condition IV, and Use Condition V. The arrangement shall be such that
the staff involved starts the release of locks necessary for emergency
evacuation or rescue and initiates other necessary emergency actions within two
minutes of alarm.
20.7.2
through 20.7.2.1.2 Delete.
20.7.2.4.7 through 20.7.2.5
Delete.
20.7.3.1 Replace with the
following:
20.7.3.1
General. Interior finish shall be in accordance with the
Building Code.
20.7.3.2 through 20.7.3.6.2.3
Delete.
20.8.1 Replace with the
following:
20.8.1
Application. New and existing hotels and dormitories shall comply
with
Section 20.820.8.2.6
Replace with the following:
20.8.2.6
Unvented Fuel-fired
Heaters. Unvented fuel-fired heaters, other than gas space heaters in
compliance with NFPA 58/ANSI Z223.2,
Liquefied Petroleum Gas
Code shall not be used in accordance with the following:
(1) Prohibited Installations. Unvented room
heaters shall not be installed in bathrooms or bedrooms.
(2) Listing and Installation. Unvented room
heaters shall be listed in accordance with ANSI Z21.11.2, Gas-Fired Room
Heaters-Volume II, Unvented Room Heaters, and shall be installed in accordance
with the manufacturer's installation instructions.
20.8.2.6.1 Add:
20.8.2.6.1
Permit. Permits,
where required, shall comply with Section 1.12.
20.8.3. through
20.8.3.5 Delete.
20.9.2.1 Replace with the
following:
20.9.2.1
Emergency
Instructions for Residential Housing for the Elderly. Emergency
instructions shall be provided annually by the housing complex administrator to
each dwelling unit when containing 6 or more to indicate the location of
alarms, egress paths, and actions to be taken, both in response to a fire in
the dwelling unit and in response to the sounding of the alarm system.
20.9.2.1.1 Add:
20.9.2.1.1 The AHJ shall visit four times a
year to:
(1) To conduct a fire drill;
or
(2) Ascertain the evacuation
process and procedure.
20.9.3.1 Replace with the
following:
20.9.3.1
General. Interior finish shall be in accordance with the
Building Code.
20.9.3.2 through 20.9.3.5
Delete.
20.10.1 Replace with the
following:
20.10.1
Application. New and existing lodging or rooming houses shall
comply with Section 20.10.
20.10.2 Replace with the following:
20.10.2
Unvented Fuel-fired
Heaters. Unvented fuel-fired heaters, other than gas space heaters in
compliance with 248 CMR, shall not be used in accordance with the following:
(1)
Prohibited Installations.
Unvented room heaters shall not be installed in bathrooms or
bedrooms.
(2)
Listing and
Installation. Unvented room heaters shall be listed in accordance with
ANSI Z21.11.2, Gas-fired Room Heaters - Volume II, Unvented Room
Heaters, and shall be installed in accordance with the manufacturer's
installation instructions.
20.10.2.1 Add:
20.10.2.1
Permit. Permits, where
required, shall comply with Section 1.12.
20.10.3.1 Replace with the
following:
20.10.3.1
General. Interior finish shall be in accordance with the
Building Code
20.10.3.2 through 20.10.3.3.2
Delete
20.11.1 Replace
with the following:
20.11.1
Application. New and existing one- and two-family dwellings shall
comply with Section 20.
20.11.2 Replace with the following:
20.11.2
Unvented Fuel-Fired
Heaters. Unvented fuel-fired heaters, other than gas space heaters in
compliance with 248 CMR, shall not be used. [101:14.5.2.2; 101: 15.5.2.2],
shall not be used in accordance with the following:
(1) Prohibited Installations. Unvented room
heaters shall not be installed in bathrooms or bedrooms.
(2) Listing and Installation. Unvented room
heaters shall be listed in accordance with ANSI Z21.11.2, Gas-Fired Room
Heaters-Volume II, Unvented Room Heaters, and shall be installed in accordance
with the manufacturer's installation instructions.
20.10.2.1 Replace with the
following:
20.10.2.1
Permit. Permits, where required, shall comply with Section
1.12.
20.11.3
through
20.11.4.2 Delete
20.11.4.5 through 20.11.5
Delete
20.12.1 Replace
with the following:
20.12.1
Application. New and existing mercantile occupancies shall comply
with
Section 20.1220.12.2.3
Delete
20.12.3.1 Replace with the
following:
20.12.3.1
General. Interior finish shall be in accordance with the
Building Code.
20.12.3.2 through 20.3.3.4
Delete
20.13.1 Replace
with the following:
20.13.1
Application. New and existing business occupancies shall comply
with
Section 20.13.20.13.2.3
Delete.
20.13.3.1 Replace with the
following:
20.13.3.1
General. Interior finish shall be in accordance with the
Building Code.
20.13.3.2 through 20.14.4.3.2
Delete.
20.15.1
Application. New and existing storage occupancies shall comply
with the appropriate codes or standards referenced in Chapter 2 and
Section 20.15.
20.15.4 Add:
20.15.4
Storage, Arrangement,
Protection and Quantities of Hazardous Commodities. The storage,
arrangement, protection, and quantities of hazardous commodities shall be in
accordance with the applicable provisions of the following:
(1) NFPA 13, Standard for the Installation of
Sprinkler Systems
(2) NFPA 30,
Flammable and Combustible Liquids Code
(3) NFPA 30B, Code for the Manufacture and
Storage of Aerosol Products
(4)
NFPA 400, Hazardous Materials Code, Chapter 14, for organic peroxide
formulations
(5) NFPA 400,
Hazardous Materials Code, Chapter 15, for oxidizer solids and liquids
(6) NFPA 400, Hazardous Materials Code,
various chapters, depending on characteristics of a particular pesticide
[101:36.4.5.3]
(7) NFPA 1124. Code
for the Manufacture, Transportation, Storage, and Retail Sales of Fireworks and
Pyrotechnic Articles, as modified by the Building
Code.
20.15.4.1 through
20.15.4.3.2 Delete
20.15.6 through 20.15.6.2
Delete.
20.16 through
20.17.3 Delete.
20.18
Add:
20.18
Special Provisions
for Certain Places of Worship Which Have Been Issued a Valid Certificate of
Occupancy for Use as a Temporary Overnight Shelter Pursuant to the
Building Code.
20.18.1 Add:
20.18.1 A place of worship which has been
issued a valid certificate of occupancy for use as a temporary overnight
shelter in accordance with the provisions of the
Building Code
shall not be deemed in violation of the provision of this
Code
as a result of such temporary use, as long as the facility meets the following
conditions:
(1) The temporary overnight
shelter is in possession of a valid certificate of occupancy for such temporary
use which has been reviewed and approved by the Head of the Fire Department in
accordance with the Building Code.
(2) The approved temporary overnight shelter
is used, occupied, and operated in accordance with the terms and conditions
specified in said certificate of occupancy and said certificate of occupancy is
posted in a conspicuous location.
(3) In addition to the terms and conditions
specified in the certificate of occupancy, the following fire safety
requirements shall be applicable:
(a) The
building which houses the approved temporary overnight shelter shall have no
known existing or outstanding violations of this Code or
M.G.L. c. 148;
(b) A copy of the
fire safety and evacuation plan, approved in accordance with the provisions of
the Building Code shall be kept on the premises and posted
near the main entrance;
(c) The
responsible person(s) identified in the application for the Temporary
Certificate of Occupancy shall maintain the condition of the shelter in
accordance with the layout contained in the approved fire safety and evacuation
plan;
(d) The employees,
volunteers, or attendants of the temporary overnight shelter shall be trained
and drilled in the duties that they are to perform in case of fire, panic, or
other emergency in accordance with the provisions of Section
20.2.4.2.1.1;
(e) No
person shall be permitted to smoke within the temporary overnight
shelter;
(f) Smoking may be allowed
outside in an area approved by the Head of the Fire Department;
(g) A document shall be posted, in a location
approved by the Head of the Fire Department, containing an accurate number of
sheltered occupants on a nightly basis;
(h) Such document shall also contain the
names of all workers and volunteers who are overseeing or assisting in the
temporary overnight shelter usage on a nightly basis. In the event of an
evacuation, a copy of the document shall be in the possession of the person in
charge at a designated meeting point;
(i) The temporary overnight shelter shall
maintain a working landline phone that must be accessible to initiate a call
for assistance in the event of an emergency. A cell phone is not acceptable for
compliance with this requirement;
(j) The use of battery operated smoke alarms
and carbon monoxide detectors, as outlined in Chapter 13. All temporary
overnight shelters shall be equipped with monitored and interconnected smoke
and carbon monoxide detection system as described in the Building
Code;
(k) Carbon monoxide
alarms shall be installed in accordance with Chapter 13. For purpose of
compliance with Chapter 13, the dwelling unit of an approved temporary shelter
shall be considered that portion of the building used for sleeping
purposes;
(l) An approved temporary
overnight shelter shall feature working and approved smoke detectors in
accordance with the requirements of the
Building Code, if
applicable. If smoke detectors are not currently required under the
Building Code, the shelter shall, at a minimum, feature
approved working smoke detectors in accordance with the provisions of Chapter
13.
(1)
Approved Smoke
Detectors. Such approved smoke detectors shall be installed in any
room or area used for sleeping purposes and in any room or area directly
adjacent to said sleeping area;
(m) The Head of the Fire Department shall be
notified, in writing, at least 48 hours prior to the actual activation of an
approved temporary overnight shelter and shall be notified, in writing, upon
the termination of such activation.
Chapter 21
Airports and
Heliports.
Chapter 21 Delete in its
entirety.
Chapter 22
Automobile Wrecking Yards.
22.8
Replace with the following:
22.8
Burning Operations. Burning operations shall not be
allowed.
Sections 22.9.3 - 22.9.5.2
Delete.
Chapter 23
Cleanrooms.
23.2.1
Add:
23.2.1
Maximum
Quantities of Hazardous Chemicals. The maximum quantities of hazardous
chemicals for a single fabrication area or at a workstation are limited by the
Building Code. A permit shall not be issued until such time
that the Building Official has confirmed the facility is classified and
constructed as the appropriate H-use group or is exempt.
Chapter 24
- Drycleaning
No amendments
Chapter 25
Grandstands and Bleachers,
Folding and Telescopic Seating, Tents, and Membrane Structures.
Chapter 25 Delete in its
entirety.
Chapter 26
Laboratories Using Chemicals.
26.1.5 Add:
26.1.5(2) The special fire protection
required when handling radioactive materials
(See NFPA 801).
26.1.1.1 Add:
26.1.1.1 Amendments to NFPA 45 include:
1. The term "laboratory unit" shall also mean
"laboratory suite" in coordination with 780 CMR.
2. Delete Section 10.1.6.9
26.1.6.1.1 Add:
26.1.6.1.1 Documentation In addition to all
other documents required by 780 CMR and 527 CMR, the building management
company, or a designated representative, must submit the following documents
with the permit documents. These shall be reviewed with the Building and Fire
Official and updated accordingly to receive a Certificate of Occupancy.
1. Emergency Action Plan
2. Hazardous Materials Management
Plan
3. Hazardous Materials
Inventory Statement
It is it responsibility of the building management company, or
designated representative, to keep these documents current.
26.1.6.1.1 Add:
26.1.6.1.1. Documentation shall be maintained
in accordance with
527 CMR
1.00 and reviewed annually, or at the discretion of
the Fire Official.
26.1.6.1.2
Add:
26.1.6.1.2
Information
required. A report shall be submitted to the AHJ identifying the maximum
expected quantities of hazardous materials to be stored, used in a closed
system and used in an open system, and subdivided to separately address
hazardous material classification categories. The methods of protection from
such hazards, including but not limited to control areas, laboratory suites,
fire protection systems and Group H occupancies shall be indicated in the
report and on the construction documents. The opinion and report shall be
prepared by a qualified person, firm or corporation approved by the AHJ and
provided without charge to the enforcing agency. For buildings and structures
with control areas, laboratory suites, or Group H occupancies, separate floor
plans shall be submitted identifying the locations of anticipated contents and
processes so as to reflect the nature of each occupied portion of every
building and structure.
26.3 Add:
26.3
Penetrations. Penetrations
through fire-rated floor/ceiling, floor, and wall assemblies shall be protected
in accordance with the Building Code.
Chapter 27
Manufactured Home and
Recreational Vehicle Sites.
Chapter 27 Delete in its
entirety.
Chapter 28
Marinas, Boatyards, Marine Terminals, Piers, and Wharves.
28.1.1.1 Replace with the
following:
28.1.1.1
Section
28.1 also applies to support facilities and structures used for
construction, repair, storage, hauling and launching, or fueling of vessels,
and independent storage and or service areas.
28.1.1.3 Replace with the
following:
28.1.1.3
Section
28.1 shall not apply to a private, noncommercial docking facility
constructed or occupied for the use of the owners or residents of the
associated single-family dwelling.
28.1.2.1.2
Replace with the following:
28.1.2.1.2 Visibility and Identification. All
portable fire extinguishers shall be clearly visible and installed in
compliance with NFPA 10.
28.1.2.2.1.2
Delete
28.1.2.2.1.3 Replace with
the following:
28.1.2.2.1.3
Existing facilities shall not be required to be protected by an automatic
fire-extinguishing system, unless required by the building code or other code
or standard.
28.1.2.2.2.2 Replace
with the following:
28.1.2.2.2.2
Existing facilities shall not be required to be protected by an automatic
fire-extinguishing system unless required by the Building Code
or other appliable code or standard.
28.1.2.2.3.1 Replace with the
following:
28.1.2.2.3.1 Combustible
piers and substructures in excess of 25 ft (7.62 m) in width or in excess of
5000 ft2 (465 m2) in
area, or within 30 ft (9.14 m) of other structures required to be so protected,
shall be protected in accordance with Section 4.3 of NFPA 307 unless otherwise
permitted by 28.1.2.2.3.2, 28.1.2.2.3.3, or
28.1.2.2.3.4.
28.1.2.2.3.4 Replace with the
following:
28.1.2.2.3.4* Existing
facilities shall not be required to be protected by an automatic
fire-extinguishing system unless required by the building code or other
applicable code or standard.
28.1.2.4.1 Replace with the
following:
28.1.2.4.1 Fire
protection shall be provided as described in 28.1.2.4.1.2
28.1.2.4.1.1 Delete
28.1.2.4.2 Delete
28.1.3.1.3 Replace with the
following:
28.1.3.1.3 Electrical
lighting shall be provided and meet the requirements of NFPA 70 to ensure
adequate illumination of all exterior areas, piers, and floats.
28.1.3.2.1.2 Delete
28.1.3.2.1.3 Replace with the
following:
28.1.3.2.1.3 The use of
blow torches or other hot works devices shall comply with Chapter 41.
28.1.3.2.1.4 Replace with the
following:
28.1.3.2.1.4 The use of
flammable solvents for cleaning purposes, paint removal, or other similar
activities shall only be allowed in well-ventilated areas in accordance with
the manufacturer's instructions.
28.1.3.2.1.6 Replace with the
following:
28.1.3.2.1.6 No
unattended electrical equipment shall be in use aboard boats unless being used
in accordance with manufacturer's operational guidelines.
28.1.3.2.1.8.1 Add:
28.1.3.2.1.8.1 Exceptions:
(1) Yards with a preapproved plan accepted by
the AHJ.
28.1.3.2.1.8.2
Replace with the following:
28.1.3.2.1.8.2 Access to buildings in which
boats are stored shall comply with Chapter 18 of this Code.
28.1.3.2.1.8.3 Replace with the
following:
28.1.3.2.1.8.3 Class I
standpipe systems shall be permitted to be used to meet the requirement in
28.1.3.2.1.8.1 or 28.1.3.2.1.8.2.
[303:7.2.1.8.3]
28.1.3.2.2 Replace with the
following:
28.1.3.2.
Indoor
Storage and Repair.28.1.3.2.3.4 and
28.1.3.2.3.5 Delete
28.1.3.2.4 Replace with the
following:
28.1.3.2.4
Battery
On Board for Long Term Storage. Where due to size and weight the removal
of batteries for storage or charging is impractical, batteries shall be
permitted to remain on board provided the following conditions are met:
(1) The battery compartment is arranged to
provide adequate ventilation.
(2) A
listed battery charger is used to provide a suitable charge.
(3) The power connection to the charger
consists of a three-wire cord of not less than No. 14 AWG conductors connected
to a source of 110 V to 125 V single-phase current, with a control switch and
approved circuit protection device designed to trip at not more than 125
percent of the rated amperage of the charger.
(4) There is no connection on the load side
of the charger to any other device except the battery, and the boat battery
switch is turned off.
(5) The
battery is properly connected to the charger, and the grounding conductor
effectively grounds the charger enclosure.
(6) Boats are stored at ground
level.
28.1.4.1.1 Replace
with the following:
28.1.4.1.1
Management shall have an inspection made of each boat received for major repair
or storage as soon as practicable after arrival of the boat and before
commencement of any work aboard. [303:8.1.1]
28.1.4.1.3 Replace with the
following:
28.1.4.1.3 Management
shall, as a condition to accepting a boat received for major repair or storage,
require the owner to correct any inadequacies found in
28.1.4.1.2 or to authorize management to do so.
[303:8.1.3]
28.1.4.2.7
Replace with the following:
28.1.4.2.7 The information on fueling
procedures shall be in accordance with 42.9.10.8
28.2.1 Replace with the following:
28.2.1
Section 28.2 shall
apply to marine terminals as defined herein. Special use piers and wharf
structures that are not marine terminals, such as public assembly, residential,
business, or recreational occupancies that differ in design and construction
from cargo handling piers, require special consideration. NFPA 307 shall be
applicable for the construction and fire protection of piers and wharves and
such structures shall comply with NFPA 307 and
Section 28.2
unless otherwise regulated by the
Building Code or other
applicable code or standard.
28.2.1.1 Replace
with the following:
28.2.1.1
Fueling operations at marine terminals, piers, and wharves shall comply with
28.1.4.2.7.
Chapter 29
Parking Garages.
29.1.1 Replace with the following:
29.1.1 The protection of new and existing
parking garages, as well as the control of hazards in open parking structures,
enclosed parking structures, and basement and underground parking structures
shall comply with this chapter and the
Building Code.
29.1.1.1 Add:
29.1.1.1 Parking garages that have elevator
equipment used as motor vehicle parking devices shall also comply with the
Elevator Code.
29.1.1.2 Add
29.1.1.2 Barriers, textile, scrim or other
covering added to an exterior wall of an open parking garage shall comply with
the Building Code.
29.1.2 Delete
Chapter 30
Motor Fuel Dispensing
Facilities and Repair Garages.
30.1.1.4
Add:
30.1.1.4
Underground
Storage Tanks. Associated Piping and Other Environmental Requirements,
see 310 CMR: Department of Environmental
Protection.
30.1.5.1*
Replace with the following:
30.1.5.1 For an unattended self-serve, motor
fuel dispensing facility, additional fire protection shall be provided where
required by the State Fire Marshal.
30.1.5.3 Add:
30.1.5.3 The fire protection system shall be
installed in accordance with the requirements of the State Fire
Marshal.
30.2.5 Replace with the
following:
30.2.5
Fixed Fire
Protection. If in the opinion of the AHJ, it is deemed necessary,
automatic sprinkler protection shall be installed in accordance with NFPA, when
any vehicle containing or using gasoline or any other petroleum product for
fuel or power is kept in a garage and are loaded with merchandise, which is of
such a flammable nature as to be readily ignitable.
30.2.6 Replace with the following:
30.2.6
Gas Detection System.
Repair garages used for repair of vehicle engine fuel systems fueled by
non-odorized gases, such as hydrogen and non-odorized LNG/CNG, shall be
provided with an approved flammable gas detection system. Gas detection systems
in repair garages for hydrogen vehicles shall be in accordance with NFPA
2.[
30A:7.4.6]
30.2.6.1.2 Replace
with the following:
30.2.6.1.2 The
gas detection system shall be designed to activate when the level of flammable
gas exceeds 25 percent of the lower flammable limit (LFL). Gas detection shall
also be provided in lubrication or chassis repair pits of garages used for
repairing non-odorized LNG/CNG fueled vehicles
[30A:7.4.6.1.2]
30.2.8.2.2 Replace with the
following:
30.2.8.2.2
Heat-producing appliances shall be of an approved type. Solid fuel stoves,
improvised furnaces, salamanders, and space heaters shall not be permitted in
areas of repair garages used for repairing or servicing of vehicles or in a
fuel dispensing area. [30A:7.6.2.2]
30.2.8.2.2
Exception 1 Add:
Exception 1: Unit heaters, when installed in
accordance with Chapter 7 of NFPA 30A, need not meet this
requirement.
