Code of Massachusetts Regulations
522 CMR - BOARD OF BOILER RULES
Title 522 CMR 4.00 - Heating Boilers and Other Heat Storage Sources
Section 4.01 - Scope and Application

Universal Citation: 522 MA Code of Regs 522.4

Current through Register 1531, September 27, 2024

(1) In accordance with the provisions of M.G.L. c. 146, § 2, the Board adopts the 2019 ASME Boiler and Pressure Vessel Code Section IV, Rules for Construction of Heating Boilers.

(2) Requirements. 522 CMR 4.00 shall apply to Boilers exceeding three horsepower and restricted to the following services:

(a) Steam Low Pressure/Heating Boilers having a minimum safety relief valve capacity greater than 200 pounds per hour for operation at pressures not exceeding 15 PSIG (100 kPa).

(b) Hot water Low Pressure/Heating Boilers and hot water supply Boilers having a minimum safety relief valve capacity greater than 200,000 BTU/hr for operation at pressures not exceeding 160 PSIG (1,100 kPa).

(c) Hot water Low Pressure/Heating Boilers and hot water supply Boilers having a minimum safety relief valve capacity greater than 200,000 BTU/hr for operation at temperatures not exceeding 250EF (120EC), at or near the Boiler outlet, except that when some of the wrought materials permitted by 2019 ASME Boiler and Pressure Vessel Code Section IV, Rules for Construction of Heating Boilers are used, a lower temperature is specified.

(d) Potable water heaters and water storage tanks for operation at pressures not exceeding 160 PSIG (1,100 kPA) and water temperatures not exceeding 210EF (99EC). 522 CMR 4.01(2)(d) shall not apply to units in this category when none of the following limitations is exceeded:
1. Heat input of 200,000 BTU/hr;

2. A water temperature of 210EF (99EC);

3. A nominal water-containing capacity of 120 gallons, except that they shall be equipped with safety devices in accordance with the requirements of the 2019 ASME Boiler and Pressure Vessel Code Section IV, Rules for Construction of Heating Boilers paragraph HLW-100.

The minimum safety valve relieving capacity for Low Pressure/Heating Boilers and other heat storage sources shall be determined in accordance with the 2019 ASME Boiler and Pressure Vessel Code Section IV, Rules for Construction of Heating Boilers.

For services exceeding these limits, the rules of the 2017 ASME Boiler and Pressure Vessel Code Section I, Rules for Construction of Power Boilers and 522 CMR 16.00: Controls and Safety Devices for Automatically Fired Boilers (ASME Code CSD-1-2015), Part CG: General, Part CM: Maintenance and Testing, Part CW: Steam and Waterside Control apply.

Boilers within the scope of 522 CMR 4.00 which were legally operating in the Commonwealth prior to January 1, 1978 and which conformed to the existing installation rules may continue in such service.

Disclaimer: These regulations may not be the most recent version. Massachusetts may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.