Current through Register 1531, September 27, 2024
2.27.2 Emergency or Standby Power System
2.27.2.4.5 Add a final paragraph that reads:
Where an emergency or standby system is required by 780 CMR:
State Board of Building Regulations and Standards, said system
shall operate the elevator or elevators in the event of normal power failure,
and the requirements of 2.27.2.1 through 2.27.2.5 shall be met. If an emergency
or standby system is not required by 780 CMR but exists and operates the
elevator or elevators, the requirements of 2.27.2.1 through 2.27.2.5 shall be
met. If fewer than all cars can be run at the same time, all cars shall be
sequenced one or more at a time to the fire recall floor automatically, after
which the selector switch located at that floor can designate a preferred
car.
2.27.3 Firefighter's Emergency Operation:
Automatic Elevators 2.27.3.1 Phase 1 Emergency Recall Operation
2.27.3.1.1 Add a new (d) that reads:
(d) The phase 1 hall key switch shall be
marked with the off position vertical and in the center. The key shall be
inserted with the cut side facing up.
2.27.3.1.6
Delete (j) and replace with:
(j) When
an elevator(s) has gone to the alternate level due to the activation of a fire
alarm initiating device at the designated level, the manual activation of the
fire-recall switch at the designated level shall cause the car to recall to
that level.
level."
2.27.3.3 Phase II Emergency In-Car
Operation. Delete first sentence of the second paragraph and replace
with:
The key shall be removable in each position. The hold
position in the center shall be vertical. The key shall be inserted with the
cut side facing up.
2.27.3.3.7 Delete the first
sentence of the second paragraph and replace with:
For all installations performed under ASME A17.1-2013/CSA
B44-13: Safety Code for Elevators and Escalators, the
firefighters' operation panel cover shall be openable with the use of a 3502
key. The key switch grooves shall be constructed and installed with the cut
side facing up.
2.27.7 Firefighter's Emergency
Operation: Operating Procedures
2.27.7.4 Delete.
2.27.8 Switch Keys. Delete and replace
with:
2.27.8 Switch Keys. Firefighter's Emergency
Operation shall only be activated with the use of the 3502 key and cylinder.
The possession of the Massachusetts firefighter key number 3502 shall be
limited to fire department personnel, licensed elevator mechanics, and elevator
inspectors, and it shall be used only in the performance of their official
duties. This key shall not operate any other switch unless specifically
described in 524 CMR and shall not be a part of a building master key
system.
2.27.9 Elevator Corridor Call Station
Pictograph. Delete and replace with:
2.27.9 Fire Emergency Hall Buttons Signs. There
shall be a sign securely fastened to the wall over every hall button station.
The minimum size shall be 3W x 214". The lettering
shall be impressed or engraved on a contrasting background, and shall read and
be sized as follows:
SIGNAGE
|
LETTERING SIZE
|
LETTERING COLOR
|
In Case of
|
Vs inch equals 14-point
lettering
|
Color: Black
|
Fire
|
% inch equals 30-point lettering
|
Color: Red
|
In This Building
|
Vs inch equals 14-point
lettering
|
Color: Black
|
Use Exit Stairways
|
3/16
inch equals 16-point lettering
|
Color: Red
|
Do Not Use This Elevator
|
Vs inch equals 14-point
lettering
|
Color: Black
|
2.27.10 Medical Emergency Elevators
"All new buildings, or complete new additions to existing
buildings in which an elevator is being installed, shall be provided with
medical emergency elevators as described in
524 CMR 17.40.
Complete new additions to existing buildings shall mean a hoistway constructed
outside the confines or footprint of the existing building."
Add a
section:
2.27.12 Medical Emergency Elevators.
(1)
Medical Emergency
Elevators.
(a) All new buildings
or complete new additions to existing buildings in which an elevator is being
installed shall be provided with at least one passenger elevator designed to
accommodate the loading and transportation of an ambulance gurney or stretcher
(24" wide by 84" long with 5" radius corners) in its horizontal position.
Complete new additions to existing buildings shall mean a hoistway constructed
outside the confines or footprint of the existing building.
(b) The hoistway and car shall be provided
with power operated passenger type horizontally sliding doors, minimum size to
be 42" wide by 78" high. When center opening doors are used they shall be
located on the narrow end of the car or car size and/or the door size will be
altered to comply with 2.27.12(l)(c).
(c) Elevator capacity, platform size, and
entrance configuration of medical emergency elevators shall be capable of
accommodating the designated gurney or stretcher with equivalent
ease.
(2)
Medical Emergency Key Switches and Markings.