30.2.8.6* Add:
30.2.8.6* Where major repairs are conducted on CNG-fueled vehicles
or LNG lighter-than-air-fueled vehicles, open flame heating equipment with
exposed surface shaving a temperature in excess of 750°F (399°C) shall
not be permitted in areas subject to ignitable concentrations of gas.
[30A: 7.4.4.1]
30.2.9
Add
30.2.9
Pits, Below Grade
Work Areas, and Subfloor Work Areas.
30.2.9.1 Add:
30.2.9.1 Pits, below grade work areas, and
subfloor work areas used for lubrication, inspection, and minor automotive
maintenance work shall comply with the provisions of this chapter, in addition
to other applicable requirements of NFPA 30A. [30A:
7.4.4.1]
30.2.9.2 Add:
30.2.9.2 Walls, floors, and structural
supports shall be constructed of masonry, concrete, steel, or other approved
noncombustible materials. [30A: 7.4.4.2]
30.2.9.3 Add:
30.2.9.3 In pits, below grade work areas, and
subfloor work areas, the required number, location, and construction of means
of egress shall meet the requirements for special purpose industrial
occupancies in Chapter 40 of NFPA 101. [30A:
7.4.4.3]
30.2.9.4 Add:
30.2.9.4 Pits, below grade work areas, and
subfloor work areas shall be provided with exhaust ventilation at a rate of not
less than 1 ft3/min/ft2 (0.3 m3/min/m2) of floor area at all times that the
building is occupied or when vehicles are parked in or over these areas.
Exhaust air shall be taken from a point within 12 in. (0.3 m) of the floor.
[30A: 7.4.4.4]
Chapter 31
Forest Products and Biomass
Feedstocks
31.1 Replace with the
following:
31.1
General. *The outside storage of forest product
materials within the purpose and scope of this Chapter shall be in accordance
with the provisions of this Chapter.
31.3.2.1.4 Replace with the
following:
31.3.2.1.4 Where the
storage of materials regulated by this Chapter are permitted to accumulate in a
quantity or location that may constitute an undue public safety hazard,
adequate fencing of not less than six (6) ft. (1.8388 m) in height with an
approved locked gate located as necessary to allow the entry of fire department
apparatus, shall be provided. The fencing shall encompass the material or
property.
31.3.3.3.4 Replace with
the following:
31.3.3.3.4 Where
stacks are supported clear of the ground, 6 in. (150 mm) of clearance shall be
provided for cleaning operations under the stacks or, as otherwise approved by
the AHJ.
31.3.3.4.1.1 Replace with the
following:
31.3.3.4.1.1 Open yard
stacking shall be located with not less than 15 ft. (4.6 m) clear space to
buildings or, as otherwise approved by the AHJ.
31.3.3.4.1.2 Replace with the
following:
31.3.3.4.1.2 Boundary
posts with signs designating stacking limits shall be provided to designate the
clear space to unsprinklered buildings in which hazardous manufacturing or
other operations take place or, as otherwise approved by the AHJ.
31.3.6.4.3* Replace with the
following:
31.3.6.4.3 Property line
clearance of not less than 25 ft. (7.62 m) at the base of the pile shall be
provided.
Chapter 32
Motion Picture and Television Production Studio Soundstages and Approved
Production Facilities.
32.1.1
Add:
32.1.1
Terms. As
used in Chapter 32, the enclosed terms shall have the following meaning
assigned to them.
32.1.1(1) Add:
(1)
On-site Personnel. Cast,
crew, vendors, contractors, and any other personnel servicing the
production.
32.2.2
Replace with the following:
32.2.2
Welding, cutting, and other hot work
(1)
Storage and use of flammable or combustible liquids or gases
(2) Use of fog and haze
(3) Use of the site as a production
location
32.2.2
Add:
32.2.2(10) Use of liquified
petroleum gases
32.3.1 Replace with
the following:
32.3.1 Where
required by the AHJ, a fire watch, or standby fire personnel shall be provided
for sound stages and approved production facilities where pyrotechnic special
effects are used.
32.6.2 Replace
with the following:
32.6.2 Chapter
65 shall be used to regulate any pyrotechnic use.
32.9.3.1 Replace with the
following:
32.9.3.1 Means of egress
shall be in accordance with the
Building Code unless otherwise
modified by
32.9.3.2 through
32.9.3.6.
32.9.4.1.2 Replace with the
following:
32.9.4.1.2 A new
soundstage or new approved production facility shall be equipped with an
approved, supervised automatic sprinkler system in accordance with the
Building Code.
32.10.1.1 Replace with the
following:
32.10.1.1 Electrical
power connections made to the site electrical service shall be in accordance
with the Massachusetts Electrical Code.
32.10.1.2 and 32.10.1.3
Delete
Chapter 33
Outside Storage of Tires.
Chapter 33 Delete in its
entirety.
Chapter 34
General Storage.
34.3.10.3
Replace with the following:
34.3.10.3
Lightweight Class.
Lightweight class shall be defined so as to include all papers having a basis
weight [weight per 1000 ft2 (93
m2)] of less than 10 lb (4.5 kg).
34.5.2.2* Replace with the
following:
34.5.2.2* Storage in
buildings and structures shall not be within two feet of a ceiling, or roof
deck or otherwise required by NFPA 13.
34.11.4.1* Replace with the
following:
34.11.4.1* The outside
storage of pallets on the same site as a manufacturing or recycling facility
shall comply with 34.11.4.
Chapter 35
Animal Housing
Facilities
Chapter 35 Delete in its
entirety.
Chapter 36
Telecommunication Facilities and Information Technology Equipment.
Chapter 36 Delete in its
entirety.
Chapter 37
Fixed Guideway Transit and Passenger Rail Systems.
Chapter 37 Delete. in its
entirety.
Chapter 38
Cannabis Growing, Processing or Extraction Facilities
38.5.1 Replace with the following:
38.5.1
Ventilation for Light
Fixtures. Light fixture ductwork shall be installed in accordance with
the manufacturer and NFPA 90A and the
Mechanical Code.
38.5.4.1 Replace with the
following:
38.5.4.1 Interior
finish, including the use of any plastic, mylar, or other thin film sheeting to
enclose rooms or cover any walls or ceilings shall be in accordance with
Sections 12.5,12.6 and the Building
Code.
Chapter
39
Wastewater Treatment and Collection Facilities
Chapter 39 Delete in its
entirety.
Chapter 40
Dust Explosion and Fire Prevention
No amendments
Chapter
41
Welding, Cutting, and Other Hot Work.
41.1.1.1 through 41.1.1.1(8)
Add:
41.1.1.1
Terms.
As used in Chapter 41, the enclosed terms shall have the following meaning
assigned to them.
(1)
Hot Work.
Work involving, burning, welding, or a similar operation that is capable of
initiating fires or explosions.
(2)
Hot Work Operator. A qualified person and if required, shall be
certified pursuant to the provisions of this chapter and standards referenced
in this chapter.
(3)
Qualified Person. A person who has successfully completed the
training criteria pursuant to Section 41.7.
(4)
Management. For the purpose
of hot work, all persons, including owners, contractors, educators, and so on,
who are responsible for hot work operations.
(5)
Permissible Areas.
(a)
Designated Area. A specific
location designed and approved for hot work operations that is maintained
fire-safe, such as a maintenance shop or a detached outside location, that is
of noncombustible or fire-resistive construction, essentially free of
combustible and flammable contents, and suitably segregated from adjacent
areas.
(b)
Permit-required
Area. Any location other than a designated area that is approved for hot
work and is made fire-safe by removing or protecting combustibles from ignition
sources.
(6)
Permit. For the purposes of hot work, a document issued, by the
AHJ, to a qualified person as defined in Section 41.1.1.1(3)
for the purpose of authorizing that individual to carry out the activity of hot
work.
(7)
Permit Authorizing
Individual (PAI). An individual designated by management to authorize
hot work.
(8)
Welding and
Allied Processes. Processes such as arc welding, oxy-fuel gas welding,
open-flame soldering, brazing, thermal spraying, oxygen cutting, and are
cutting.
41.1.5.3
Add:
41.1.5.3
Hot Work
Permit. Hot work permits, where required shall comply with
Section 1.12 and Chapter 41.
41.2.1.8 through 41.2.1.10
Add:
41.2.1.8 Management shall
ensure that the contractor has evidence of financial responsibility, which can
take the form of an insurance certificate or other document attesting to
coverage or responsibility, a copy and an education certification of completion
shall be submitted to the AHJ when requested.
41.2.1.9 Management shall assure that welders
and their supervisors are trained in the safe operation of their equipment, the
safe use of the process, and emergency procedures and maintain education
certificates of completion on file and if requested submit to the
AHJ.
41.2.1.10 Management or
designated agent shall select contractors to perform welding who provide
trained and qualified personnel, and who have an awareness of the risks
involved. [ANSI Z49, 2012]
41.2.2 Replace with
the following:
41.2.2
Permit
Authorizing Individual (PAI). In conjunction with management and in
consultation with the AHJ if required, the PAI shall be responsible for the
safe operation of hot work activities.
41.2.3(4) Add:
(4) The hot work operator shall be permitted
to be the PAI, however, in those cases, the hot works operator shall not be
permitted to issue a hot work permit for the work to be performed by himself,
see the provisions of Section 41.4(1) or
41.4(2).
41.2.4.8 through
41.2.4.8.1 Add:
41.2.4.8 A fire watch, when required, shall
be maintained for at least 1 hour after completion of hot work operations in
order to detect and extinguish smoldering fires. The duration of the fire watch
shall be permitted to be extended if the PAI or the AHJ determines the fire
hazards warrant the extension.
41.2.4.8.1 More
than one fire watch shall be required if determined by the AHJ that combustible
materials could be ignited by the hot work operation which cannot be directly
observed by the initial fire watch.
41.2.5.1 Add:
41.2.5.1
Certificates. A hot
work training certificate shall be carried on person at all times, and shall be
produced upon request.
41.3.5.1
Replace with the following:
41.3.5.1 Before a hot work permit is issued
the following conditions in
41.3.5.1.1 through
41.3.5.1.15 shall be verified by the PAI, and with the AHJ if
required.
41.3.5.1.1 Replace with the
following:
41.3.5.1.1.2 Add:
41.3.5.1.1.2 The hot work equipment to be
used shall be in satisfactory operating condition and in good
repair.
41.3.5.3 Replace with the
following:
41.3.5.3 The PAI in
consultation with the AHJ, if required shall determine the length of the period
for which the hot work permit is valid.
41.3.6.1 Replace with the
following:
41.3.6.1 A fire watch
shall be required by the PAI in consultation with the AHJ, when hot work is
performed in a location where other than a minor fire might develop or where
the following conditions exist:
(1)*
Combustible materials in building construction or contents closer than 35 ft
(11 m) to the hot work operation
(2) Combustible materials more than 35 ft (11
m) away from the hot work operation but easily ignited by sparks
(3) Wall or floor openings within a 35 ft (11
m) radius that expose combustible materials in adjacent areas, including
concealed spaces in walls or floors
(4) Combustible materials adjacent to the
opposite side of partitions, walls, ceilings, or roofs and likely to be
ignited
41.3.6.1.3 Add:
41.3.6.1.3 Figure 41.3.6.1.3 entitled Fire
Watch Decision Tree shall be permitted to be used by the PAI and AHJ to
determine if a fire watch is necessary.
Figure 41.3.6.1.3 Fire Watch Decision Tree
Click to view
image
41.4 Replace with the following:
41.4
Sole Proprietors and Individual
Operators.
41.4.1 Replace with the
following:
41.4.1 All hot work
operations shall require a permit from the Head of the Fire Department unless
specifically otherwise allowed by
41.4.1(1) through
(3):(1)
Hot Work
Operations Conducted by Persons Licensed by Other Jurisdictions.
Pursuant to
Section 1.1.2, a hot work permit shall not be
required from the fire department when the hot work activity is performed by a
person, or under the direct supervision of a person, licensed and permitted
pursuant to a specialized code as defined in M.G.L. c. 143, § 96. Any
licensed person performing hot work must have obtained training for hot work
safety either:
(a) by obtaining training
approved by the authority issuing them a license to perform specialized code
work; or
(b) by meeting the
requirements of Section 41.7 of Chapter 41.
(2)
Hot Work Operations
Conducted by Persons on Their Own Equipment on Their Own Premises. A
permit from the Head of the Fire Department for hot works shall not be required
by individuals who conduct hot work operations on their own equipment on their
own premises. Any person performing such hot work shall be trained as provided
by 41.7 of Chapter 41.
(3)
Homeowners and Hobbyists.
Homeowners and hobbyists are exempt from the permit requirements as provided by
1.12, and the training requirements required in
41.7 of Chapter 41. See exhibitions
41.5.
41.4.2 Replace with
the following:
41.4.2
Assignment of PAI and Fire Watch. Sole proprietors and individual
operators as provided in Sections 41.4(1) and (2) shall be permitted to serve
as PAI, fire watch and operator.
41.4.3 Add:
41.4.3
Written Hot Work Permit.
A checklist shall be permitted to serve as the written hot work permit.
41.5.4.4 Add:
41.5.4.4
Inspection by the AHJ.
41.5.4.4.1 through 41.5.4.4.2
Add:
41.5.4.4.1 The AHJ shall be
permitted to require annual inspection for designated areas.
41.5.4.4.2 The AHJ shall be permitted to
inspect a premise for compliance before any hot work is carried out.
41.7
Add:
41.7
Qualifications. An individual to be qualified to be a PAI, perform
fire watches, perform, supervise or delegate any activities of hot work as
defined in this chapter shall first provide documentation that he or she has
successfully completed training approved by the State Fire Marshal in the
following areas:
(1)527 CMR
1.00: Massachusetts Comprehensive Fire Safety
Code, Chapter 41: Hot Work Operations;
(2)
29 CFR
1910.252 Subpart Q: Welding, Cutting
and Brazing;
(3) NFPA 51B:
Standard for Fire Prevention During Welding, Cutting, and Other Hot
Work;
(4) NFPA 241:
Standard for Safeguarding Construction, Alteration, and Demolition
Operations;
(5) ANSI Z49:
Safety in Welding, Cutting, and Allied Processes.
41.7.1 Successfully completed as used here
means training successfully completed on the currently adopted standard as
provided in 41.7(1) through (5).
41.7.2 A certificate of completion shall be
issued to the individual with the date of completion on the certificate and a
providers/instructors signature acknowledging such individual attended and
completed the training as provided in 41.7(1) through
(5).
Chapter
42
Refueling.
42.1
Replace with the following:
42.1
General. Chapter 42 shall apply to refueling of automotive
vehicles and marine vessels. It shall not be applied to the transportation of
fuel gases over the highways in interstate commerce or vehicles complying with
Federal Motor Vehicle Safety Standards.
42.1.1
Replace with the following:
42.1.1
Terms. As used in Chapter 42, the enclosed terms shall have the
following meaning assigned to them.
42.1.1.1
Add:
42.1.1.1
Point of
Delivery. The outlet of the service meter assembly or the outlet of the
service regulator or the crash valve or service shut off valve where no meter
is provided.
42.1.3
Certificates. Certificates, where required, shall comply with
Section 1.12.8.51 and
Section 1.13, as
applicable.
42.2.2.2 Add:
42.2.2.2 This Chapter shall apply to the
transportation of Class II and Class IDA combustible liquids, by Massachusetts
registered motor vehicles in cargo tanks, portable tanks and transfer tanks by
transport vehicles and flammable liquids in non-bulk packagings.
42.2.2.3 Add:
42.2.2.3 The intent of this Chapter is to
protect the public safety and welfare from the danger of fire due to tank or
container leakage of flammable or combustible liquids and is in addition to the
requirements of the U.S. Department of Transportation, (DOT) Title 49
CFR.
42.3.3.1.1.1 Add:
42.3.3.1.1.1
Underground Tanks.
Underground storage tanks shall comply with
310 CMR
80.00: Underground Storage Tank (UST)
Systems and meet all applicable requirements of NFPA 30, Chapters 21:
Storage of Liquids in Tanks - Requirements for All Storage
Tanks and 23: Storage of Liquids in Tanks - Underground
Tanks.
42.3.3.7 Replace
with the following:
42.3.3.7
Corrosion Control. Any portion of a tank or its piping that is in
contact with the soil shall have properly engineered, installed, and maintained
corrosion protection in accordance with the American Petroleum Institute, the
American Society of Mechanical Engineers, or Underwriters Laboratories Inc. If
corrosion is anticipated beyond the applicable design formulas or standards,
metal thickness or approved protective coating or liners shall be provided to
compensate for corrosion loss expected during the design life of the tank. If
requested by the AHJ, an engineering analysis shall be permitted required to
assure compliance.
42.5.3.4.1 through
42.5.3.4.1(2) Add:
42.5.3.4.1 Dispensing devices shall:
(1) Be rigidly mounted;
(2) Be protected from vehicle damage by at
least one of the following:
(a) The dispensing
device shall be mounted on a concrete platform at least six inches in
height.
(b) Vertical barriers shall
be installed at the ends of pumps.
42.5.3.6.3 Replace with the
following:
42.5.3.6.3
Maintenance. At least annually or when maintenance to dispensing
devices is necessary and such maintenance is capable of causing accidental
release or ignition of liquid, the following precautions shall be taken before
such maintenance is begun:
(1) Only persons
knowledgeable in performing the required maintenance shall perform the
work.
(2) All electrical power to
the dispensing devices, to the pump serving the dispensing devices, and to all
associated control circuits shall be shut off at the main electrical disconnect
panel.
(3) The emergency shutoff
valve at the dispenser, if installed, shall be closed.
(4) All vehicular traffic and unauthorized
persons shall be prevented from coming within 20 ft (6 m) of the dispensing
device.
42.5.7.8 Replace with the
following:
42.5.7.8 The manner of
resetting shall be approved by the AHJ.
42.5.7.10.1 through 42.5.7.10.3
Delete
42.7.2.1 Delete
42.7.2.4.3 Add:
42.7.2.4.3 No gasoline shall be handled
outside of storage tanks or portable gasoline tanks except in approved safety
cans or approved metal or plastic containers, and they shall be kept tightly
closed except when in use. Containers used for the handling and storage of
gasoline in garages shall have a total quantity not to exceed 12
gallons.
42.7.2.6.3 Replace with
the following:
42.7.2.6.3
Fire Suppression Systems. For attended self-serve facilities,
automatic fire suppression systems shall be installed in accordance with the
appropriate NFPA standard, manufacturers' instructions, and the listing
requirements of the systems.
42.7.4.5 through 42.7.4.5(2)(b)
Add:
42.7.4.5 The dispensing of
motor fuel by means of self-service automated dispensing systems shall be
permitted, provided that the applicant for such a system has submitted complete
plans and specifications of the proposed installation to the State Fire
Marshal, accompanied by the required examination fee as authorized in M.G.L. c.
7, § 3B and has obtained approval of such plans, and further provided that
there is compliance with the following:
(1)
Attended Self-service Motor Fuel Dispensing Facility may be allowed provided
that:
(a) The service station is under the
control of the owner, operator, or duly authorized employee who shall be on
duty at all times while motor fuel is being sold or dispensed.
(b) The motor fuel shall be dispensed only by
a competent licensed motor vehicle operator or by the service station
attendant.
(c) Approved signs
bearing the wording "Extinguish All Smoking Materials" and "Stop Engine While
Refueling" shall be conspicuously posted at both ends of the pump dispensing
island visible to approaching vehicles. All approved signs required shall
consist of block letters not less than two inches in height and be either red
letters on a white background or white letters on a red background.
(d) The controlling mechanism console
providing power to the pump motor is in constant attendance by the owner,
operator or duly authorized employee at all times while motor fuel is being
dispensed and is properly protected against physical damage from motor
vehicles. Constant attendance shall mean that the console operator must be at
the console during its operation.
(e) There is constant contact between the
controlling mechanism console operator and the pump island by means of an
intercommunication system which shall be maintained in proper operating
condition at all times while motor fuel is being dispensed.
(f) A means is provided for the controlling
mechanism console operator to observe the filling operation at each vehicle,
and the dispensing of motor fuel shall be continuously observed by the console
operator during the time that any of the pumps have been activated to dispense
motor fuel.
