Code of Massachusetts Regulations
522 CMR - BOARD OF BOILER RULES
Title 522 CMR 3.00 - Power Reactor Vessels and Piping and Unfired Pressure Vessels As Used In Atomic Energy Installations
Section 3.06 - Miscellaneous Provisions

Universal Citation: 522 MA Code of Regs 522.3

Current through Register 1531, September 27, 2024

(1) The owner of a nuclear power plant shall provide a procedure by which all agency reports and data sheets shall be coordinated to the satisfaction of the Chief or his or her designee.

(2) Pressure Tests.

(a) An Authorized Nuclear Inspector may require a pressure test to determine the extent of a defect or detrimental condition found in a Pressure Vessel. Such test shall be performed in accordance with the 2019 NBIC and 2015 ASME Boiler and Pressure Vessel Code, Section III, Rules for Construction of Nuclear Facility Components.

(b) The maximum metal temperature is not to be more than 120EF, unless the Authorized Nuclear Inspector agrees to a temperature higher than 120EF.

(c) When the contents of the vessel prohibit contamination by any other medium or when a hydrostatic test is not possible, other testing media may be required by the Authorized Nuclear Inspector, provided that the precautionary requirements in the NBIC are followed.

Disclaimer: These regulations may not be the most recent version. Massachusetts may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.