Current through Register 1531, September 27, 2024
(1)
Main Burners.
(a)
Each burner assembly and its component parts shall be installed according to
the manufacturer's instructions and shall be properly and firmly secured in
place to maintain correct alignment in normal use.
(b) The burner assembly shall be installed so
that sufficient accessibility is afforded for cleaning, inspection, repair, and
replacement of all burners, controls and safety devices.
(c) Burner assembly parts, when adjustable,
shall be provided with suitable locking devices to prevent accidental
shifting.
(d) Provision shall be
made to permit ready observation of each pilot and main burner flame during
adjustment and under operating conditions.
(e) A burner assembly, when adjusted
according to the manufacturer's instruction, shall maintain satisfactory
operating characteristics as specified in
248 CMR
7.04(5) at all firing rates
called for by input and air-gas ratio controls applied to the
installation.
(2)
Control Application.
(a) Each control shall be supported in such a
manner that it and its sensing element will remain in proper position. It shall
be possible to determine by observation or test that each control is in its
proper location and capable of functioning as intended.
(b) Nothing shall be provided for the purpose
of permitting any safety control to be rendered ineffective or allowing firing
of the burner assembly without the protection of all of the specified safety
controls except as permitted by 248 CMR 7.03(2)(c).
(c) A low-water cutoff may be bypassed for
blow-down purposes only. Such a bypass shall be of a type which must be
manually held in the bypass portion and which is self-restoring when
released.
(d) A burner assembly not
equipped to provide safe automatic restarting shall be arranged to require
manual restart after any control functions to cause the fuel supply to be shut
off and the following restoration of an interrupted power supply.
(e) The safety-control circuit shall be
two-wire, one side grounded, having a nominal voltage of 150 volts or less. The
circuit shall be connected to a branch circuit that can be protected against
over current at not more than the value appropriate for the rating of the
electrical components included in the circuit.
(f) A safety control or protective device
switch shall interrupt the ungrounded conductor(s).
(g) Safety controls shall not depend on
electricity to attain the off position.
(3)
Control of Combustion
Air.
(a) An air shutter shall be
capable of being readily adjusted to any desired setting and securely locked to
prevent accidental change in setting.
(b) The air inlet(s) shall supply an adequate
amount of air for combustion under the specified draft conditions and at the
maximum firing rate of the burner assembly as installed. All air required for
combustion shall be introduced in a manner so as to provide thorough mixing of
the gas and air. If a burner is intended for installation with an air or wind
box(es), it shall be supplied by the burner manufacturer or be built in
accordance with the burner manufacturer's instructions.
(c) Linkage for controlling air and gas input
rates shall be designed to reliably maintain the correct gas-air ratio and to
resist accidental damage and disengagement.
(d) Equipment having forced or induced draft
fans or both, shall be provided with means to automatically continue safe
combustion or to shut off the gas supply upon failure of the equipment
supplying the air.
(e) If air under
pressure is mixed with the gas supply in a mixer, effective means shall be
provided to prevent air from passing back into the gas line or gas into the air
supply. The gas and air supply shall be controlled to prevent gas from entering
burners until the air supply is available and, in the event of air failure, to
shut off the gas supply.
(4)
Primary Safety Control (Flame
Safeguard).
(a) Unless a flame
safeguard control is provided by the manufacturer, each burner assembly shall
be provided with a non-recycling primary safety control that will de-energize
the main gas safety shutoff valve(s) upon loss of flame at point of
supervision.
(b) Safety control
timings shall not exceed the values given in 248 CMR 7.03: Table
1.
(c) Gas to pilots shall
be automatically shut off if the pilot is not proved, and safety shutdown
established.
(d) Pilot supervision
by the primary safety control shall be only at the point where the pilot flame
will effectively ignite the gas at the main burner or burner group with the
pilot burning at any flame that will actuate the safety control.
(e) Supervision of the main burner flame only
shall begin at the end of the main burner flame-establishing period for:
1.Power burners having a firing rate per
combustion chamber of 2,500,000 Btu per hour and over.
TABLE 1
Maximum Safety Control Timings
Maximum Firing Rate Per Combustion Chamber in Million
Btu Per Hour
|
2.5 or less
|
Over 2.5 to 12.5
|
Over 12.5
|
Pilot Flame Establishing Period
|
15 Seconds
|
10 Seconds
|
10 Seconds
|
Main Burner Flame Establishing Period (If
Required)
|
15 Seconds *
|
10 Seconds
|
10 Seconds *
|
Flame Failure Response Time
|
4 seconds
|
4 Seconds
|
4 Seconds
|
Valve Closing Time
|
5 Seconds
|
1 Second
|
1 Second
|
* Main burner flame-establishing period may be 30 seconds for
burner other than power burners equipped with a safety shutoff valve having a
full opening time of not less than 25 seconds.
2.All types of burners with modulating or
high-low firing rate per combustion chamber of 2,500,000 Btu per hour and
over.
3.All types of burners with
an interrupted pilot(s), and
4.Atmospheric type burners having a firing
rate per combustion chamber of 5,000,000 Btu per hour and over. If the main
burner flame is not proved, safety shutdown shall be established.
(f) A burner assembly shall be
equipped so that no gas can flow to the main burner on burner group operating
as a unit unless the pilot is proved.