(g) The controlling
mechanism console includes a disconnect switch which will instantly cut off all
pumping power to all motor fuel pumps at the service station.
(h) The controlling mechanism console,
switches and related equipment are of a design and type listed for use with the
dispensing devices.
(i) Any person,
firm, or corporation constructing a self-service facility or making changes or
alterations, in the method of dispensing motor fuel, or to the pre-engineered
fixed fire extinguishing system(s) other than normal maintenance, or to the
self-service dispensing island arrangement(s) resulting in a change of hazard
area protection, or environmental changes resulting in the inability of a
console operator to constantly observe the fuel dispensing operation, shall
notify the Head of the Fire Department, in writing, prior to submitting plans
to the State Fire Marshal.
(j)
Self-service automated motor fuel dispensing systems shall be equipped with an
overhead fixed fire extinguishing system of a type approved by the State Fire
Marshal, details of which shall be included with plans submitted to the State
Fire Marshal for approval.
(k) The
use of automatic credit card reading devices as a means of payment at the pump
island shall be allowed provided that:
1. Each
sale shall be individually authorized by the self-serve attendant;
authorization functions shall not be overridden.
2. The automatic credit card reading device
shall not be used as physical authorization for the dispensing of motor fuel;
and
3. The automatic credit card
reading devices are included on plans submitted to and approved by the State
Fire Marshal.
(l)
Activation of such new fire extinguishing system shall be electrically
supervised by a listed fire alarm control unit and such alarm signal shall be
automatically transmitted in accordance with the requirements of 780
CMR
(2) Split island
facilities shall be permitted provided that:
(a) There shall be installed on the full
service islands an additional switch which will activate the overhead fire
extinguishing system, and deactivate power to the self-service island
dispensing pumps.
(b) Whenever the
self-service dispensing mechanism is in operation, the service station operator
shall be within visual range of the filling operation by either being at the
controlling mechanism console or at the full service pump island within 25 feet
of the switch.
42.7.5 through
42.7.5.6 Delete.
42.7.6.3 Replace with the
following:
42.7.6.3 The dispensing
hose shall not exceed 150 ft. (46 m) in length.
42.9.1.2(4) Add:
(4) Foreign vessels regulated under Title
33 CFR
155 and U.S. and foreign public vessels,
i.e., warships, naval auxiliaries or other ships owned and
operated by a country when engaged in noncommercial service.
42.9.3 through
42.9.3.7.5 (9) Add:
42.9.3.7
Wharf of a Marine Fueling Facility.
42.9.3.7.1 Any wharf of a Marine Fueling
Facility shall be equipped with only listed and labeled control valves and
devices.
42.9.3.7.2 Authorized
Fueling Facility System Operators shall be aware of the location of all such
shut-off control devices.
42.9.3.7.3 The use of additional shut-off
control valves in excess of the required minimum shall be permitted to
facilitate fuel system servicing and to control fuel flow during both normal
and emergency operation.
42.9.3.7.4
Cast iron valves or fittings shall not be used in any pipe connection located
between the tank and dispensing nozzle.
42.9.3.7.5 Items (1), (2) (3) and (5) shall
be required for all fixed facilities. Items (4), and (6) shall be permitted on
a site specific basis.
(1) Dispensing Nozzle
shall be approved.
(2) Dispenser
Shut-off.
(a) All dispensers shall be provided
with an approved shut-off valve at the fueldispensing unit.
(b) This valve shall be permitted to be the
dispenser unit shut-off.
(3) Manual Electrical Emergency Fuel Shut-off
Pull Stations shall be U.L. listed; and
(a)
shall be provided to disrupt power to all dispensers and fuel storage tank
discharge pump(s).
(b) These Pull
Stations shall be located within 25 ft. of any metering unit; and shall be
located to be in the path of exit travel.
(c) Additional pull station shall be provided
as required by the Head of the Fire Department or the State Fire
Marshal.
(d) Pull stations shall
not be located on gangways.
(e) All
pull stations shall be marked "EMERGENCY FUEL SHUT-OFF" in two inch red block
capital letters; and shall be accessible at all times.
(4) Fuel piping systems to floats shall be
provided with a readily accessible approved shut off valve on the fixed pier
(or land if applicable) within 15 ft. of the flexible connector from the pier
(or land) to the float.
Said shut-off controls shall be marked "EMERGENCY FUEL
SHUT-OFF" in two inch red block capital letters; and shall be accessible at all
times.
(5) Fuel piping
systems on fixed piers shall be provided with a readily accessible shut-off
valve on the pier within four feet of the flexible connector to the land and on
the land within 15 ft. of the pier.
Shut-off controls shall be marked "EMERGENCY FUEL SHUT OFF" in
two inch red block capital letters and shall be accessible at all times.
(6) Emergency shut-off valves,
incorporating a fusible link or other approved thermally actuated device
designed to close automatically in event of fire exposure or severe impact,
shall be installed in accordance with the manufacturer's instructions in the
flammable or combustible liquid supply line.
(a) The shut-off valve shall be located at
the base of each individual dispenser or at the inlet to the overhead
dispenser.
(b) The automatic
closing feature of excess flow valves shall be tested at least once per month
by manually tripping the hold open device.
(c) The valves shall be readily accessible;
and
1. shall employ cover or similar means
located on the shore side of the wharf; and
2. shall be so marked by two inch red block
capital letters.
(7) Divisional valves shall be installed on
the marine wharf so that the maximum length of the piping system is 300 ft.
between divisional valves.
(a) Divisional
valves shall be marked by two inch red block capital letters.
(b) Each valve shall be clearly identified,
by marking with a permanent plate or tag indicating its system
function.
(8) At marine
fueling facilities where tanks are at an elevation which produces a gravity
head on the dispensing unit, the tank outlet shall be equipped with a device,
such as a solenoid valve, positioned adjacent to, and downstream, so installed
and adjusted that liquid cannot flow by gravity from the tank in case of piping
or hose failure when the dispenser is not in use.
(9) Shut-off and check valves shall be
equipped with a pressure-relieving device that will relieve any pressure
generated by thermal expansion of the contained liquid back to the storage
tank.
42.9.3.8
Add:
42.9.3.8 Shut-off and check
valves shall be equipped with a pressure-relieving device that will relieve any
pressure generated by thermal expansion of the contained liquid back to the
storage tank.
42.9.3.9
Add:
42.9.3.9 Marine piping systems
shall contain a sufficient number of approved valves to control the flow of
flammable or combustible liquid during normal operations and to provide
adequate shut-off protection in the event of fire or physical damage.
42.9.4.1.1.1 Add:
42.9.4.1.1.1 Said hose shall be a rubber like
material resistant to petroleum products and petroleum product, containing a
continuous static ground, not exceeding 30 feet in length. Where hose length at
a marine fueling facility exceeds 30 feet, the hose shall be secured by a hose
retrieving mechanism so as to protect it from damage.
42.9.4.8 through
42.4.8.2 Add:
42.9.4.8
If a remote pumping system is used, a labeled or listed rigidly anchored
emergency shutoff valve incorporating a fusible link or other thermally
actuated device, designed to close automatically in event of fire exposure or
severe impact, shall be installed in accordance with the manufacturer's
instructions in the flammable or combustible liquid supply line at the base of
each individual dispenser or at the inlet of each overhead dispenser.
42.9.4.8.1 The automatic closing feature of
this valve shall be checked at least once a month by manually tripping the
hold-open linkage.
42.9.4.8.2 An
emergency shut-off valve incorporating a slip-joint feature shall not be
used.
42.9.4.9
Add:
42.9.4.9 The fueling facility
shall be located so as to minimize exposure to all other operational marina or
pleasure boat berthing area facilities. Where tide and weather conditions
permit, all flammable and combustible liquid fuel handling shall be outside the
main berthing area. Inside marina or pleasure boat berthing area, fueling
facilities shall be so located that in case of fire aboard a boat alongside,
the danger to other boats near the facility will be minimal. No vessel or craft
shall be made fast to or berthed at any marine wharf, except during fueling
operations, and no vessel or craft shall be made fast to any other vessel or
craft occupying a berth at a marine wharf, or other fueling facility.
42.9.4.10 Add:
42.9.4.10 Fueling of floating marine craft at
other than a fueling facility is prohibited, except by prior written
authorization by the AHJ.
42.9.7.4 through 42.9.7.4.1
Add:
42.9.7.4 All marine fueling
facilities shall provide roadways to provide for adequate access for emergency
vehicles, including fire apparatus to within 150 feet (45 m) or less travel
distance to the shore end of the marine wharf.
42.9.7.4.1 When approved by the Head of the
Fire Department, a manual standpipe system shall be permitted to be installed
along marine wharfs when conditions are such that providing fire department
access roads to within 150 feet (45 m) of the shore end of the marine wharf is
not practical.
42.9.7.5
through 42.9.7.5.3 Add:
42.9.7.5 A manual standpipe system shall be
installed at all fueling wharfs where the travel distance from the closest
point of access for the fire department apparatus to the most remote accessible
portion of the marine wharf exceeds 150 feet (45 m).
42.9.7.5.1 The type and location of standpipe
systems and standpipe outlets shall be approved by the Head of the Fire
Department, but in no case shall they be more than 150 feet (45 m) of travel
distance apart, and no more than 150 feet (45 m), travel distance from a dead
end.
42.9.7.5.2 The fire department
pumper can be considered as a standpipe system discharge point if it is within
150 feet (45 m) of the shore end of the marine wharf.
42.9.7.5.3 The standpipe piping shall be no
less that three inches (76.2 mm) inside side nominal diameter and sized to
provide a minimum of 500 gpm (1893L/min) at 100 psi outlet pressure at the
hydraulically most remote outlet with an outlet.
42.9.7.6 through 42.9.7.6.3
Add:
42.9.7.6 Hydrants shall be
provided on marine fueling facility wharfs where fire apparatus is expected to
drive onto the wharf to protect a fueling facility.
42.9.7.6.1 The hydrants shall be installed,
tested and maintained in accordance with NFPA 307: Standard for the
Construction and Fire Protection of Marine Terminals, Piers, and
Wharves in locations approved by the Head of the Fire
Department.
42.9.7.6.2 In a hydrant
shall be within 100 feet (30.48 m) of the required standpipe
connection.
42.9.7.6.3 If
available, the type and capacity of the water supply system for the fire
hydrants shall be sufficient to deliver adequate water and water pressure as
determined by the Head of the Fire Department, who shall take into
consideration the relative fire hazard, the property involved, the availability
of marine firefighting equipment, and the time frame that the water supply
volume will be required to be maintained.
42.9.8.4 Add:
42.9.8.4 No cargo tank, portable tank or
transfer tank shall be mounted in the bed or body of any vehicle which contains
a hoist to raise such bed or body.
42.9.9.8 Add:
42.9.9.8 Vehicles, other than approved tank
vehicles, shall be permitted to transport combustible liquids in transfer
tanks, provided that an application has been made and a permit to transport has
been issued. The vehicle shall be approved for the transportation of the
combustible liquid provided that:
(1) The tank
shall be constructed of not less than 14 USS gauge standard open hearth steel
tank plate or 1/8 inch aluminum and otherwise constructed to withstand any
stress to which it may reasonably be subjected.
(2) The liquid is drawn only from the top of
the tank by means of a suitable pump to which is attached a durable hose
equipped with a self-closing nozzle.
(3) All openings in the tank are secured by
plugs or caps maintained wrench tight while the vehicle is in
transit.
(4) The tank is securely
mounted to the vehicle body or truck bed and its capacity does not exceed 110
gallons.
42.9.9.9 Any
flammable or combustible liquid transported by other than cargo tank, portable
tank or transfer tank shall be transported in listed containers, with all
openings tightly closed, and in an upright and secured position.
42.9.10.1(5) Add:
(5) In the event of a leak, rupture, spill,
overflow or other incident involving the handling of flammable or combustible
liquids, at the fuel facility, both the Fire Department and the State Fire
Marshal shall be notified immediately by the fueling operations supervisor or
the permit holder.
42.10 through 42.10.6.2.9
Delete.
42.11.1 Delete.
42.11.1.1.2 through 42.11.1.1.4
Delete
42.11.1.1.5 Add:
42.11.1.1.5
Marker Plate, Sign.
Any liquefied gaseous system container or cylinder installation shall be
provided with a marker plate or sign indicating the name and telephone number
of the supplier, facility maintenance person, owner, or operator responsible
for responding to the permitted location in the event of an
emergency.
42.13.1
through 42.13.11 Add:
42.13.1
Fuel Vessels and
Barges.
42.13.2 No fuel
barge or fuel vessel shall be permitted to anchor or moor for fueling purposes
within a marina or pleasure boat berthing area.
42.13.3 A 200 ft. (60.96 m) radius marine
fueling safety zone shall be maintained between the fuel barge, or fuel vessel
acting as a fueling facility, and any marina or pleasure boat berthing
area.
42.13.4 This 200 ft. (60.96
m) radius marine fueling safety zone if required, shall be subject to written
review by the Head of the Fire Department in specific instances.
42.13.5 The State Fire Marshal shall approve
the marine fueling safety zone written review.
42.13.6 Fuel barges and fuel vessels shall be
subject to assignment as to location by the harbor master in accordance with
the authority vested in him by M.G.L. c. 102. When located on waters where no
harbor master is provided, such assignment shall be made by the State Fire
Marshal. The State Fire Marshal shall approve the permanent assignment of fuel
barges and fuel vessels.
42.13.7
Fuel barges, fuel vessels, and fueling facilities shall be open to inspection
by the AHJ or a harbor master having jurisdiction.
42.13.8 Flammable and combustible liquids
kept for resale on fuel barges or fuel vessels shall be stored in metal tanks.
Such tanks shall be constructed, braced and secured so as to prevent injury,
rupture or displacement and to withstand the normal stresses to which they may
be subjected. Tanks constructed in accordance with 46 CFR Part 30 through 40,
Subchapter D -Tank Vessels, will be considered as complying
with the requirements of this chapter.
42.13.9 Every fuel barge or fuel vessel used
for the keeping of flammable or combustible liquids for resale and every fuel
barge or fuel vessel used for the transportation of flammable or combustible
liquids, shall be identified by a name marked in clearly legible letters not
less than four inches in height on some clearly visible exterior part of the
port and starboard bow and the stern of that fuel barge or fuel
vessel.
42.13.10 Fuel barges and
fuel vessels which, in the opinion of the Head of the Fire Department or the
State Fire Marshal, pose a substantial fire hazard due to the cargo they are
carrying or the location they are moored shall rig fire warps. Fire warps shall
consist of hausers of sufficient size to take the barge or vessel under tow in
the event of an emergency. Fire warps shall be secured to the deck of the barge
or vessel and shall hang over the outboard side to within 6 feet of the surface
of the water. An eye shall be spliced into the outboard end of the warp of
sufficient size to permit the rapid attachment of a towing shackle.
42.13.11 Every fuel barge, fuel vessel, or
fueling facility used for the keeping of flammable or combustible liquids for
resale shall be provided with such fire extinguishing appliances as required by
Section 13.6.
42.14 Add:
42.14
Containers and Movable
Tanks.
42.14.1 through
42.14.4 Add:
42.14.1
The temporary use of movable tanks in conjunction with the dispensing of
liquids into the fuel tanks of marine craft shall be permitted. Such use shall
only be made with the approval of the AHJ.
42.14.2 Class I or Class II liquids shall not
be dispensed into a portable container, unless the container is constructed of
metal or is listed for its use, has a tight closure, and is fitted with a spout
or is so designed that the contents can be dispensed without
spilling.
42.14.3 Portable
containers of 12 gal. (45 L) capacities or less shall not be filled while they
are in or on a marine craft.
42.14.4 Smoking is prohibited on any fuel
barge or fuel vessel used for the keeping of flammable or combustible liquids
for resale and on any fuel barge or fuel vessel used for the transportation,
storage or delivery of flammable or combustible liquids.
42.15.1 Add:
42.15.1 All electrical components shall be
installed and used in accordance with the Massachusetts Electrical
Code.
42.15.2
Add:
42.15.2 Clearly identified
emergency switches, readily accessible in case of fire or physical damage at
any dispensing unit, shall be provided on each marine wharf so interlocked as
to shut off power to all pump motors from any individual location and to reset
only from the master switch at the main electrical disconnect panel. Each such
switch is to be identified by an approved sign stating "EMERGENCY PUMP
SHUT-OFF" in two inch red block capital letters.
42.15.3 Add:
42.15.3 A readily accessible valve to shut
off the liquid supply from shore shall be provided in each pipeline, at or near
the approach to the pier and at the shore end of each marine pipeline adjacent
to the point where each flexible hose is attached. Each valve shall be marked
"EMERGENCY FUEL SHUT-OFF" in two inch red block capital letters.
42.16 Add:
42.16
Transportation by Transfer
Tanks.
42.16.1 Add:
42.16.1 Vehicles other than approved tank
vehicles shall be permitted to transport combustible liquids in transfer tanks,
provided that an application has been made in accordance with this
Code.
42.16.2
through 42.15.2(5) Add:
42.16.2 The vehicle shall be approved for the
transportation of the combustible liquid provided that:
(1) The tank is securely mounted to the
vehicle body or truck bed and its capacity does not exceed 119
gallons;
(2) The tank shall be
constructed of not less than 14 USS gauge standard open hearth steel tank plate
or
1/8 inch aluminum
and otherwise constructed to withstand any stress to which it may reasonably be
subjected;
(3) The liquid is drawn
only from the top of the tank by means of a suitable pump to which is attached
a durable hose equipped with a self-closing nozzle;
(4) All openings in the tank are secured by
plugs or caps maintained wrench tight while the vehicle is in transit;
and
(5) The vehicle is equipped
with a fire extinguisher in accordance with Section
13.6.
42.16.3
Add:
42.16.3 Any flammable or
combustible liquid transported by other than cargo tank, portable tank or
transfer tank shall be transported in listed and labeled containers, with all
openings tightly closed, and in an upright and secured position.
42.16.4 Add:
42.16.4 No person shall transport by cargo
tank or transport vehicle, any combustible liquid within the Commonwealth,
unless such liquid is transported in accordance with the requirements of this
Chapter. No person shall transport by cargo tank or transport vehicle, any
flammable liquid unless such liquid is transported in accordance with U.S. DOT,
Title 49 CFR.
Chapter
43
Spraying, Dipping, and Coating Using Flammable or
Combustible Materials
43.1.3.1.1.2
Replace with the following:
43.1.3.1.1.2 Air intake filters that are a
part of a wall or ceiling assembly shall be listed as Class 1 or Class 2, in
accordance with ANSI/UL 900, Standard for Air Filter Units.
[33:5.1.1.2]
43.1.5.3*
Make-Up Air. An adequate supply of clean make-up air shall be
provided to compensate for the air exhausted from spray operations. The intake
for this make-up air shall be located so that the air exhausted from spray
operations is not recirculated. [33:7.3]
Chapter 44
Solvent Extraction.
44.3.1 Add:
44.3.1 Permits may be required by Chapter 60,
or other chapters, based on the type of process and level of hazard.
Chapter 45
Combustible
Fibers.
45.5.3.1 Replace with the
following:
45.5.3.1 Quantities
exceeding 100 ft.3 (2.8
m3) of loose combustible fibers, but not exceeding
500 ft.3 (14.2 m3), shall
be permitted to be stored in rooms or compartments in which the floors, walls,
and ceilings have a fire-resistance rating of not less than 1 hour.
45.6.1.1 Replace with the
following:
45.6.1.1 No single block
or pile shall contain more than 7,500 ft.3 (212.376
m3) of combustible fibers, exclusive of aisles or
clearances. However, a single block or pile shall be permitted containing
25,000 ft.3 (708 m3) of
combustible fibers, exclusive of aisles or clearances, if the criteria of NFPA
13: Standard for the Installation of Sprinkler Systems are
met.
Chapter 46
Additive Manufacturing (3D Printing)
Chapter 50
Commercial Cooking.
50.1.3* Cooking equipment used in fixed,
mobile, or temporary concessions, such as trucks, buses, trailers, pavilions,
tents, or any form of roofed enclosure, shall comply with NFPA 96 or this
chapter unless otherwise exempted by the AHJ in accordance with
1.3.2 of NFPA 96. [96.1.13]
50.2.1.1(1) through (2)(b) Add:
50.2.1.1(1) Cooking equipment used in
processes producing smoke or grease-laden vapors shall be equipped with an
exhaust system that complies with all the equipment and performance
requirements of this chapter.