(a) This elevator shall be controlled by a
two position key switch at the main floor of a building and by a similar key
switch in the car operating panel. The lock and key shall be that manufactured
by Medeco Security Locks, Inc. and the key number shall be 65W 2650 T101 26 R7.
The lock shall be arranged so that the switch shall be off when the key is in a
vertical position and it shall be on when the key cut is facing approximately
90 to the right of the vertical. The key shall only be removable in the off
position.
(b) Only elevator
companies or manufacturers authorized by the Division may order this
lock.
(c) Only personnel authorized
by the Division may purchase this key.
(d) Both locks shall be identified with the
words "MEDICAL EMERGENCY" engraved adjacent to the lock. The lettering shall be
a minimum of 14 points with lettering or background color blue.
(3)
Medical Emergency
Operation.
(a) When the main
floor key is turned to the on position, it shall activate a continuous audible
signal in the car which can be the same signal used for fire service. It shall
also activate a visual signal in the car and at the main floor key call station
that reads "Medical Emergency." All car calls shall be canceled and be unable
to be re registered. The car shall not accept any hall calls after this service
is activated.
(b) When the car is
in motion, the in-car stop switch shall be de activated.
(c) When the car is moving toward the main
floor it shall return non stop and open its doors on arrival. It shall not
comply with 2.27.12(3)(b) until the car begins to move.
(d) When the car is moving away from the main
floor it shall reverse direction at the next available floor without opening
its doors and return non stop to the main floor.
(e) When the car is at a floor, other than
the main floor with its doors open, they shall close without delay, and the car
return to the main floor.
(f) The
car shall return to the main floor after being called by the EMS main floor
switch and open its doors even if the main floor EMS key switch has been
returned to the off position during travel. On arrival at the main floor the
audible signal in the car shall cease.
(g) Upon arrival at the main floor the doors
shall open and if the main floor EMS key switch is "on" they shall remain open
until that switch is turned "off." If the main floor EMS key switch is "off"
the visual signals shall remain illuminated for a minimum of 60 seconds. During
this delay the EMT shall insert his key into the car control panel and turn it
to the "on" position to retain control of the car. Upon expiration of the
delay, without the key in the car being turned on the car shall return to
normal service.
(h) If the elevator
is an automatic car with attendant or independent service operation it shall
activate its audible and visible signal and if on attendant service shall
return to automatic operation after a minimum of 15 seconds and a maximum delay
of 60 seconds and then proceed to the main floor.
(4)
Car Operation.
(a) Upon entering the car it shall not accept
a car call until the in car EMS key switch is turned to the on position. After
turning that key on and registering a call, the car shall automatically close
its doors and proceed to the call. All door zone detection devices shall be
operative. If more than one call is registered, it shall stop at the first call
and cancel all others at which time a second choice can be made.
(b) Upon arriving at the desired floor, the
doors shall open automatically and the EMT shall remove his key when the switch
is in the off position, the car shall then remain at that floor and will not
accept a call or move away from that floor until the key is again turned
on.
(c) The car shall be returned
to the main floor on EMS service and the key removed in its off position before
returning the car to normal operation.
(d) If the car is on any form of special
service such as inspection, firefighters, or similar, when EMS service is
initiated the audible and visible signals in the car shall be activated but the
car shall not respond to the main floor EMS call.
(e) If the car has responded to a medical
emergency call prior to a call for fireman's service, the EMT call for service
shall not be overridden by firefighters service call until it returns to the
main floor but the fire service audible and visible signals shall be
activated.
(5)
Designation. Medical emergency service shall be
identified as follows:
(a) At the main floor
this elevator shall be identified by the national medical symbol (star of
life), shown below.
(b) These
symbols (two) shall be permanently attached to the hoistway door frame on each
side of that frame at right angles to the sill at a height not less than 66"
and not more than 78" above the floor level at the sill.
(c) The symbol shall be blue in color with
contrasting background, the staff and serpent shall be white.
(d) The symbol itself shall be two to three
inches in height.
EXCEPTIONS: The following elevator
installations need not comply with 2.27.12:
(a) Elevators in structures such as rock
quarries, steel towers, dams, storage bins, smoke stacks, tanks (and other
special industrial installations) where the elevators are used only by
maintenance and operating personnel, or in hospitals where the normal services
of an EMT are available.
(b)
Elevators in buildings or structures where each landing is at ground level or
is accessible to ground by a ramp.
(c) Elevators in buildings or structures
equipped with stairs that extend no more than one floor above or below the
building entrance grade and with a configuration that shall accommodate the
carrying of a gurney or stretcher on said stair and when said stair conforms to
780 CMR: State Board of Building Regulations and Standards and
is permitted by the authority having jurisdiction.