(1) Type 1 hoods
are required for the removal of grease-laden vapors provided they meet all the
material and performance requirements of this Code.
(2) The following are types of hoods used for
exhaust:
(a)
Type I. Hoods
designed for grease exhaust applications.
(b)
Type II.
Hoods designed for heat and steam removal and other non-grease applications.
These hoods are not applicable to this standard.
50.2.1.2.1 Add:
50.2.1.2.1
Certificates.
Certificates, where required, shall comply with Section
1.13.
50.6.4.1
Add:
50.6.4.1 If the AHJ determines
that the exhaust system of such operation has not been inspected pursuant to
Section 50.6.4 for grease buildup within the past 12-month
period, the AHJ shall issue an order to cease such operation pending such
inspection. Section 50.6.4.1 shall not limit the ability of
the AHJ to issue such other reasonable orders relating to compliance with this
Chapter.
50.6.6.2* Replace with the
following:
50.6.6.2 Hoods, grease
removal devices, fans, ducts, and other appurtenances shall be cleaned to
remove combustible contaminants to a minimum of 50 pm (0.002 in.). A
measurement system of deposition shall be established for each facility to
trigger a need to clean, to verify the requirements contained in Table 50.6.4,
in addition to a time reference based on equipment emissions.
50.6.6.2.1 Add
50.6.6.2.1 The owner or operator of the
commercial cooking operation, or employee thereof, shall not be prohibited from
conducting the actual cleaning and grease removal of hoods, grease removal
devices, fans, ducts and other appurtenances of his or her own commercial
cooking operations, as long as said owner, operator, or employee holds a
"restricted" Certificate of Competency issued by the State Fire Marshal.
However, this provision does not allow such owner, operator, or employee to
conduct such cleaning services for any other commercial kitchen
operation.
50.6.6.13
Replace with the following:
50.6.6.13 When an exhaust cleaning service is
used, a certificate showing the name of the servicing company, the name of the
person performing the work, and the date of inspection or cleaning shall be
maintained on the premises. The content, size, design, and placement of any
label shall be prescribed by the State Fire Marshal. [96:11.6.13].
50.6.6.14.1 through 50.6.6.14.1.2
Add:
50.6.6.14.1 If a
qualified individual determines that a commercial cooking system, after
cleaning or inspection thereof, is not in compliance with this Chapter,
relative to grease buildup and related contaminants, said individual shall,
within 48 hours, notify in writing, on a form prescribed by the State Fire
Marshal, the Head of the Fire Department of the location of said system and the
nature of such noncompliance. A copy of said form shall also be given to the
owner and operator of the system.
50.6.6.14.1.1 A record of each inspection for
grease and related contaminants and each cleaning activity relating to grease
buildup shall be produced by the qualified person who conducted said inspection
or cleaning. Said record shall include:
(1)
The dates of inspection or cleaning;
(2) Location;
(3) The CR number for the contractor and CC
number for the inspector and cleaner;
(4) Signatures of each involved in the
inspection and cleaning;
(5) Any
other information as determined by the State Fire Marshal; and
(6) A copy of such record shall be maintained
by:
(a) The operator within the building or
structure where the system is located; and
(b) The qualified person who conducted said
inspection or cleaning activity.
50.6.6.14.1.2 Such records shall be open to
the inspection of the AHJ during regular hours of operation and shall be
maintained for a period of at least three years.
50.6.6.14.1.3 Any incident involving the loss
or theft of any label(s) must be reported to the State Fire Marshal and the
police department within the jurisdiction where the loss or theft occurred
within 72 hours. Failure to report such loss or theft shall result in the
rebuttable presumtion that the holder of the label performed or allowed another
to perform the services associated with said label(s). Any person who
unwittingly allows another to use their label(s) after a prudent licenseholder
would have cause to know of a loss or theft of same, or misappropriation or
misrepresentation of identity, may have their Certificate of Competency and
Certificate of Registration suspended for a minimum of two years.
Chapter 51
Industrial Ovens and Furnaces
No amendments
Chapter
52
Energy Storage Systems
52.1.1.1 Add:
52.1.1.1
One- and Two-Family Dwelling
and Townhouse Units. Where one- and two-family dwellings and townhouse
units are provided with energy storage systems (ESS) they shall be in
accordance with Chapter 15 of NFPA 855 and Section
52.9.
52.1.8.2 Replace
with the following:
52.1.8.2
Operational permits shall be in accordance with
52.1.2.
52.9
Replace with the following:
52.9
One- and Two-Family Dwelling and Townhouse Units. Where one-and
two-family dwellings and townhouse units are provided with energy storage
systems (ESS) they shall be in accordance with Chapter 15 of NFPA 855.
52.9.1* through 52.9.7.2* Add:
52.9.1*
Other technology
Where other than lithium-ion energy storage systems are
provided, they shall be in accordance with Table 1.3 of NFPA 855 and this
code.
52.9.2
Construction Documents. The plans and specifications associated
with an ESS and its intended installation, replacement or renewal,
commissioning, and use shall be submitted to the AHJ for approval and include
the following:
1. Location and layout diagram
of the room or area in which the ESS is to be installed.
2. Details on wall construction for rooms or
areas where ESS are installed.
3.
The quantities and types of ESS units.
4. Manufacturer's specifications, ratings,
and listings of ESS.
5. Description
of energy storage management systems and their operation.
6. Location and content of required
signage.
7. Details on fire
suppression, smoke or fire detection, gas detection, thermal management,
ventilation, exhaust, and deflagration venting systems, if provided.
8. Support arrangement associated with the
installation, including any required seismic support.
9. Description of scope of work for retrofit
or repairs of ESS.
52.9.3
Decommissioning. A decommissioning plan shall be prepared in
accordance with Chapter 8 of NFPA 855, submitted to the AHJ and approved prior
to decommissioning the system.
52.9.4
Location. ESS shall only
be installed in the locations specified by Chapter 15 of NFPA 855 and
52.9.4.1
52.9.4.1 ESS
installed in enclosed utility closets, storage, or utility spaces is permitted
only where the enclosed utility closet, storage, or utility space does not open
into a sleeping area.
Exception: Buildings provided throughout with an
automatic fire sprinkler system complying with NFPA 13D, 13R, or
13.
52.9.5
Operation, Testing and
Maintenance. Operation, maintenance, and testing of ESS shall be in
accordance with the manufacturer's instructions. Records shall be provided to
the AHJ upon request.
52.9.6
Combustible Storage. Combustible materials not related to the ESS
shall not be stored in rooms, cabinets, enclosures, or closets containing ESS
equipment.
52.9.6.1 Where ESS is installed in
a garage and not separated from the remainder of the room by an enclosure,
combustible materials shall not be stored within 3 ft. of the ESS
equipment.
52.9.7
Equipment. Repairs and retrofitting of ESS shall only be done by
qualified persons, comply with the applicable provisions of NFPA 855, and
documented per
52.9.2.
52.9.7.1
Replacements.
Replacement of ESS shall be considered new ESS installations and comply with
the provisions applicable to new ESS.
52.9.7.2*
Increase in power rating or
maximum stored energy.
A complete new ESS that is added to an existing installation of
one or more systems shall be treated as a new system and meet the applicable
requirements. The increased system shall be evaluated in the aggregate.
Chapter
53
Mechanical Refrigeration.
53.1.1.4 through 53.1.1.4.1
Add:
53.1.1.4 Hazardous Materials
Processing
53.1.1.4.1 Ammonia and LP Gas
Refrigeration systems shall comply with
60.8.
53.1.2.1 Delete.
Chapter 54
Ozone Gas Generating
Equipment
Chapter 54 Delete in its entirety.
Chapter 55
Cleaning and Purging of
Flammable Gas Piping Systems
No amendments
Chapter
60
Hazardous Materials.
60.1.2(14) Add:
(14) Consumer fireworks, 1.4G in mercantile
occupancies complying with Section 65.10
[5000:34.1.1.2]
60.1.2(15) through (17) Add:
(15) Closed piping systems containing
flammable or combustible liquids or gases utilized for the operation of
machinery or equipment.
(16) The
storage or utilization of materials for agricultural purposes on the premises
complying with the Building Code Appendix C Group
U--Agricultural Buildings.
(17) The storage of black powder, smokeless
propellants, small arms primer in use group M or R-3 and special industrial
explosive devices in use group B, F, M, and S provided the storage conforms to
Chapter 65.
60.4.2.1.1.3
Replace with the following:
60.4.2.1.1.3 A permit shall not be issued in
excess of these quantities until such time that the Building Official has
confirmed the facility is classified and constructed as the appropriate a
H-use, control area, or is exempt.
60.4.2.1.1.3 Replace table as follows:
Table 60.4.2.1.1.3 Maximum Allowable Quantity (MAQ) of
Hazardous Materials per Control Area
a,p,q,s,u,v
Insert Table 60.4.2.1.1.3
Table 60.4.2.1.1.3 Maximum Allowable Quantity (MAQ) of
Hazardous Materials per Control Area
|
High |
Storagea |
Use - Closed
Systemsa |
Use - Open
Systemsa |
Hazard |
Liquid |
Liquid |
Liquid |
Protection |
Solid |
Gallons |
Gasb
scf |
Solid |
Gallons |
Gasb
scf |
Solid |
Gallons |
Material |
Class |
Level |
Pounds |
(lb) |
(lb) |
Pounds |
(lb) |
(lb) |
Pounds |
(lb) |
Physical Hazard Materials |
Combustible
liquidm,o |
II |
2 or 3 |
N/A |
120c,d |
N/A |
N/A |
120d |
N/A |
N/A |
30d |
IIIA |
2 or 3 |
N/A |
330c,d |
N/A |
N/A |
330d |
N/A |
N/A |
80d |
IIIB |
N/A |
N/A |
13200c,e |
N/A |
N/A |
13200e |
N/A |
N/A |
3300e |
Combustible dust |
N/A |
2 |
See note
v |
N/A |
N/A |
See note
v |
N/A |
N/A |
See note
v |
N/A |
Combustible fiber
t |
Loose |
3 |
(100) |
N/A |
N/A |
(100) |
N/A |
N/A |
(20) |
N/A |
Baledr |
3 |
(1000) |
N/A |
N/A |
(1000) |
N/A |
N/A |
(200) |
N/A |
Cryogenic fluid [55:Table 6.3.1] |
Flammable |
2 |
N/A |
45d |
N/A |
N/A |
45d |
N/A |
N/A |
45
d |
Oxidizing |
3 |
N/A |
45d |
N/A |
N/A |
45d |
N/A |
N/A |
45
d |
Inert |
N/A |
N/A |
N/A |
NL |
N/A |
N/A |
NL |
N/A |
N/A |
Explosives |
Division 1.1 |
1 |
1
c,i |
(1)
c,i |
N/A |
1/4i |
(1/4)i |
N/A |
1/4i |
(1/4)i |
Division 1.2 |
1 |
1
c,i |
(1)
c,i |
N/A |
1/4i |
(1/4)i |
N/A |
1/4i |
(1/4)i |
Division 1.3 |
1 or 2 |
5
c,i |
(5)
c,i |
N/A |
1i |
(1)
i |
N/A |
1
i |
(1)
i |
Division 1.4 |
3 |
50
c,i |
(50)
c,i |
N/A |
50 i |
(50)
i |
N/A |
N/A |
N/A |
Division 1.4G |
3 |
125
c,i |
N/A |
N/A |
N/A |
N/A |
N/A |
N/A |
N/A |
Division 1.5 |
1 |
1
c,i |
(1)
c,i |
N/A |
1/4i |
(1/4)i |
N/A |
1/4i |
(1/4)
i |
Division 1.6 |
1 |
1
c,i |
N/A |
N/A |
N/A |
N/A |
N/A |
N/A |
N/A |
Flammable Gas1 [55: Table
6.3.1] |
Gaseous |
2 |
N/A |
N/A |
1000
c,d |
N/A |
N/A |
1000
c,d |
N/A |
N/A |
Liquefied |
2 |
N/A |
N/A |
(150)
c,d |
N/A |
N/A |
(150)
c,d |
N/A |
N/A |
Liquefied Petroleum (LP) |
See note |
See note |
See note |
See note |
See note |
See note |
See note |
See note |
See note |
Flammable
Liquidm |
IA |
2 |
N/A |
30c,d |
N/A |
N/A |
30
d |
N/A |
N/A |
10
d |
IB and IC |
3 |
N/A |
120
c,d |
N/A |
N/A |
120
d |
N/A |
N/A |
30
d |
Combination (IA, IB, IC) |
2 or 3 |
N/A |
120
c,d,n |
N/A |
N/A |
120
d,n |
N/A |
N/A |
30
d,n |
Flammable Solid |
N/A |
3 |
125
c,d |
N/A |
N/A |
125
d |
N/A |
N/A |
25d |
N/A |
Inert Gas |
Gaseous |
N/A |
N/A |
N/A |
NL |
N/A |
N/A |
NL |
N/A |
N/A |
Liquefied |
N/A |
N/A |
N/A |
NL |
N/A |
N/A |
NL |
N/A |
N/A |
Organic Peroxide |
UD |
1 |
1c,i |
(1)
c,i |
N/A |
1/4i |
(1/4)i |
N/A |
1/4i |
(1/4)i |
I |
2 |
5
c,d |
(5)
c,d |
N/A |
1
d |
(1)
d |
N/A |
1
d |
(1)
d |
II |
3 |
50
c,d |
(50)
c,d |
N/A |
50d |
(50)
d |
N/A |
10d |
(10)
d |
III |
3 |
125
c,d |
(125)
c,d |
N/A |
125
d |
(125)d |
N/A |
25
d |
(25)
d |
IV |
N/A |
NL |
NL |
N/A |
NL |
NL |
N/A |
NL |
NL |
V |
N/A |
NL |
NL |
N/A |
NL |
NL |
N/A |
NL |
NL |
Oxidizer |
4 |
1 |
1i |
(1)
i |
N/A |
1/4i |
(1/4)i |
N/A |
1/4i |
(1/4)i |
3f |
2 or 3 |
10c,d |
(10)
c,d |
N/A |
2d |
(2)d |
N/A |
2
d |
(2)
d |
2 |
3 |
250,c,d |
(250)
c,d |
N/A |
250
d |
(250)
d |
N/A |
50
d |
(50)
d |
1 |
N/A |
4000c,e |
(4000)
c,e |
N/A |
4000e |
(4000)
e |
N/A |
1000e |
(1000)e |
Oxidizing Gas |
Gaseous |
3 |
N/A |
N/A |
1500g,c,d |
N/A |
N/A |
1500
g,c,d |
N/A |
N/A |
Liquefied |
3 |
N/A |
(1500)
g,c,d |
N/A |
(1500)
g,c,d |
N/A |
N/A |
Pyrophoric |
2 |
4c,i |
(4)
c,i |
N/A |
1i |
(1)
i |
N/A |
0 |
0 |
Pyrophoric Gas |
Gaseous |
2 |
N/A |
N/A |
50
c,i |
N/A |
N/A |
10c,i |
N/A |
N/A |
Liquefied |
2 |
N/A |
N/A |
(4)
c,i |
N/A |
N/A |
(4)
c,i |
N/A |
N/A |
Unstable (reactive) |
4 |
1 |
1c,i |
(1)
c,i |
N/A |
1/4i |
(1/4)i |
N/A |
1/4i |
(1/4)i |
3 |
1 or 2 |
5c,d |
(5)
c,d |
N/A |
1
d |
(1)
d |
N/A |
1
d |
(1)
d |
2 |
2 |
50
c,d |
(50)
c,d |
N/A |
50
d |
(50)
d |
N/A |
10
d |
(10)
d |
1 |
N/A |
NL |
NL |
N/A |
NL |
NL |
N/A |
NL |
NL |
Unstable (reactive) Gas |
Gaseous 4 or 3 |
1 |
N/A |
N/A |
10
c,i |
N/A |
N/A |
2
i |
N/A |
N/A |
Detonable
3 |
2 |
N/A |
N/A |
50
c,d |
N/A |
N/A |
10
d |
N/A |
N/A |
Nondetonable
2 |
3 |
N/A |
N/A |
750
c,d |
N/A |
N/A |
750
d |
N/A |
N/A |
1 |
N/A |
N/A |
N/A |
NL |
N/A |
N/A |
NL |
N/A |
N/A |
Water (reactive) |
3 |
2 |
5
c,d |
(5)
c,d |
N/A |
5
d |
(5)
d |
N/A |
1
d |
(1)
d |
2 |
3 |
50
c,d |
(50)
c,d |
N/A |
50
d |
(50)
d |
N/A |
10
d |
(10)
d |
1 |
N/A |
NL |
NL |
N/A |
NL |
NL |
N/A |
NL |
NL |
Corrosive |
N/A |
5000
d |
500
d |
N/A |
5000d |
500c,d |
N/A |
1000d |
100
d |
UD: Unclassified detonable
For SI units, 1 lb = 0.454 kg; 1 gal = 3.785 L; 1 scf = 0.0283
Nm3. N/A: Not applicable. NL: Not limited. NP: Not permitted.
Note: The hazardous material categories and MAQs that are
shaded in this table are not regulated by Chapter 60 or NFPA 400:
Hazardous Materials Code but are provided here for
informational purposes. See Chapter 2 for the reference code
or standard governing these materials and establishing the MAQs. In accordance
with 1.1.1.2 of NFPA 400, materials having multiple hazards
that fall within the scope of NFPA 400 shall comply with NFPA 400.
a. Table values in parentheses correspond to
the unit name in parentheses at the top of the column. The aggregate quantity
in use and storage is not permitted to exceed the quantity listed for
storage.
b. Measured at NTP or 70EF
(21EC) and 14.7 psia (101.3 kPa).
c. Quantities are permitted to be increased
100% where stored or used in approved cabinets, gas cabinets, exhausted
enclosures, gas rooms explosives magazines, or safety cans, as appropriate for
the material stored, in accordance with this Code. Where
footnote d also applies, the increase for both footnote c. and footnote d. is
permitted to be applied accumulatively.
d. Maximum quantities are permitted to be
increased 100% in buildings equipped throughout with an automatic sprinkler
system in accordance with NFPA 13: Standard for the Installation of
Sprinkler Systems. Where footnote c. also applies, the increase for
both footnote c. and footnote d. is permitted to be applied
accumulatively.
e. The permitted
quantities are not limited in a building equipped throughout with an automatic
sprinkler system in accordance with NFPA 13: Standard for the
Installation of Sprinkler Systems.
f. A maximum quantity of 200 lb (91 kg) of
solid or 20 gal (76 L) of liquid Class 3 oxidizer is permitted where such
materials are necessary for maintenance purposes, operation, or sanitation of
equipment. Storage containers and the manner of storage are required to be
approved.
g. Allowed only where
stored or used in gas rooms or approved cabinets, exhausted gas cabinets or
exhausted enclosures, as specified in this Code. [5000: Table
34.1.3.1]
h. Conversion. Where
quantities are indicated in pounds and when the weight per gallon of the liquid
is not provided to the AHJ, a conversion factor of 10 lb/gal (1.2 kg/L) shall
be used.
i. Permitted only in
buildings equipped throughout with an automatic sprinkler system in accordance
with NFPA 13: Standard for the Installation of Sprinkler
Systems.
j. None allowed
in unsprinklered buildings unless stored or used in gas rooms or in approved
gas cabinets or exhausted enclosures, as specified in this
Code.
k. With
pressure-relief devices for stationary or portable containers vented directly
outdoors or to an exhaust hood. [55: Table 6.3.1.1]
l. Flammable gases in the fuel tanks of
mobile equipment or vehicles are permitted to exceed the MAQ where the
equipment is stored and operated in accordance with this Code.
[400: Table 5.2.1.1.3]
m. The
quantities of alcoholic beverages in retail and wholesale sales occupancies
shall not be limited provided the liquids are packaged in individual containers
not exceeding 1.3 gallons. In retail and wholesale sales occupancies, the
quantities of medicines, foodstuffs or consumer products, and cosmetics
containing not more than 50% by volume of water-miscible liquids with the
remainder of the solutions not being flammable, shall not be limited, provided
that such materials are packaged in individual containers not exceeding 1.3
gallons.
n. Containing not more
than the maximum allowable quantity per control area of Class
IA, IB or IC flammable liquids.
o.
The maximum allowable quantity shall not apply to fuel oil storage complying
with Section 603.3.2 of the International Fire
Code in accordance with the Building Code.
p. For gallons of liquids, divide the amount
in pounds by ten in accordance with Section 5003.1.2 of the
International Fire Code in accordance with the
Building Code.
q.
For storage and display quantities in Group M and storage quantities in Group S
occupancies complying with the Building Code.
r. Densely packed baled cotton that complies
with the packing requirements of ISO 8115: Cotton Bales -- Dimensions
and density shall not be included in this material class in accordance
with the Building Code.
s. The following shall not be included in
determining the maximum allowable quantities in accordance with the
Building Code:
1. Liquid or
gaseous fuel in fuel tanks on vehicles.
2. Liquid or gaseous fuel in fuel tanks on
motorized equipment operated in accordance with the International Fire
Code.
3. Gaseous fuels in
piping systems and fixed appliances regulated by the International Fuel
Gas Code.
4. Liquid fuels
in piping systems and fixed appliances regulated by the International
Mechanical Code.
5.
Alcohol-based hand rubs classified as Class I or II liquids in dispensers that
are installed in accordance with Sections 5705.5 and 5705.5.1 of the
International Fire Code. The location of the alcohol-based
hand rub (ABHR) dispensers shall be provided in the construction
documents.
t. Where
manufactured, generated or used in such a manner that the concentration and
conditions create a fire or explosion hazard based on information prepared in
accordance with the Building Code.
u. For use of control areas,
see the Building Code.
v. Quantities in parenthesis indicate
quantity units in parenthesis at the head of each column.
60.4.2.1.2 through
60.4.2.1.4
Delete
Table 60.4.2.1.2.1 Delete
60.5.1.3.7.1 Replace with the
following:
60.5.1.3.7.1 The person,
firm, or corporation responsible for an unauthorized release shall institute
and complete all actions necessary to remedy the effects of such unauthorized
release, whether sudden or gradual, at no cost to the AHJ, in accordance with
M.G.L. 21E, Massachusetts Oil and Hazardous Material Release Prevention Act.
60.5.1.4.3.2(5) through
60.5.1.4.3.2(9) Add
(5) Identify
Emergency Coordinators who will either be on the premises or on call and
available to respond to an emergency within one hour of an emergency
situation.
(6) Maintain an updated
list containing the names, and the office, home, and/or mobile telephone
number(s) of all designated Emergency Coordinators and the times of their
availability. If for a particular period more than one individual is listed,
the primary Emergency Coordinator shall be identified and others shall be
listed in the order in which they will assume responsibility to fulfill the
requirements of this role.
(7)
Maintain and provide to the AHJ, a facility floor plan, not to scale, showing
the locations of the hazardous material stored, the typical volumes, location
of emergency spill containment equipment (pads, booms,
etc.).
(8) For
those facilities covered by Section 60.8 and having either
Category 3, Category 4 and Category 5 processes, their Emergency Response
Liaison personnel shall communicate to the fire department any concerns and
establish a protocol in conjunction with the AHJ on the shutdown of any of the
process that would pose a risk to the public in the event of loss of any
controls. This protocol shall include a facility liaison to meet with the
Incident Commander upon arrival to ensure a safe shutdown if
necessary.
(9) Notify the AHJ of
any material changes to the Emergency Response Plan, including the name of the
primary Emergency Coordinator, within 14 calendar days of the change.
60.5.1.19.1.1 Replace
with the following:
60.5.1.19.1.1
Underground storage tanks are regulated by
310 CMR
80.00: Underground Storage Tank (UST)
Systems.
60.7 Replace with
the following:
60.7
Performance Alternative. In lieu of complying
with Chapter 60 in its entirety, occupancies containing high hazard Level 1 to
high hazard Level 5 contents shall be permitted to comply with Chapter 10 of
NFPA 400, Hazardous Materials Code, subject to an independent
review in accordance with Section 1.15 and a copy, including
its recommendations, shall be submitted to the Building Official.
60.8 through 60.8.1.1(20)
Add:
60.8
Hazardous Material
Process or Processing.
60.8.1
General. This section shall apply to both new and existing
facilities that process hazardous materials.
60.8.1.1 This section shall not apply to the
following:
(1) Motor vehicle service stations
regulated in accordance with Chapter 30;
(2) Construction and maintenance projects
regulated in accordance with this Code;
(3) Products that are designed pre-mixed in
accordance with the manufacturer's instructions or products that are labeled
and packaged for sale to the consumer at retail;
(4) The activities of healthcare professional
offices or facilities under the supervision of a licensed medical doctor,
dentist, or veterinarian;
(5)
Retail facilities such as pharmacies, hardware stores, department stores, or
restaurants regulated by and in accordance with the provisions of this
Code;
(6)
Refrigeration systems which employ a refrigerant other than ammonia or
LPG;
(7) The processing or
treatment of potable water and sanitary wastewater;
(8) Wastewater treatment operations that are
operated by Grades 1I, 1M, 2I, and 2M operators as classified according to
257 CMR
2.00: Certification of Operators of Wastewater
Treatment Facilities;
(9)
The consumption of fuels solely for the purpose of the operation of equipment,
such as generators, torches, and consumptive use boilers regulated in
accordance with the provisions of this Code;
(10) The storage of hazardous materials in
atmospheric vessels, if they are maintained below the stored material's normal
boiling point without benefit of chilling, refrigeration, or heat;
(11) The processing of hazardous materials
and their byproducts which has a hazard ratings of two or less, according to
criteria of NFPA 704;
(12)
Hazardous waste activities regulated and in compliance with the provisions of
310 CMR
30.00: Hazardous Waste;
(13) Biological and medical activities
regulated by the Department of Public Health;
(14) Handling and use of liquid nitrogen
cooling systems at atmospheric pressure;
(15) The handling and repackaging of products
regulated in accordance with the provisions of this
Code;
(16) Use of
inert gas;
(17) Swimming pools
regulated by Department of Public Health under
105 CMR
435.000: Minimum Standards for Swimming Pools
(State Sanitary Code: Chapter V);
(18) Air pollution control devices that are a
component of a process regulated by Massachusetts Department of Environmental
Protection under
310 CMR
7.00: Air Pollution
Control;
(19) The
production and handling of explosives and fireworks regulated in accordance
with Chapter 65;
(20) The
equipment, process, handling, storage, or use of compounds, liquids,
pesticides, fertilizers, or soil treatments regulated in accordance with the
provisions of this Code or as regulated by 248 CMR:
Board of State Examiners of Plumbers and Gas
Fitters.
60.8.1.1.1
Add:
60.8.1.1.1
Permits. Permits where required, shall comply with Section
1.12.
60.8.2 Add:
60.8.2
Terms. As used in Chapter
60, the enclosed terms shall have the following meaning assigned to them.
60.8.2.1 through 60.8.2.3(6)
Add:
60.8.2.1
Capacity. The nominal capacity of the vessel as specified by the
manufacturer.
60.8.2.2
Category 3 Hazard Evaluation. A written evaluation performed or
procedure conducted to identify hazards, including adjacent vessels that
contain hazardous materials, and determine the required preventive, protective,
and safety control measures in conformance with recognized and generally
accepted good engineering and safe work practices associated with a particular
process or condition and the facility wherein such process or condition is
taking place.
60.8.2.3
Category 4 Limited Safety Program. A documented evaluation,
policy, or required procedure to ensure compliance with all of the following:
(1) Process information including, but not
limited to, SDS for the chemicals and products being processed, process
chemistry, piping and instrumentation diagram, safety relief design, process
control safety alarms and interlocks;
(2) Facility suitability including, but not
limited to, the Building Code compliance, electrical hazard
(Check article 500) classification, ventilation design, fire alarm and fire
protection, spill containment and control;
(3) A process hazard safety analysis
including but not limited to, effects in the event of failure, suitable
administrative and engineering controls to minimize failure and to control
unanticipated releases, and emergency responses to safeguard life and
property;
(4) Written procedures,
including routine operating and maintenance, as well as precautionary,
shut-down and emergency response measures;
(5) A written training program for operating
and maintenance personnel and outside contractors whose work or activity may
affect process safety;
(6) A
written records management protocol which tracks any changes, including but not
limited to changes to chemicals, equipment, operating procedures training
program. Such records shall include the date of such change and the name of the
manager responsible for such change; and an internal review at a maximum every
three years.
60.8.2.4
Competent Professional. A person who, based upon education,
training, skill, experience or professional licensure or a combination thereof,
has a specialized knowledge beyond that of an average person, about risk
assessment, process hazard analysis, and/or process safety management
principles, for the process or processes being evaluated.
60.8.2.5
Facility. A structure,
building or complex of buildings or structures where hazardous materials are
processed.
60.8.2.6
Facility
Category. Since multiple hazardous material processes may exist within a
facility, each facility shall identify all the categories of processes present
and verify compliance with all the categories for each process identified at
the facility.
60.8.2.6.1 For purposes of
determining facility category classification under Section
60.8, the highest level of actual or possible hazardous process
category shall determine the appropriate Facility Category.
60.8.2.7
High-hazard Group
H. High-hazard Group H occupancy includes, among others, the use of a
building or structure, or a portion thereof that involves the manufacturing,
processing, generation or storage of materials that constitute a physical or
health hazard in quantities in excess of those allowed in control areas
complying with the Building Code.
60.8.2.8
Incident. An unplanned
event arising from a hazardous material process resulting in a fire, explosion,
reportable release, or injury.
60.8.2.9
Mixture. A combination
of materials in a vessel. The mixture shall be considered a different material
from those before being added to the vessel, regardless of whether a reaction
or change of state occurred in the vessel, and regardless of whether the
mixture is homogeneous or heterogeneous. Material hazards of the mixture shall
be classified based on the hazards of the mixture as a whole, in accordance
with nationally recognized reference standards, by an approved qualified
organization, individual, or Safety Data Sheets (SDS), or by other approved
methods.
60.8.2.10
Person. An individual, firm, corporation, company, partnership,
association, including any officer, trustee, assignee, receiver, personal
representative, designee, manager or employee thereof.
60.8.2.11
Vessel. The container
in which partial or the actual process takes place. Examples of vessels are
beakers, pails, tanks, reactor kettles, pipe reactors, and drums. The size of a
vessel is its capacity.
60.8.3 through 60.8.6.1
Add:
60.8.3
Hazardous Process
Category. Hazardous Material processes shall be defined per
60.8.3.1 through
60.8.3.5.
60.8.3.1
Category 1 Process. A
process which involves or produces a Hazardous Material which occurs in a
vessel with a capacity that is less than or equal to 2.5 gallons.
60.8.3.2
Category 2 Process. A
process which involves or produces a Hazardous Material which occurs in a
vessel with capacity that is greater than 2.5 gallons but less than or equal to
60 gallons.
60.8.3.3
Category
3 Process. A process which involves or produces a Hazardous Material
which occurs in a vessel that is greater than 60 gallons but is less than or
equal to 300 gallons that contains a hazardous material that is processed or a
process area that is classified as being a H Occupancy as defined by the
Building Code.
60.8.3.4
Category 4 Process. A
process which involves or produces a Hazardous Material which occurs in a
vessel with a capacity that is greater than 300 gallons and is not considered a
Category 5 Process.
60.8.3.5
Category 5 Process. A process which involves or produces Hazardous
Material which occurs in a vessel with a capacity that is equal or in excess of
threshold quantities stated in
29 CFR
1910.119 or 40 CFR Part 68 and regulated by
such standard.
60.8.3.6
Multiple Processes. Since multiple hazardous material processes
may exist within a facility, each facility shall identify all the categories of
processes present and verify compliance with all the categories for each
process identified at the facility.
60.8.3.6.1
For purposes of determining category classification under this
Code the actual or possible Hazardous Processing activity
shall determine the appropriate Category.
60.8.4 Add:
60.8.4
Permits. Permits, where
required, shall comply with
Sections 1.12 and
60.8.4.1 through 60.8.4.4
60.8.4.1 No person shall engage in the
Process or Processing of any Hazardous Material at any Facility identified in
Section 60.8 as Category 2 through Category 5 unless said
Facility is in compliance with the permit requirements of the provisions of
this
Code.
60.8.4.1.1 A
permit holder shall apply for the renewal of said permit on an annual
basis.
60.8.4.1.2 The application
shall contain such information and be in a form as prescribed by the State Fire
Marshal.
60.8.4.2 An
applicant for the permit required by Section 1.12 shall submit
an application for Permit to Process Hazardous Material to the Head of the Fire
Department on a form prescribed by the State Fire Marshal.
60.8.4.3 As provided in M.G.L. c. 148, §
10A the AHJ may deny or withhold the issuance of a permit however, such denial
or withholding shall be in writing. Said notice of denial shall contain
specifications of the alleged violation or deficiency together with their
interpretation of Section 60.8. The AHJ shall be permitted to
require technical assistance in accordance with Section 1.15
to evaluate the adequacy of Category 3 or Category 4 process safety conditions,
programs, procedures, and practices undertaken at the facility but only after a
notice of denial has been properly served upon the person making
application.
60.8.4.4 Any person
who has been permitted to engage in the Process or Processing of Hazardous
Material at any Facility or any person creating a new process facility, shall,
prior to engaging in any new or modified hazardous material process activity
which results in a change to the highest process category authorized by the
current permit, notify the Head of the Fire Department of such new change or
modification and submit a new application to appropriately modify the existing
permit.
60.8.5
Add:
60.8.5
Compliance
Requirements.
60.8.5.1 Add:
60.8.5.1 Facilities operating hazardous
material processes as defined by this
Code shall maintain, for
each process in their facility, the following required documents and procedures
at their facility for periodic inspection and review by the Head of the Fire
Department to remain in compliance with this Section.
60.8.5.1.1
Category 1 Process
Documents. Provide the following documentation for Category 1 processes.
(1) Documentation that adequately
demonstrates that the facility maintains and implements a policy in compliance
with 29 CFR
1910.1200 and
29 CFR
1910.1450 as applicable, and (2)
Documentation that adequately demonstrates that the facility maintains and
implements a policy in compliance with Chapter 66, Flammable and
Combustible Liquids, Chapter 67, Flammable Solids, as
applicable, and
(3) Demonstrate
compliance with Sections 60.1.5.1 Emergency Action Plan and
Sections 60.5.1.4.3.2 (5) through (9).
(4) Comply with the permitting requirements
of Sections 1.12 and 60.8.4.
60.8.5.1.2
Category 2
Process Documents. Provide the following documentation for Category 2
processes.
(1) Provide documentation that
adequately demonstrates that the facility complies with the requirements for a
Category 1 Process in accordance with Section
60.8.5.1.1.
60.8.5.1.3
Category 3 Process
Documentation and Analysis. Provide the following documentation and
evaluations for Category 3 processes.
(1)
Provide documentation that adequately demonstrates that the facility complies
with the requirements for a Category 2 Process in accordance with
Section 60.8.5.1.2; and
(2) Complete a Category 3 Hazard Evaluation
for each Category 3 process; and
(3) Ensures a Hazard Evaluation policy is in
place and has been completed prior to conducting such process or activity
modification thereto; and
(4)
Implement appropriate process safety controls to mitigate the hazards
associated with normal and abnormal operating conditions as identified in the
Category 3 Hazard Evaluation; and
(5) Maintain Category 3 Hazard Evaluation
documents and records for review by the Head of the Fire Department or Marshal
for a minimum of two years following issuance of a permit.
60.8.5.1.4
Category 4 Process
Documentation and Analysis. Provide the following documentation and
evaluations for Category 4 processes.
(1)
Provide documentation that adequately demonstrates that the facility complies
with the requirements for a Category 3 Process in accordance with
Section 60.8.5.1.3; and
(2) Complete a Category 4 Limited Process
Safety Program for each Category 4 Process.
(3) Ensure a Category 4 Limited Process
Safety Program policy is in place and has been completed prior to each process
or being modified.
(4) Implement
appropriate process safety controls to mitigate the hazards associated with
normal and abnormal operating conditions as identified in the Category 4
Process Limited Safety Program; and
(5) Maintain Category 4 Limited Safety
Program documents and records for review by the Head of the Fire Department or
Marshal for a minimum of two years following issuance of a permit.
60.8.5.1.5
Category 5
Process Documentation and Analysis. Provide the following documentation
and evaluation for Category 5 processes.
(1)
Provide documentation that adequately demonstrates that the facility complies
with the requirements for Category 4 process in accordance with Section
60.8.5.1.4; and
(2)
Implement and self-certify compliance with
29 CFR
1910.119
Process Safety Management of
Highly Hazardous Chemicals program or with 40 CFR Part 60
Chemical Accident Prevention Provisions.
(3) Maintain Hazard Evaluation documents and
records for review by the Head of the Fire Department or Marshal for a minimum
of two years following issuance of a permit.
60.8.6 Add:
60.8.6
Post-incident Analysis.
60.8.6.1 Post-incident analysis shall be
applicable to Category 3 and Category 4 processes. For a Category 5 Process, a
copy of the report submitted in accordance with the OSHA or EPA Risk Management
Standard, shall be considered acceptable.
60.8.6.1.1 In the event of an incident
involving a process in which there is fire department, EMS response, or a
notification of unauthorized release, a written post incident analysis must be
initiated within 48 hours. Upon completion of the analysis, the AHJ shall be
given a duplicate copy of the analysis.
60.8.6.1.2 A completed post-incident written
analysis report shall be completed within 45 days, unless an extension is
provided by the AHJ for just reason.
60.8.6.1.3 The post-incident analysis report
shall provide the following information:
(1) A
summary of the cause of the incident and contributing factors;
(2) Recommendations to prevent a future
recurrence;
(3) A summary of the
dates of implementation of the post-incident analysis recommendations and
corrective actions;
(4) A
reassessment and confirmation of the category under which the facility is
operating or application for a new permit as part of the report.
60.8.7
Add
60.8.7
Trade
Secrets. A facility owner or operator subject to this
Code and required to submit to the AHJ a permit application
and/or supporting documents may claim information as a trade secret as provided
in this Section.
60.8.7.1 A facility
owner/operator shall be permitted to withhold the name of a specific hazardous
material when notifying the fire department under Section 60.8
if that chemical is claimed as a trade secret or confidential business
information.
60.8.7.2 If the
hazardous material is claimed as a trade secret:
(1) The generic class or category that is
structurally descriptive of the chemical must be provided on the permit
application as a matter of public record;
(2) The Safety Data Sheet (SDS) for the
hazardous substance shall be available for review on-site by representatives of
the Fire Department or the State Fire Marshal.
60.8.7.3 A facility owner or operator shall
be permitted to claim information, required under this
Code,
is treated as confidential and not as a matter of public record if:
(1) The information has not been disclosed to
anyone else, other than employees of the facility or the AHJ, an officer or
employee of the United States or a state or local government, or anyone who is
bound by a confidentiality agreement;
(2) The facility has taken reasonable
measures to protect the confidentiality of such information and intends to
continue to take such measures;
(3)
The information is not required to be disclosed, or otherwise made available to
the public under any other federal or state law; and
(4) Disclosure of the information may cause
substantial harm to the competitive position of the facility.
60.8.7.4 All documentation and
records claimed as trade secret or confidential information, including but not
limited to the "Permit to Process Hazardous Material Application", "hazard
evaluation documentation", "process safety program documentation", shall be
clearly marked as "Trade Secret", "Confidential", or other words of similar
meaning.
Chapter
61
Aerosol Products
(No amendments)
Chapter
63
Compressed Gases and Cryogenic Fluids
(No amendments)
Chapter
64
Corrosive Solids and Liquids
(No amendments)
Chapter
65
Explosives, Fireworks, Model Rocketry,
Cannons, and Mortars
Title of Chapter 65. Modify by adding Cannons, and
Mortars to the end of the title Explosives, Fireworks, Model Rocketry,
Cannons, and Mortars.
65.1.3
Add:
65.1.3
Certificates. Certificates, where required, shall comply with
Section 1.13.
65.1.4 Add:
65.1.4
Terms. As used in Chapter
65 the enclosed terms shall have the following meaning assigned to them.
65.1.4.1
Barrier. As used in
Chapter 65, is an object or structure, such as, but not limited to, a fence
with warning sign, or tape, that prohibits or restricts passage or
travel.
65.1.4.2
Blasting
Mat. A mat of woven steel wire, rope, scrap tires, or other suitable
material, earth fill or construction to cover blast holes, for the purpose of
preventing flyrock.
65.1.4.3
Blasting Operation. Any person engaged in the conduct of blasting
under the terms of a contract or otherwise.
65.1.4.4
Maximum charge per
delay. The maximum weight of explosives detonated per eight (8)
milliseconds or less when using pyrotechnic initiation (non-electric and
electric) or the maximum weight of explosives detonated per millisecond when
using non-pyrotechnic electronic initiation.
65.1.4.5
Natural Barrier. A
restrictive terrain, or body of water, that in itself, will assist in
restricting the display area at a fireworks show without the need for an
additional barrier to be erected. Natural barriers must be approved by the
State Fire Marshal in advance of a show.
65.1.4.6
Physical Barrier. A
structure of substantial strength that is uniformly supported and provides an
uninterrupted barrier both vertically and horizontally that consists of a
height no less than 40 inches including, but not limited to, snow fencing or
its equivalent.
65.1.4.7
Special Industrial Explosives Device. Shaped materials, sheet
forms, and various other extrusions, pellets, and packages of high explosives
used for high-energy-rate forming, expanding, and shaping in metal fabrication
and for dismemberments and reduction of scrap metal.
65.1.4.7.1 The high explosives used include
dynamite, trinitrotoluene (TNT), PETN, and cyclotrimethylenetrinitramine
(RDX).
65.1.4.7.2 Special
industrial explosive material shall also include explosive materials used
exclusively for research and development including, but not limited to,
explosive detection and explosive safety.
65.2.1 Replace with the following:
65.2.1 The construction, handling, and use of
fireworks intended solely for outdoor display as well as the general conduct
and operation of the display, shall comply with the requirements of NFPA 1123,
Code for Fireworks Display, including its annexes A, D and
E.
65.2.2 Replace with the
following:
65.2.2 All storage of
display fireworks shall comply with NFPA 1124, Code for the
Manufacture, Transportation, Storage, and Retail Sales of Fireworks and
Pyrotechnic Articles.
65.2.4 Add:
65.2.4
Delivery of Fireworks.
65.2.4.1 Delivery of fireworks shall be made
only to authorized persons who are in possession of a valid Certificate of
Competency (Fireworks Display) and a Permit to Display Fireworks (Supervised
Display of Fireworks).
65.2.4.2 As
soon as the fireworks have been delivered to a display site, they shall not be
left unattended, and they shall be kept dry.
65.2.4.3 Upon delivery of the fireworks to
the display site, members of the public, the audience, spectators, and other
persons not otherwise authorized by the AHJ, shall be kept at a distance not
less than those specified in NFPA 1123, Table 5.1.3.1
Distances for
Outdoor Aerial Shell Display Sites: Minimum Separation Distances from Mortars
to Spectators for Land or Water Displays.
65.2.4.3.1 Where it is impractical to locate
the delivery vehicle within the perimeter of the display site the vehicle shall
be parked and secured.
65.2.4.3.1.1 The
minimum secured radius from any point of transfer of fireworks from the vehicle
to the display site shall be 150 ft.
65.2.4.3.1.2 Audience members, spectators and
the general public shall not be allowed within this area.
65.2.5 Add:
65.2.5
Requirements for Display
Fireworks.
65.2.5.1 The audience at a
supervised display of fireworks shall be restrained behind a physical or
natural barrier.
65.2.5.1.1 Such barrier shall
clearly define the restricted display site.
65.2.5.1.2 This restricted area shall be
defined based on the minimum separation distances specified by NFPA 1123, Table
5.1.3.1 Distances for Outdoor Aerial Shell Display Sites: Minimum
Separation Distances from Mortars to Spectators for Land or Water
Displays.
65.2.5.2 A portable anemometer or similar
device for measuring wind velocity shall be available for use at all times by
the operator.
65.2.5.2.1 Any supervised
display of fireworks shall be stopped immediately in the event that upper level
wind conditions cause the fall out area to change and pose a threat to public
safety or property.
65.2.5.2.2 A
test shot shall be provided to check for high level winds at the request of the
AHJ.
65.2.5.2.3 The term high winds
as used in this section are when the wind velocity exceeds 20 miles per hour at
ground level.
65.2.6 Add:
65.2.6
Nighttime Fireworks.
Where fireworks are displayed at night, a thorough search of the display site
shall be made by the competent operator immediately after the display and again
at first light the following morning to ensure recovery of all unexploded
shells.
65.2.6.1 If the competent operator is
unavailable due to unforeseen circumstances such as illness or injury, a
substitute competent operator, upon approval of the AHJ, shall be permitted
conduct the aforementioned searches. A thorough search shall include, but not
be limited to:
(1) A Search as described
above;
(2) Completed form
prescribed by the State Fire Marshal that indicates the start and stop time of
the search; and
(3) Acknowledgement
by the operator and Head of the Fire Department or his or her designee that
they have completed the requirements of this section.
65.2.7 Add:
65.2.7
Fire Department
Coordination. The sponsor shall be responsible for the detailing of one
or more members of the fire department as may be required by the Head of the
Fire Department.
65.2.7.1 The fire department
detail shall be on duty from the time the fireworks are delivered to the site
until the termination of the display and removal of all fireworks and debris
from the site and in compliance with Section 65.2.6.
65.2.8 Add:
65.2.8
Mortar and Shells.
65.2.8.1 No fireworks display shall include
mortars or shells in excess of 12 inches in diameter, unless the certificate
holder shall have obtained prior written approval from the State Fire
Marshal.
65.2.8.2 Add:
65.2.8.2 Multiple shot mortar devices using
mortars less than three inches in diameter including, but not limited to cakes,
and repeaters, shall be buried F of their length in a trench, mortar trough, or
sturdy drum filled with clean sand or substantial wooden boxes.
65.2.8.2.1 The Head of the Fire Department
shall be permitted to allow for an equivalent alternative, such as sandbags or
racks constructed with material similar to mortar rack construction, provided
the same degree of protection is provided.
65.2.8.3 The use of aluminum mortars is
prohibited.
65.2.8.4 All supervised
displays of fireworks shall be electrically fired. Mortars shall not be
reloaded.
65.2.8.5 Add:
65.2.8.5
Electrical Firing
Units.
65.2.8.5.1* All electrical
firing units shall be included on an approved list from the State Fire
Marshal's Office, or display be inspected by the State Fire Marshal and a decal
issued by the State Fire Marshal for a term determined by the State Fire
Marshal shall be displayed on the panel.
A65.2.8.5.1 Electronic firing panels that have been
approved by the State Fire Marshal are published on a list maintained by the
State Fire Marshal's office.
65.2.8.5.2 The panel shall contain a key
operated safety switch which controls the overall power and functionality of
the firing unit.
65.2.8.5.3 The
unit shall be operated in accordance with the manufacturer's
instructions.
65.2.8.5.4 All
electrical firing units, and any associated devices, wiring, or connections
shall be adequately maintained.
65.2.8.6 Add:
65.2.8.6
Racks.
A65.2.8.6 Guidance for the construction of racks is
included in the appendix of NFPA 1123
65.2.8.6.1 Parallel racks or rows of racks
shall be separated by a minimum distance not less than twice the inside
diameter of the largest mortar in an adjacent rack.
65.2.8.6.2 Dense Pack Modular Racks, approved
for use on licensed trailers and trailer launched portable barges shall be
permitted.
65.2.8.6.3 Dense Pack
Modular Racks shall be made of aluminum or other suitable metal framework
system and shall be subject to restrictions and inspections as established by
the State Fire Marshal.
65.2.8.6.4
All mortars approved for use in dense pack modular racks must be secured to the
framework system.
65.2.8.6.4.1 Spacing between
mortars in a rack shall be at least F the diameter of the adjacent
mortar.
65.2.8.6.5 Only
single break shells shall be fired.
65.2.8.6.6 Dense Pack Modular Racks shall be
permitted to be placed on firm ground, bridge, barge or secured to an approved
trailer or barge licensed for the use of firing display shells utilizing dense
pack modular racks.
65.2.8.6.7
Dense Pack Modular Racks placed on the ground or on a barge, not part of an
approved trailer or barge system shall be placed in rows of racks separated by
twice the diameter of the largest mortar within the rack.
65.2.8.6.8 Parallel rows of racks shall be
separated by a minimum distance not less than 24
inches.
65.3.4
Add:
65.3.4 The use of pyrotechnic
special effects indoors is prohibited in nightclubs, discotheques, dance halls,
bars, or similar occupancies (defined as A-2 or A-3 by the Building
Code).
65.3.5
Add:
65.3.5 The use of pyrotechnic
special effects indoor in entertainment venues (defined as A-3 by the
Building Code) and theatres (defined as A-1 by the
Building Code) shall be permitted provided the facility is
protected throughout with automatic sprinklers.
65.3.6 Add:
65.3.6 Approval of the use of pyrotechnic
special effects shall be subject to such terms and conditions as the Head of
the Fire Department may require.
65.3.7 Add:
65.3.7 No bombs, salutes, roman candles,
skyrockets, firecrackers, torpedoes, or similar pyrotechnic shall be used
before a proximate audience unless specifically approved in writing by the
State Fire Marshal.
65.3.8
Add:
65.3.8 The theatre,
auditorium, or similar facility shall certify that the proscenium protection is
in compliance with the Building Code.
65.3.9 Add:
65.3.9 Electrical firing panels shall comply
with
Sections 65.2.12 and
65.2.13. A
performer shall not be required to comply with
Section
65.2.12, if firing a single special effect.
65.4.1.1 Add:
65.4.1.1 The use of flame effects indoors is
prohibited in nightclubs, discotheques, dance halls, bars, or similar
occupancies. The use of flame effects indoors, in entertainment venues (defined
as A-3 by the Building Code) and theatres (defined as A-1 by
the Building Code), shall be permitted provided the facility
is protected throughout with automatic sprinklers.
65.5.1 Replace with the following:
65.5.1 The manufacture, transportation, or
storage of fireworks shall comply with NFPA 1124 Chapters 1 through 5 and
Chapter 8.
65.5.3 Add:
65.5.3 No person shall manufacture fireworks
except in accordance with this Code. The manufacture of any fireworks, as
defined in this Code, shall be prohibited unless it is authorized by federal
license or permit, and a license issued by the local licensing authority and a
permit issued by the State Fire Marshal.
65.5.3 Add:
65.5.3 No person shall manufacture fireworks
except in accordance with this Code. The manufacture of any
fireworks, as defined in this Code, shall be prohibited unless
it is authorized by federal license or permit, and a license issued by the
local licensing authority and a permit issued by the State Fire
Marshal.
65.6.1 Add:
65.6.1
Permit. Permits, where
required, shall comply with Section 1.12.
65.7.2 Delete.
65.9.1 Replace with the following:
65.9.1 The manufacture, transportation,
storage, sale, and use of explosive materials shall comply with NFPA 495:
Explosive Materials Code, including appendix A, C, D and E,
and NFPA 498,
Standard for Safe Havens and Interchange Lots for
Vehicles Transporting Explosives.
65.9.1.1 Add:
65.9.1.1 All magazines containing explosive
materials shall be opened and inspected at maximum intervals of seven days to
determine whether there has been unauthorized or attempted entry into the
magazines or whether there has been unauthorized removal of the magazines or
their contents.
65.9.1.2
Add:
65.9.1.2
Terms.
As used in Chapter 65, additional terms are defined in
65.1.4.
65.9.3 Add:
65.9.3 Reserved
65.9.4 Add:
65.9.4
Storage of Explosives on
Water65.9.4.1 No person shall store
any explosives on the waters of the Commonwealth unless a permit for such
storage has been secured from the State Fire Marshal, and unless the explosives
are stored in accordance with the following requirements:
(1) Such explosives shall be stored in a
magazine located on a boat or vessel used exclusively for the purpose, and such
boat or vessel shall be securely moored or anchored according to the direction
of the harbor master. The storage magazines shall be subject to the
requirements of Chapter 65;
(2) No
detonators shall be stored or transported on a boat or vessel on which any
explosives are kept or stored, except in accordance with the applicable
provisions of Chapter 65;
(3) No
explosives shall be delivered or removed from a boat or vessel during foggy
weather;
(4) In the loading or
unloading of any explosive, care shall be taken in the handling of same and it
shall be so placed or stowed as to prevent displacement during
transit;
(5) No explosives shall be
carried or transported on the waters of the Commonwealth on any vessel which is
carrying passengers;
(6) Any vessel
containing explosives in transit on any of the waters of the Commonwealth shall
display on a suitable staff an international Code Flag B (a red flag) readily
discernible from a distance of not less than 1,000 feet by day and which shall
be properly illuminated at night;
(7) No smoking shall be allowed on any vessel
containing explosives;
(8) All such
boats and vessels shall display the word "EXPLOSIVES" in a conspicuous manner
so that it shall be permitted to be seen by day from all sides at a distance of
not less than 200 feet, and shall be properly illuminated at night.
65.9.5 Add:
65.9.5
Magazines. The
requirements of
Section 65.9 shall be in addition to
applicable U.S. Department of Transportation (U.S. Coast Guard) Regulations,
33 CFR
126, and
46 CFR
194.
65.9.5.1
Magazine Alteration. No
alteration changing the constructed storage capacity of a magazine shall be
made without notifying the State Fire Marshal and the Head of the Fire
Department in writing and then receiving written acknowledgment of receipt of
the notification from the State Fire Marshal and the Head of the Fire
Department.
65.9.5.2
Equivalent Alternate Construction Standards. Alternate storage
facilities for explosive materials shall be permitted to be approved by the
State Fire Marshal when it is shown that such alternate facilities are or will
be constructed in a manner substantially equivalent to the standards of
construction contained in Chapter 65 and such construction has been approved in
accordance with 27 CFR
201(b).
65.9.5.3 Magazines shall be sequentially
numbered by a minimum of two inch block numbers plainly visible on the outside.
65.9.5.3.1 This number shall correspond to
those drawn on a storage facility site diagram, drawn to scale, clearly
indicating the separation distances between magazines, inhabited buildings,
railways, highways, and other magazines.
65.9.5.4 The owner shall plainly post on the
interior side of the magazine door the current Table of Distance storage
capacity.
1. The hazard analysis shall be
prepared and certified by a Massachusetts Registered Professional
Engineer.
2. The analysis shall
demonstrate that the change in liquid classification does not constitute an
increase in fire or explosion hazards or risks to life and property.
65.9.6 Add:
65.9.6
Operational Procedure Manual for
Storage of Explosives. A Magazine Facility Operational Procedure Manual
shall be maintained on the storage facility which shall include the following:
(1) facility emergency policy and
procedures;
(2) administrative and
emergency notification procedures;
(3) scaled plot plan of the storage facility
site;
(4) showing magazines,
inhabited buildings railways and highways within 2,000 feet of the closest
magazine, Explosive Material Manufacturers Safety Data Sheets (SDS) for all
explosive materials and SARA Title III Hazardous Materials on the
site.
65.9.6.1 This manual shall be
kept current and a copy provided upon request to the Head of the Fire
Department and the State Fire Marshal or their designees.
65.9.6.2 A magazine facility containing
10,000 or less pounds of explosive materials shall be exempt from this
requirement.
65.9.6.3 Delivery of
explosives shall only be made to persons displaying proper permits and licenses
and shall be delivered into magazines or temporary storage or handling areas as
authorized by this Code.
65.9.6.4 No person shall deliver explosive
materials to any magazine, building or structure that is not permitted by the
State Fire Marshal.
65.9.6.5 Any
person who delivers explosive materials shall keep a record of the delivery
transaction.
65.9.6.5.1 The record shall
contain the permit number assigned by the State Fire Marshal to the magazine,
building or structure where said materials are to be stored.
65.9.7 Add:
65.9.7 Explosives shall be transported in
accordance with 29 CFR
1926.903.
65.9.8 through 65.9.8.4.3
Add:
65.9.8
Blast
Analysis. Before conducting a blast, the blaster shall conduct a blast
analysis of the overall factors affecting the blasting operations. This
analysis shall consider;
(1) adjacent area
structure(s), building(s), building foundations, utilities, including gas and
water supply lines, septic systems and swimming pools,
(2) area geology within 250 ft. (76.2 m) of
the center of the blast site,
(3)
the identification of commercial equipment such as computers, electron
microscopes, laser equipment, relays etc., which are sensitive
to vibrations,
(4) other
underground objects that might be damaged by the effects of a blast.
65.9.8.1 A blast analysis shall be compared
to the blast design plan to establish a sound relationship between the blast
design and the effects of blasting upon the neighborhood within the blast area.
65.9.8.1.1 The blast analysis shall contain a
discussion of plan factors to be used which protect the public and meet the
applicable airblast, flyrock, and ground vibration standards.
65.9.8.2 The area of the blast
analysis shall be within 250 ft. (76.2 m) from the closest borehole.
65.9.8.3
Blast Plan. When
blasting is done in a congested area or within 250 ft. (76.2 m) of a building,
structure, railway, or highway, or any other installation that may be affected,
precautions shall be taken by the blaster in the design of the blast plan to
prevent damage and to minimize adverse effects including ground vibrations, air
overpressure and flyrock.
65.9.8.3.1 Such
precautions shall include but not be limited to, review of each shot variable
or dimension to ensure a blast design plan which establishes sound
relationships between current industry standards and the allowable limits of
the effects of blasting.
65.9.8.3.2
A blast design plan shall describe as a minimum, the amount of material to be
removed, benches and lifts, sketches of proposed drill patterns, spacings, free
face, borehole size, depth, and angle, stemming, decking, weight of explosive
material per delay, delay periods, initiation techniques, the amount of
explosive material to be used, critical dimensions, location and descriptions
of building(s) and structure(s) to be protected, their number, and the
placement of seismographs.
65.9.8.3.3 All shots shall be designed using
the most current industry standards, to prevent excessive air overpressure,
ground vibration, and flyrock.
65.9.8.4
Blasting Precautions.
Blasting mats shall be required if the material to be blasted lies within 100
feet of a highway, an inhabited building or structure not under the control of
the project.
65.9.8.4.1 A blaster authorized
to prepare explosive charges or to conduct blasting operations shall use every
reasonable precaution, including but not limited to warning signals, flags,
barricades, or other equally effective means to ensure the safety of the
general public and workers.
65.9.8.4.1.1 A
code of blasting signals shall be posted on one or more conspicuous places at
the operation.
65.9.8.4.1.2 All
employees shall be required to familiarize themselves with the blasting signal
code. The code shall be:
(1) WARNING SIGNAL:
Three long blasts five minutes prior to blast signal.
(2) BLAST SIGNAL: Two blasts one minute prior
to the shot.
(3) ALL CLEAR SIGNAL:
A prolonged blast following the inspection of the blast area.
65.9.8.4.2 Blast signals
shall be clearly audible for a distance of 250 ft. (76.2 m) of the blast
site.
65.9.8.4.3 No person shall
fire a blast in any blasting operation on Sunday or between the hours of sunset
and sunrise unless otherwise authorized in writing by the State Fire Marshal or
the Head of the Fire Department, but in any case the authority of the State
Fire Marshal shall prevail.
65.9.9
Reserved
65.9.10 Add:
65.9.10 No blast shall be fired without a
positive signal from the blaster-in-charge and only the blaster-in-charge shall
fire the blast.
65.9.11
Reserved
65.9.12 Add:
65.9.12 Whenever quarry blasting is conducted
within 500 ft. (152.4 m) of building(s) used for human habitation a series of
durable warning signs shall be erected along the entire perimeter of any rock
face more than six feet high.
65.9.12.1 They
shall be spaced not more than 75 ft. (22.86 m) apart and set back a reasonable
distance from the face.
65.9.12.2
Each sign shall contain the words "WARNING BLASTING AREA DANGER" in letters at
least two inches in height. (See St. 2014, c. 149, § 7:
An Act Relative to Natural Gas Leaks.)
65.9.13 Add:
65.9.13
Alternative Allowable Vibration
Levels. Alternative limits of the effect of blasting shall permitted to
be adopted for quarry operations located adjacent to inner city areas as a
local municipal regulation adopted in accordance with M.G.L. c. 148, §
9.
65.9.14 through
65.9.14.4.5 Add:
65.9.14
Blaster's Log.
65.9.14.1 A blaster who performs blasting
operations shall maintain a blaster's log on a form approved by the State Fire
Marshal recording each blast.
65.9.14.1.1 The
blaster's log shall be completed within 6 hours of a blast and retained for a
minimum of three years from the date of the blast.
65.9.14.1.2 Blasters' logs shall be made
readily available to the State Fire Marshal, the Head of the Fire Department or
their designees.
65.9.14.1.3 The
blaster's log shall contain:
(1) Name,
signature, and Certificate of Competency Number of the blaster in
charge;
(2) Blast location,
address, city, description;
(2)
Date and time of blast;
(4) Type of
material blasted;
(5) Distance, in
feet, to the nearest inhabited building or structure, neither owned or leased
by holder or holder client of the Explosives User Certificate;
(6) Scaled distance or alternative option
used to determine blast design;
(7)
Type of matting or cover over blast if applicable;
(8) Weather conditions, including
temperature, cloud cover, and wind direction;
(9) Blast plan and sketch showing blast hole
diameter, delay, delay pattern and types of detonators, spacing, depth of blast
hole, hole pattern, and number of holes;
(10) Explosive material type, size, total
weights of each explosive by hole;
(11) Type of initiation system (methods of
firing and type of circuit);
(12)
Feet of over burden, depth, and type of stemming;
(13) Maximum charge per delay;
(14) The seismograph(s) location(s),
including distance and direction from the seismograph to the closest borehole,
and from the seismograph to the closest structure;
(15) Seismograph readings, including peak
particle velocity, frequency, and airblast;
(16) Type of seismograph, instrument make,
model serial number, calibration date, and sensitivity settings;
(17) Name of person taking the seismograph
reading. The name and firm analyzing the seismograph record if applicable;
and
(18) Complaints or comments
following the blast.
65.9.14.2 Blasts that exceed the maximum
allowable peak particle velocity frequency or decibel levels established by
Chapter 65 or are known by the blaster in charge to have produced flyrock,
shall be reported to the Head of the Fire Department within 24 hours and a
written report shall be provided within five days.
65.9.14.3
Seismograph Placement.
The seismograph shall be placed at the nearest inhabited building adjacent to
the blast area that is not owned, leased, or controlled by the blasting
operation.
65.9.14.3.1 If there is no suitable
location for seismograph placement within ten feet of the structure that is
mutually agreed upon by the blaster and the Head of the Fire Department or his
designee, the condition which made it unsuitable to place to seismograph within
ten feet of the structure and the alternative location agreed upon by the Head
of the Fire Department or his designee shall be noted, in writing, in the blast
plan.
65.9.14.3.2 If the person in
control of said nearest structure refuses to grant permission for seismograph
placement as required by this
Code the Head of the Fire
Department shall be immediately notified.
65.9.14.3.2.1 Such refusal shall be further
documented in writing by the blaster and be placed in the blasting
record.
65.9.14.3.2.2 Placement of
the seismograph shall then be at a location mutually agreed upon by the blaster
and the Head of the Fire Department or his or her designee.
65.9.14.3.3 In the case of
underground pipelines, bridges, roadways, steel construction, and other heavy
construction, where prescribed vibration or airblast levels would be overly
restrictive in relation to the nature of the project, vibrations and airblast
levels in excess of the tables listed above shall be allowable when authorized
in writing by the owner or representative of the owner of adjacent inhabited
building(s) or structure(s) within the blast area.
65.9.14.3.4 Seismograph monitoring shall be
required for all blasting operations.
65.9.15 Add:
65.9.15
Pre-blast Inspection
Surveys.
65.9.15.1 The intent of a
pre-blast survey is to provide documentation of the existing physical condition
of buildings and structures within the blasting area with the dimensions of
each observed defect clearly noted.
65.9.15.1.1 With the approval of the AHJ,
requirements for pre-blast survey may be suspended if the blaster adheres to a
Scaled Distance 50 [Allowed Charge Weight per Delay = ((distance to
structure)/50)² ], and a peak particle velocity limit of 0.5in/s. If this
option is selected, the blaster named on the Use and Handling Permit shall sign
a statement of compliance on a form approved by the Marshal to adhere to a
Scaled Distance 50.
65.9.15.1.2
When blasting within 250 ft. (76.2 m) of a structure, as measured from the
closest borehole to the structure, or structures, not owned or controlled by
the project, a pre-blast inspection survey shall be offered.
65.9.15.1.3 It shall be the responsibility of
the blaster to notify structure owners of the survey.
65.9.15.1.4 Surveys in excess of the above
shall be permitted to be conducted at the discretion of the blaster.
65.9.15.1.5 If the owner or occupant request
surveys in excess of the above, the cost of the survey(s) shall be paid by the
owner or occupant of the structure.
65.9.15.1.6 The pre-blast survey shall
document the existing visual conditions of the interior and exterior of the
structure including improvements to the property and other physical factors
that could reasonably be affected by the blasting.
65.9.15.1.7 Structures such as pipelines,
cables, transmission lines, cisterns, wells, and other water systems warrant
special attention; however the assessment of these structures shall be
permitted to be limited to surface conditions and other readily available
data.
65.9.15.1.8 The survey shall
accurately record deficiencies by means of written notes, sketches,
photographs, video tape, cassette tape narrative, or any other format or
combination that sufficiently depicts the pre-existing conditions prior to the
blasting.
65.9.15.1.9 If the owner
refuses the survey the inspector shall request that he sign a waiver of the
survey.
65.9.15.1.10 A pre-blast
survey waiver shall be made on a form approved by the State Fire
Marshal.
65.9.15.1.11 If the owner
or occupant refuses to sign a waiver, the inspector shall sign the waiver
attesting to the refusal.
65.9.15.1.12 Three attempts shall be made to
contact the owner to offer the survey.
65.9.15.1.12.1 If no response is made after
the second attempt, or the owner refuses to sign a survey waiver, a notice
offering the survey shall be sent via any carrier capable of providing a
receipt of delivery.
65.9.15.1.12.2
A receipt of delivery shall satisfy this requirement.
65.9.15.1.13 Surveys shall be conducted by
technicians familiar with construction methods and materials, familiar with
blasting procedures, and this Code.
65.9.15.1.14 When a blast inspection is made,
the results of that inspection shall be permitted to only be made available to
the Head of the Fire Department, the State Fire Marshal or their designees upon
request with the written consent of the occupant of the structure.
65.9.15.1.14.1 The blast inspection shall be
made available to the owner of the inspected property within a reasonable time
after request is made in writing.
65.9.15.1.14.2 Failure to provide a blast
inspection report within 30 days of such request shall be grounds for
revocation of a Use and Handling Permit.
65.9.16 Underwater blasting shall
be conducted in accordance with
29 CFR
1926.912.
65.9.17
Charge Activated Device.
The use of charge activated devices shall comply with the following:
(1) Use and Handling Permits shall be
obtained as required in Section 1.12.
(2) The charge activated device shall be
exempt from the following, blast analysis and the use of a seismograph.
However, the blast design plan is required.
(3) A blaster's log shall be
maintained.
(4) Matting of
sufficient size and strength shall be utilized during all
detonations.
(5) All holes must be
drilled to the manufacturer's specifications and no hole shall be
redrilled.
65.9.18
Blasting Regulatory Review.
65.9.18.1 Any person or firm alleging damage
as a result of blasting operations shall make a complaint on a "Blasting
Regulatory Review" form approved by the State Fire Marshal and obtained from
the fire department of the city or town where damage occurred.
65.9.18.1.1 The Blasting Regulatory Review
Form shall contain a signed certification.
65.9.18.1.2 Completed forms shall be returned
within 30 days of the blasting incident to the Head of the Fire
Department.
65.9.18.2 The
Head of the Fire Department upon receiving a Blasting Regulatory Review Form
shall cause the holder of the "Explosives Users Certificate" and the blaster in
charge, to report to the fire department with copies of pertinent blasters'
logs for the dates in question and to provide copies of the blaster's log for
the dates alleged.
65.9.18.2.1 The blaster in
charge shall be interviewed and blast logs examined to determine any violations
of this Code.
65.9.18.2.2 The fire department authority
shall record the results of his or her inquiry on the Blasting Regulatory
Review Form.
65.9.18.3
The Head of the Fire Department shall retain the original of the Blasting
Regulatory Review Form and forward a copy to the State Fire Marshal's
Office.
65.9.18.4 The holder of the
Explosives Users Certificate shall receive a copy of the complaint form and
acknowledge receipt by signature and date in the space provided on the
complaint form.
65.9.18.5 The
holder of the Explosives Users Certificate or the holder's insurance carrier
shall respond to the claimant within 30 days after the date that the holder
received the complaint form.
65.9.19 Add:
65.9.19
Manufacture of
Explosive.
65.9.19.1
General.
65.9.19.1.2 A
manufacturer of explosives shall mean any person licensed in accordance with 27
CFR Part 55, and engaged in the business of manufacturing explosives for the
purpose of sale or distribution.
65.9.19.1.2.1
A federal manufacturer license is required when a binary system is used and the
components are mixed in the course of a trade or business to create an
explosive material.
65.9.19.1.2.2
In the case of binary systems, the supplier of pre-weighted or pre-measured
ingredients, not the person mixing the ingredients, is considered the
manufacturer of any pyrotechnic materials created from binary
components.
65.9.19.1.2.3 The
person loading binary materials into devices supplied by the manufacturer of
binary systems shall not be considered a manufacturer when such loading is
performed according to the instructions of the manufacturer.
65.9.19.2 Add:
65.9.19.2
Explosives
Manufactories.
65.9.19.2.1 All
explosives manufactories shall be supplied with some means of direct
communication with the Head of the Fire Department, such as radio, telephone or
fire alarm boxes, for immediate notice in case of fire.
65.9.19.2.2 There shall be a competent
watchman on guard at all explosive manufactories except when the same are in
actual operation.
65.9.19.2.3 No
dry vegetation or combustible rubbish shall be allowed to accumulate within 50
feet of any building connected with such manufactories.
65.9.19.2.4 Persons younger than 18 years old
shall not be employed in an explosive manufactory and shall not be permitted to
enter such manufactory unless accompanied at all times by a responsible adult
person.
65.9.20
Add:
65.9.20
Explosives
Transaction Records.
65.9.20.1 All
persons keeping, storing, using, selling, manufacturing, handling, or
transporting explosive material shall maintain records so that the quantity and
location of such explosive materials are readily available for inspection by
the Head of the Fire Department, the State Fire Marshal, their designees, or a
police officer.
65.9.20.1.1 Quantity and
location records shall be delivered to the State Fire Marshal forthwith upon
demand.
65.9.20.2
Daily Summary of Magazine Transactions:
65.9.20.2.1 In taking the inventory required
by Chapter 65, a licensee or permitee shall enter the inventory in a record of
daily transactions which shall be kept for each magazine on a storage
facility.
65.9.20.2.2 These records
shall be permitted to be kept at one central location on the business premises
if separate records of daily transactions are kept for each magazine.
65.9.20.2.3 Not later than the close of the
next business day, each licensee or permitee shall record by the manufacturer's
name or brand name, the total quantity received in and removed from each
magazine during the day, and the total quantity remaining on hand at the end of
the day.
65.9.20.2.4 Any
discrepancy which might indicate a theft or loss of explosive materials shall
be reported to the State Fire Marshal immediately.
65.9.21 Add:
65.9.21
Discontinuance of
Business. Where an explosive materials business or operation is
discontinued or succeeded by a new licensee or registrant, the records
prescribed by Chapter 65 shall appropriately reflect such facts and shall be
delivered to the successor.
65.9.21.1 Where
discontinuance of the business or operation is absolute, copies of the records
required shall be delivered to the State Fire Marshal within 30 days following
the business or operation discontinuance.
65.9.22 Any person who transports or delivers
explosive materials to any magazine, building or structure shall keep a record
of the permit number assigned to said magazine, building, or structure by the
State Fire Marshal in accordance with Chapter 65.
65.9.23
Theft. The loss or theft
of any explosives shall be immediately reported to the State Fire Marshal and
confirmed in writing within 24 hours.
65.9.24 The State Fire Marshal or his or her
designee shall be permitted, in his or her discretion, upon discovering a
violation of this
Code or upon determination of a fire or
explosion hazard, require the removal of any explosive material or that a
watchman be placed continuously in charge of it.
65.9.24.1 The expense of said removal or
watchman shall be the responsibility of the person in whose possession the
explosive material is found.
65.9.25 Any explosion, fire, or collision
occurring in connection with the keeping, storage, manufacture, sale,
transportation or use of explosive material causing loss of life or injury to
any person or damage to property shall be reported immediately to the State
Fire Marshal and the Head of the Fire Department, giving an account of the
same, and then confirmed giving a detailed account in writing within 24
hours.
65.9.26 Any person, firm, or
corporation in the Commonwealth who keeps, uses, sells, transports, or stores
any explosive shall keep a record of the disposition of such explosive by
recording the batch number, if any, from the case from which individual
explosive has been removed, if sold in less than case lots, or the number of
cases with their batch numbers if sold in case lots.
65.9.26.1 The person to whom such explosive
has been transferred shall record the transaction and such records shall be
maintained for ready inspection by the State Fire Marshal, the Head of the Fire
Department, or the Head of the Police Department, or their designees, for a
period of three years.
65.9.27
Laboratories. Industrial
laboratories, laboratories of technical institutes, colleges, universities, and
similar institutions shall be permitted to keep, store, and use explosives or
blasting agents when confined to the purpose of scientific or technical
instruction or research, provided the storage and use of explosives or blasting
agents is conducted or supervised by a person holding a Certificate of
Competency and not more than 50 lbs. of explosive are kept on hand at any time
in such laboratories.
65.9.27.1 Such
Certificate of Competency can be issued by the State Fire Marshal without
testing, providing a curriculum vitae is provided.
65.10 Add:
65.10 The possession and use of consumer
fireworks is prohibited in the Commonwealth unless part of a display firework
show in accordance with Section 65.2 or part of a Pyrotechnics
Before a Proximate Audience in conformance with Section
65.3.
65.11 Add:
65.11
Cannon or Mortar Firing.
65.11.1 The firing of muzzle-loading cannons
during patriotic celebrations and reenactments, including all such cannons
ranging from pre-Revolutionary War vintage to present day facsimiles shall
comply with
Section 65.11.
65.11.1.1 This Section shall not apply to any
cannon exhibit in which explosives are not being used.
65.11.1.2 This Section shall not apply to the
storage of ammunition for any cannon and shall be subject to all the applicable
requirements in Section 65.9.
65.11.2
Permits. Permits, where
required, shall comply with Section 1.12.
65.11.3 Add:
65.11.3
Terms. As used in
Chapter 65, the enclosed terms shall have the following meaning assigned to
them.
65.11.3.1 through 65.11.3.6
Add:
65.11.3.1
Blank-fire. The supervised discharge of a cannon or mortar without
projectile.
65.11.3.2
Cannon. Any gun designed to be fired from a carriage resting on
the ground and which is loaded from the muzzle with rigid noncombustible black
powder cartridge.
65.11.3.3
Display. The supervised discharge of cannon or mortar, whether
blank-fire without projectile or live-fire with projectile.
65.11.3.4
Live-fire. The
supervised discharge of cannon or mortar with projectile.
65.11.3.5
Mortar. Any cannon
whose length is less than six times its bore diameter, or any cannon fired at
an elevation of 45E or more from the horizontal.
65.11.3.6
Range. An area
designated for the discharge of various weapons, having a minimum unobstructed
length of 100 yards (99.44 m), a minimum unobstructed width of 25 yards (22.86
m), equipped with a natural or manmade down range barrier a minimum of ten feet
in height.
65.11.4
Add:
65.11.4
Range Conditions
and Other Pre-firing Requirements.
65.11.4.1 A cannon be only be fired with
ball, shot or projectile on ranges approved by the AHJ.
65.11.4.1.1 Such ranges shall be clear and unobstructed between
discharge point and target area and for a safe distance to the rear of target
in event of an overshoot.
65.11.4.1.2 The
target area shall not exceed 250 yards (228.6 m) from the point of
discharge.
65.11.4.2
There shall be no permanent building, public highway, railroad, or other public
way within the forward sector of a 180E arc having a radius of 100 ft. (30.48
m) from the muzzle of the cannon.
65.11.4.2.1
A similar sector of 180E directed toward the rear 75 ft. (22.86 m) in radius
shall be clear of all public ways, permanent buildings, or other
obstructions.
65.11.4.3
The firing of the cannon shall comply with the following:
(1) No cannon shall be discharged during any
windstorm in which the direction and velocity of the wind renders the display
dangerous to the public safety and/or surrounding property.
(2) There shall be no discharging of cannon
between the hours of sunset and sunrise without prior written approval from the
Head of the Fire Department.
(3)
The Head of the Fire Department shall designate the location and type of fire
extinguishing equipment as may be required.
(4) No firing of any cannon shall be
conducted unless the crew is present in adequate numbers for the particular
cannon or mortar.
(5) The competent
operator shall be responsible to ensure that all members of the crew have been
fully trained in the safe operation of the cannon or mortar.
(6) No member of the gun crew shall be
younger than 18 years old.
(7)
Smoking shall be prohibited in the discharge area.
(8) No member of the audience shall be
allowed in the forward or flank zone of the muzzle of a cannon firing a
projectile within a forward sector of 180E having a radius of 150% of the
estimated range of the piece.
(9)
The audience at a supervised firing of cannon shall be restrained behind lines
60 ft. (18.29 m) on the flank area back of the muzzle and 60 ft. (18.29 m) to
the rear of the gun.
(10) Unless
otherwise allowed by the State Fire Marshal, no piece shall be discharged with
blank ammunition, unless all spectators are at a safe distance from the front
of the piece and at least 60 ft. (18.29 m) to the rear or flank. Adjacent
pieces shall be at a safe interval.
65.11.5 Add:
65.11.5
Magazines and Powder.
65.11.5.1 All ammunition and powder shall
comply with the following:
(1) All ammunition
for cannon shall be transported and temporarily stored at the firing location
in the finished state in a portable magazine.
(2) Such magazine shall be constructed of at
least 24-gauge sheet metal lined with a minimum of 3/4 inch marine plywood
or other non-sparking material, and shall be of sturdy sealed construction held
together with non-sparking fastenings. A suitable lock and hasp of non-sparking
material shall be provided.
(3) In
the discharge area, a ready-service box constructed of wood with non-sparking
fastenings and cover designed to be self-closing shall be positioned at ground
level approximately 25 ft. (7.62 m) to the rear of the piece being served with
the hinges toward the piece.
(4)
All magazines and ready-service boxes shall be closed prior to the loading of
each cartridge of the piece being served and adjacent pieces.
(5) Ready-service boxes for each gun shall
contain the minimum number of cartridges required for the gun during that
particular display.
(6) Magazines
and ready-service boxes shall at all times be under the control of a competent
member of the gun crew.
(7) No
loose or bulk powder other than priming powder in quantities not exceeding
1/2 ounce shall be used in the firing of any cannon, and no loose or bulk
powder shall be transported or stored in any portable magazine with
cartridges.
(8) Blank artillery
cartridges shall be made up of black powder only, not to exceed four ounces per
inch of largest bore diameter.
(9)
Cartridges must have a minimum of three wraps of heavy-duty aluminum foil and
be packed to a firm consistency.
(10) Only cannon grade, 1F, or 2Fg black
powder will be used.
(11) Powder
grades cannot be mixed.
(12) No
artillery cartridges shall be constructed at the event site.
(13) No wadding of any kind is permitted in
blank firing.
(14) The amount of
black powder used in each cartridge shall be such as to not present an undue
hazard to persons, property, or the piece itself.
(15) Powder cartridges for cannons shall not
exceed four ounces of powder per inch of bore diameter.
(16) Powder cartridges for mortars shall not
exceed four ounces of powder per inch of chamber diameter.
(17) No torch shall be used to ignite any
cartridge to be fired from cannon.
(18) All cannons used to fire a projectile
shall be provided with an instant source of ignition such as an electrical
squib, or bridge wire or percussion cap, or other approved instant firing
device. Exception to the foregoing shall apply to the use of fuses for the
firing of mortars.
(19) No firing
of any steel or iron cannon or mortar shall be conducted unless the weapon
contains a seamless steel safety sleeve with breech plug, designed for such
firing and have had a boroscope inspection conducted by a qualified
person.
(20) Original guns and
bronze guns shall permitted to be used without a safety sleeve, provided that
they have had a boroscope inspection conducted by a qualified person. Pits,
scratches, or other defects more than 3/16 inch deep shall render the cannon
unusable.
(21) Cannons and mortars
used for live-firing shall have a boroscope inspection conducted at least once
every five years.
(22) Cannons and
mortars used exclusively for blank-firing shall have a boroscope inspection
conducted at least once every 10 years.
(23) Projectiles shall not be so constructed
as to develop any unsafe pressures; and no combustible, explosive, or
pyrotechnic projectiles shall be used.
(24) Reloading shall not commence until the
worming and wet sponging have been completed after firing.
(25) The piece shall be wormed and wet
sponged between shots and the vent stopped from the time the worm enters the
muzzle until the rammer is removed from the bore after the cartridge is rammed
in blank-firing, or the projectile is rammed in live-firing.
(26) At no time shall any cannon be left
unattended while loaded or during a misfire until the piece has been
cleared.
(27) In the event of a
misfire, the competent operator shall take the following steps:
(a) The gunner shall give an audible
warning.
(b) No personnel shall
approach the front of the muzzle.
(c) A mandatory three minute cooling off
period shall be observed.
(d) The
piece shall be re-primed from a safe position and a repeated attempt made to
fire the piece.
(e) If the attempt
to re-fire the piece is unsuccessful, the piece shall be flooded with water
through the vent and allowed to soak for a period of at least one hour unless
the water or compressed gas can be used to flush the cartridge out of the
muzzle.
(f) The projectile and/or
cartridge shall be removed through the muzzle.
(28) If, after a display, the competent
operator has reason to believe that there are any unignited charges or remnants
thereof containing explosives in the area, he shall make a thorough search of
the area for such explosives. The responsibility for disposition of it shall be
assumed by the certificate holder.
(29) Any explosion, fire, or other accident
occurring in connection with the keeping, storage, manufacture, handling,
transportation, supervised display, or other disposition of ammunition for
cannon causing loss of life or injury to any person or damage to property,
shall be immediately reported to the State Fire Marshal by the competent
operator, giving a detailed account of same and confirmed in writing.
Chapter
66
Flammable and Combustible Liquids.
66.1.1 Replace with the following:
66.1.1 * The storage, handling, and use of
flammable and combustible liquids, including waste liquids, as herein defined
and classified, shall comply with this chapter; NFPA 30, Flammable and
Combustible Liquids Code; Sections 60.1 through
60.4 of this Code; and NFPA 35:
Standards for the Manufacture of Organic Coatings, as
applicable.
66.1.4 Replace as
follows:
66.1.4 Installations made
in accordance with the applicable requirements of the following standards shall
be deemed to be in compliance with this Code except that the
maximum allowable quantities of hazardous materials are limited to the
quantities listed in the Building Code and Table 60.4.2.1.1.3
of this Code:
66.4.1.1.1.1 Add:
66.4.1.1.1.1 For the purposes of this
classification if an accurate boiling point is unavailable for the material in
question or if a mixture does not have a constant boiling point, the 20%
evaporated point of a distillation performed in accordance with ASTM D 86:
Standard Test Method for Distillation of Petroleum Products at
Atmospheric Pressure shall be used as the boiling point of the
liquid.
66.21.4.1.6 Add:
66.21.4.1.6
Pre-fabricated Tanks and
Dikes.
(1) Pre-fabricated tanks and
dikes shall provide 110% containment.
(2) If a rain shield is provided, it shall
have provisions that an overfill of the tank will go directly into the
dike.
66.21.5.2.1 (2)
Delete.
66.21.6.4 Add:
66.21.6.4
Automotive Lubrication
Service Centers.
66.21.6.4.1 Tanks
shall be located in a separate room from the main work area by a 2 hour fire
rated enclosure.
66.21.6.4.2 The
storage room shall be equipped with a fixed fire suppression system designed
and installed in accordance with Section 13.8.
66.21.6.4.3 The storage room shall have an
area not less than 110% of the largest tank capacity plus 10% of the aggregate
amount of all other tanks in that room.
66.21.6.4.3.1 If water is utilized for
suppression the containment area shall comply with the Building
Code.
66.21.7.4 Replace with the
following:
66.21.7.4
Removal
from Service of Storage Tanks.
66.21.7.4.1 Add:
66.21.7.4.1
Closure of Aboveground
Storage Tanks.
Aboveground tanks taken out of service or abandoned shall be
emptied of liquid, rendered vapor-free, and safeguarded against trespassing in
accordance with NFPA 326, Standard for the Safeguarding of Tanks and
Containers for Entry, Cleaning, or Repair, or in accordance with the
requirements of the AHJ.
66.21.7.4.2
Reuse of Aboveground
Storage Tanks.
Aboveground tanks shall be permitted to be reused for flammable
or combustible liquids service provided they comply with applicable sections of
this Code and are approved.
66.21.7.4.3
Removal from Service of
Underground Storage Tanks.
66.21.7.4.3.1
General.
Underground tanks taken out of service shall comply with
310 CMR
80.00: Underground Storage Tank (UST)
Systems and be emptied of liquid and residuals, rendered vapor-free,
and safeguarded against trespassing in accordance with this section and in
accordance with NFPA 326 or in accordance with the requirements of the AHJ. The
procedures outlined in this section shall be followed when taking underground
tanks temporarily out of service, closing them in place permanently, or
removing them.
66.21.7.4.3.2
Temporary Closure. Underground tanks shall comply with
310 CMR
80.00:
Underground Storage Tank (UST)
Systems and be rendered temporarily out of service only when it is
planned that they will be returned to active service, closed in place
permanently, or removed within an approved period not exceeding five years. The
following requirements shall be met:
(1)
Corrosion protection and release detection systems shall be maintained in
operation.
(2) The vent line shall
be left open and functioning.
(3)
The tank shall be secured against tampering.
(4) All other lines shall be capped or
plugged.
66.21.7.4.3.2.1 Tanks
remaining temporarily out of service for more than five years shall be
permanently closed in place or removed in accordance with Section
66.21.7.4.3.3 or 66.21.7.4.3.4, as
applicable.
66.21.7.4.3.3
Replace with the following:
66.21.7.4.3.3
Permanent Closure in
Place. Underground tanks shall be permitted to be permanently closed in
place if approved by the AHJ and in accordance with
310 CMR
80.00:
Underground Storage Tank (UST)
Systems. All of the following requirements shall be met:
(1) All applicable AHJs shall be
notified.
(2) A safe workplace
shall be maintained throughout the prescribed activities.
(3) All flammable and combustible liquids and
residues shall be removed from the tank, appurtenances, and piping and shall be
disposed of in accordance with regulatory requirements and industry practices,
using a written procedure.
(4) The
tank, appurtenances, and piping shall be made safe by either purging them of
flammable vapors or inerting the potential explosive atmosphere. Confirmation
that the atmosphere in the tank is safe shall be by testing of the atmosphere
using a combustible gas indicator if purging, or an oxygen meter if inerting,
at intervals in accordance with written procedures.
(5) Access to the tank shall be made by
careful excavation to the top of the tank.
(6) All exposed piping, gauging and tank
fixtures, and other appurtenances, except the vent, shall be disconnected and
removed.
(7) The tank shall be
completely filled with an inert solid material.
(8) The tank vent and remaining underground
piping shall be capped or removed. Underground steel storage tanks used for the
storage of flammable liquids shall be disposed of at a Tank Dismantling Yard
approved by the State Fire Marshal.
(9) The tank excavation shall be
backfilled.
66.21.7.4.3.4
Add
66.21.7.4.3.4
Removal and Disposal. Underground tanks and piping shall be
removed in accordance with the following requirements:
(1) The steps described in
66.21.7.4.3.3(1) through 66.21.7.4.3.3(5)
shall be followed.
(2) All exposed
piping, gauging and tank fixtures, and other appurtenances, including the vent,
shall be disconnected and removed.
(3) All openings shall be plugged, leaving a
1/4 in. (6 mm) opening to avoid buildup of pressure in the tank.
(4) The tank shall be removed from the
excavated site and shall be secured against movement.
(5) Any corrosion holes shall be
plugged.
(6) The tank shall be
labeled with its former contents, present vapor state, vapor-freeing method,
and a warning against reuse.
(7)
The tank shall be removed from the site as authorized by the AHJ, preferably
the same day.
66.21.7.4.3.5
Temporary Storage of
Removed Tanks. If it is necessary to temporarily store an underground
tank that has been removed, it shall be placed in a secure area where public
access is restricted. A 1/4 in. (6 mm) opening shall be maintained to
avoid buildup of pressure in the tank.
66.21.7.4.3.6
Disposal of Tanks.
Disposal of underground tanks shall meet the following requirements:
(1) Before a tank is cut up for scrap or
landfill, the atmosphere in the tank shall be tested in accordance with
66.21.7.4.3.3(4) to ensure that it is safe.
(2) The tank shall be made unfit for further
use by cutting holes in the tank heads and shell.
66.21.7.4.3.7
Documentation. All
necessary documentation shall be prepared and maintained in accordance with all
federal, state, and local rules and regulations.
66.21.7.5 Add:
66.21.7.5 Reserved.
66.21.7.6 Add:
66.21.7.6
Application for Approval of
Tank Dismantling Yards.66.21.7.6.1
Underground steel storage tanks used for the storage of flammable liquids shall
only be disposed of at tank dismantling yards approved by the State Fire
Marshal.
66.21.7.6.2 Application
for approval of a tank dismantling yard small shall be made on a form approved
by the State Fire Marshal (Form FP-295). Completed applications shall be
submitted to: Department of Fire Services, Division of Fire Safety, P.O. Box
1025, 1 State Road, Stow, MA 01775.
66.21.7.7
Tank Dismantling Yard.
66.21.7.7.1 Each tank dismantling yard shall
hold valid licenses or permits from any and all local city and town Boards,
Agencies, Departments, where necessary to conduct operation for underground
steel storage tank dismantling and storage.
66.21.7.7.2 Each tank dismantling yard shall
comply with all the provisions of regulation and be approved by the State Fire
Marshal and endorsed by the Head of the Fire Department.
66.21.7.8
Operation of Tank Dismantling
Yards.
No person at a tank dismantling yard shall accept an
underground steel storage tank that in any way would be used for reuse or
resale purposes.
66.21.7.8.1 Each
approved tank dismantling yard shall maintain a written ledger listing all
underground steel storage tanks received, a receipt of disposition thereof and
any other data required by the Marshal.
66.21.7.8.2 All underground steel storage
tanks shall be pumped out dry before transported to a tank dismantling
yard.
66.21.7.8.3 The vapors in an
underground steel storage tank may be made inert. Solid carbon dioxide (dry
ice) crushed and distributed evenly over the greatest possible area in the
amount of 1.5 (lbs) pounds per 100 gallons of tank capacity may be used to
inert the tank.
66.21.7.8.4 The
cleaning and residue of the underground steel storage tank must be treated as a
hazardous waste and removed by a licensed hazardous waste or waste oil
transporter, as required by the 310 CMR: Department of Environmental
Protection. The hazardous waste manifest number shall be recorded on the fire
department permit.
66.21.7.8.5 The
underground steel storage tank shall be purged with an inert gas, such as
nitrogen or carbon dioxide, while all connecting lines to the tank including
the vent, shall be removed.
66.21.7.8.6 Holes or openings shall be
drilled or made in the tank when received at the tank disposal yard.
66.21.7.8.7 Each tank dismantling yard shall
have a device capable of measuring flammable vapors. The device shall be
properly calibrated, and employees shall be trained in its use.
66.21.7.8.8 No tank dismantling yard shall
accept any tank that has not been purged of product and inerted.
66.21.7.8.9 All tanks shall be stored on the
secured premises of an approved dismantling yard where they can be safeguarded
from the general public.
66.21.7.8.10 If a tank yard finds product in
a tank, such as sludge or other contaminated waste, the material shall be
treated as a hazardous waste and removed by a hazardous waste or waste oil
transporter in accordance with 310 CMR: Department of Environmental
Protection.
66.21.7.8.11 All
underground steel storage tanks accepted at approved tank yards must be
dismantled within two working days of the date of acceptance. No tanks shall be
stored in excess of 72 hours without approval of the Head of the Fire
Department.
66.21.9
Add:
66.21.9 Storage tanks that
undergo a change of stored liquid that represents a change in liquid
classification, as defined in
Section 66.4.2, or change in
physical properties, shall be re-evaluated for compliance with
Sections
66.21 through
66.25, as applicable.
66.21.9.1 Where a storage tank does not
comply with
Sections 66.21 through
66.25 and
was legally constructed in accordance with the applicable fire code at the time
of its construction or where a requirement was waived by the applicable AHJ, a
hazard analysis shall be completed in accordance with
Section
66.6 and the following:
1. The hazard
analysis shall be prepared and certified by a Massachusetts Registered
Professional Engineer.
2. The
analysis shall demonstrate that the change in liquid classification does not
constitute an increase in fire or explosion hazards or risks to life and
property.
66.21.9.2 The
AHJ may require additional measures of protection.
Chapter 67
Flammable Solids
(No amendments)
Chapter
68
Highly Toxic and Toxic Solids and Liquids
(No amendments)
Chapter
69
Liquified Petroleum Gases and Liquified Natural
Gases
69.1.1.1 Replace with the
following:
69.1.1.1 The storage,
use, and handling of liquefied petroleum gases (LP-gas) upstream from the
outlet of the first stage regulator shall comply with the requirements of this
chapter; NFPA 58, Liquefied Petroleum Gas Code; and Sections
60.1 through 60.4 of this
Code.
69.1.1.4
Add:
69.1.1.4
Certificates. Certificates of completion, where required, shall
comply with Section 1.12.8.51 and Section
1.13 as applicable.
69.1.3
Add:
69.1.3
Terms. As
used in Chapter 69, the enclosed terms shall have the following meaning
assigned to them.
69.1.3.1
Abandoned. Any container which has not been used either for
filling or draw off of LP-gas for a continuous period in excess of 12
months.
69.1.4
LP-container, Filling, Shipment, Odorization, and Testing
Requirements. If odorization is required, as provided in NFPA 58:
Liquefied Petroleum Gas Code,
Section 4.2.1,
one of the testing thresholds required in
Section 69.1.4.2(2)
shall be completed and documented. The presence of the odorant shall be
permitted thereafter by sniff testing each time the propane changes in the
distribution network. If the amount of odorant in the propane is questionable
by sniff testing or the records are not accepted by or made available to the
AHJ as required in
Section 69.1.4.3.1, the testing as
prescribed in accordance with the Section 69.1.4.2(2) shall be repeated. If
necessary, thresholds shall be met by adding additional odorant to obtain
proper odorized propane levels as prescribed in
Section
69.1.4.2(1) or 69.1.4.2(2). In such situations where the propane
odorant is questionable, immediate verbal notification shall be given to the
AHJ, which shall be followed by written notification within 24 hours
documenting the date, time, and location of discovery and status of such event.
69.1.4.1
Railcar Shipments. Each
railcar shipment of LP-gas intended for distribution within Massachusetts shall
comply with the provisions in Section 69.1.4.2(1). Each
railcar shipment delivered for distribution shall be tested for odorization
using one of the tests prescribed in Section 69.1.4.2(2) and
Sub-sections (a), (b), (c).
69.1.4.2
Odorization Thresholds,
Testing and Filling of Containers:
(1)
If ethyl mercaptan is used for odorization purposes, it shall be injected at a
minimum rate of one lb per 10,000 gallons of propane.
(2) For testing purposes one of the following
tests listed in (a), (b) or (c) shall be required to determine adequate ethyl
mercaptan odorant levels equivalent to 1 lb per 10,000 gallons of propane.
(a) Vapor Test using stain tubes resulting in
a minimum of five ppm of ethyl mercaptan utilizing ASTM D 5305:
Standard Test Method for Determination of Ethyl Mercaption in LP-gas
Vapor.
(b) Flash Vapor
Test using stain tubes resulting in a minimum of 17 ppm of ethyl mercaptan
utilizing ASTM D 5305: Standard Test Method for Determination of Ethyl
Mercaption in LP-gas Vapor.
(c) Liquid Test for analysis of volatile
sulfurs using gas chromatography resulting in a minimum of 17 ppm of ethyl
mercaptan utilizing ASTM D1265: Standard Practice for Sampling
Liquefied Petroleum (LP) Gases, Manual Method.
(3) Newly filled tanks and containers shall
be purged according to manufacturer's instructions.
(4) Newly installed tanks greater than 125
gallons shall comply with the following:
(a)
Within two business days of the tank installation approval by the AHJ, such
tank shall be filled with LP-gas and;
(b) If the tank is not placed into service
within 30 days of the tank installation approval date, such tank shall be
tested by the LP-gas company in accordance with Section
69.1.4.2(2), prior to being placed into service and;
(c) Maintain records in accordance with
Section 69.1.4.3 and report findings, if applicable, in
accordance with Section 69.1.4.
69.1.4.3
Records. Records of all
testing required by this Code shall be maintained. The results shall be kept by
both the shipper and user for a minimum of 3 years from the date of delivery.
69.1.4.3.1 Test results shall be made
available to the AHJ upon request.
69.1.4.4 Each person handling LP-gas shall be
trained, at applicable level, in accordance with the "Dispensing Propane
Safely" program published by the Propane Education and Research Council or
other education programs acceptable to the State Fire Marshal.
69.1.4.4.1 Certificates of completion shall
be maintained by the employer for three years and a copy of said certificate
shall be given to the trainee at the completion of each program.
69.1.4.4.2 Certificates of completion shall
include the date of completion, the course name, and be signed by the
instructor or provider. Such certificates shall be submitted to the AHJ upon
request.
69.1.4.5
Field Equipment Identification. All LP-gas installations of 125
gallons or greater shall be provided with a sign identifying the responsible
party for the installation and maintenance of the LP-gas installation.
69.1.4.5.1 The sign shall be installed in a
plainly visible location.
69.1.4.5.2 Such sign shall include the name
and telephone number of the LP-gas supplier, plant installer, owner, or
operator.
69.1.4.6
Emergency and Reporting Procedure. In situations where a gas leak
results in imminent danger, immediate verbal notification shall be given to the
911 dispatch center.
69.1.4.6.1 The AHJ shall
receive written notification within 24 hours of said notification documenting
the date, time, and location of discovery, status, and remediation of such
event.
69.1.4.6.2 In situations
where the AHJ has directed an LP-gas provider to take corrective action, the
provider shall immediately respond verbally to the AHJ, as directed, such
provider's response shall be followed by written notification, if requested,
within 24 hours after resolution, documenting the date, time, and the location
of discovery and status of the LP-gas installation.
69.3.5.4.3 Replace with the
following:
69.3.5.4.3 The distance
measured with a 3 ft arc from the point of discharge of a container pressure
relief valve to any building opening below the level of such discharge shall be
in accordance with Table 69.3.5.4.3.
69.3.14.6.3 Add:
69.3.14.6.3 The owner of the storage
equipment shall be responsible for the installation of the LP-gas facility and
for maintaining it in a safe operating condition.
63.3.14.6.4 Add:
69.3.14.6.4 No person shall install, remove,
connect, disconnect, fill, or refill any LP-gas container without permission of
the owner of the container.
69.3.14.6.5 Only a trained individual
complying with Section 69.1.4.4 shall install, remove,
connect, disconnect, sell, fill, refill, deliver or permit to be delivered, or
operate any LP-gas system utilizing containers of over 42 lbs (10 gallons)
product capacity.
69.3.14.6.6 The
State Fire Marshal shall be permitted to order the user of a system in writing
to meet requirements:
(1) Where unusual
conditions exist;
(2) When it is
necessary for the protection of life and property;
(3) Provided the requirements are within the
intent and purpose of this Code.
69.3.15.4.4 Add:
69.3.15.4.4 "NO SMOKING" and "STOP ENGINE
WHEN REFUELING" signs shall be displayed on the front and rear of each
dispenser at the filling station. The signs shall have block letters at least 1
inch high with either red letters on a white background or white letters on a
red background.
69.5.2.1.6
Add:
69.5.2.1.6 Areas used for the
storage of containers or cylinders awaiting use or resale shall post a readily
accessible and clearly visible warning sign stating "NO SMOKING" and "FLAMMABLE
GAS" or otherwise indicate the contents of such containers or cylinders, such
as "FLAMMABLE GAS PROPANE" or "FLAMMABLE GAS BUTANE".
Chapter 70
Oxidizer Solids and
Liquids
(No amendments)
Chapter
71
Pyrophoric Solids and Liquids
(No amendments)
Chapter
72
Unstable (Reactive) Solids and Liquids
(No amendments)
Chapter
73
Water-Reactive Solids and Liquids
(No amendments)
Chapter
74
- Ammonium Nitrate
(No amendments)
Chapter
75
Organic Peroxide Solids and Liquids
(No amendments)