(g) If two or more burner assemblies are
installed in a single piece of equipment, the primary safety control of each
burner assembly shall operate independently of the other, or equivalent safety
features shall be provided so that in no case can any one burner operate
unsafely.
(5)
Limit Controls.
(a)
Limit Control.
1.A
limit control shall be provided to prevent excessive steam pressure in a steam
boiler or excessive pressure or temperature in a hot water boiler.
2.Each steam and hot water boiler shall be
equipped with a control which will prevent firing of the boiler in the event of
insufficient water in the boiler.
3.The limit control shall be in addition to
operating controls. Manual restart shall be required after a pressure or
temperature limit control functions.
(b) A limit control which functions by
opening a switch shall directly open the electrical circuit to the safety
shutoff valve(s).
(6)
Combustion (Input) Control Systems.
(a) The combustion (input) control system
shall maintain predetermined air-fuel mixtures within the limits required by
the burner for stable combustion throughout the entire operating range of the
burner and during changes in the firing rate.
(b) To accomplish changes in the firing rate,
the fuel and air supplies shall be maintained at a pre-determined optimum
air-fuel ratio, either manually or automatically.
(c) Burners having a firing rate per
combustion chamber of 1,000,000 Btu per hour and over shall be equipped with a
proven low-fire start.
(d) Burners
having a firing rate per combustion chamber of 2,500,000 Btu per hour and over
shall be provided with combustion control.
(7)
Pilots.
(a) Main burners shall be equipped with a
supervised pilot adequate to provide safe main burner ignition under all
conditions of operation. Multiple burner heads operated as a single burner unit
shall use a sufficient number of supervised pilots to accomplish safe
ignition.
(b) A pilot burner not
automatically lighted shall be located so that it can be safely lighted
manually.
(c) Gas supply pressure
to the pilot or group of pilots:
1.The gas
supply pressure to the pilot or group of pilots shall be regulated.
2.The regulator(s) shall be listed; and
vented in accordance with 248 CMR 7.03(11)(c), unless constructed or equipped
to limit the escape of gas from the vent opening in the event of diaphragm
failure to not more that 2.5 cubic feet per hour.
3.The pilot supply line shall be connected
upstream of all main burner valves and the main gas pressure
regulator.
(d) Primary
air openings and orifices shall be easily accessible for servicing.
(e) An electric ignition system shall ignite
only a pilot.
(f) If means for
ignition is cut off at the termination of either the main burner
flame-establishing period, the ignition shall remain off for the duration of
that firing cycle and for the specified purge period.
(g) A pilot burner, electric igniter, and
pilot flame sensing device shall be supported in such a manner that their
position relative to each other and to the main burner port(s) will remain
fixed.
(8)
Gas Valve Pressure Ratings.
(a) Gas valves shall be capable of
withstanding without damage a pressure of not less than 10% above the relieving
pressure of the nearest upstream relief device.
(b) In case no relief device is provided, the
gas valves shall be capable of withstanding without damage a pressure of not
less than the maximum inlet pressure of the nearest upstream gas pressure
regulator or the maximum setting of the over-pressure protection
device.
(9)
Manually Operated Gas Shutoff Valves. (See
248 CMR 7.03: Figures 1 and 2.)
(a) A manually operated main burner shutoff
valve shall be installed in the line supplying all main burners of each piece
of equipment and upstream of all other main burner control valves.
(b) A manually operated main pilot shutoff
valve shall be located in the gas supply line to the pilot burner.
(c) Manually operated main shutoff and pilot
shutoff valves in sizes larger than two inches or for pressures greater than
1/2 psig shall be of the lubricated plug or ball type with stops. Manually
operated valves shall have the handle securely attached parallel to the gas
flow in the open position, shall be readily accessible, and shall clearly
indicate the "on" and "off" positions.
(d) A manually operated main burner test
valve (checking gas cock) shall be provided downstream from the safety shutoff
valve for each main burner. On manually lighted burners, the valves shall be
interlocked with the safety control circuit and arranged so that the main
burner safety shutoff valves must be opened against their associated closed
test valves.
(e) In multiple burner
installations a manual valve shall be provided for each main and each pilot
burner except those utilizing a single zero governor inspirator mixer for
several burners in which case this valve shall be located at a point
immediately upstream of the zero governor.
(f) Provisions shall be made so that the gas
supply to equipment may be shut off from a location outside the room where said
equipment is located.
FIGURE 1
Illustration of Manual Valving Arrangement for a Multiple
Burner, Single Boiler Arrangement
Click to view
image
FIGURE 2
Illustration of Manual Valving Arrangement for a Multiple
Burner, Single Boiler Arrangement
Click to view
image
(10)
Control and Safety Shutoff
Valves. (See 248 CMR 7.03: Figure
3.)
(a) An automatic input control
valve may be in combination with a safety shutoff valve.
(b) A bypass to provide for minimum flame may
be installed around a valve to control input only. A bypass shall not be
installed around a safety shutoff valve or a combustion input control and
safety shutoff valve.
(c)
Safety Valves:
1.Each main burner supply line and each pilot
supply line shall be equipped with a safety shutoff valve(s) which will close
independent of external force.
2.The safety shutoff valve(s) shall close
with sufficient force to provide tight shutoff under normal operating
conditions and when closed by the safety control system or by an emergency
device.
3.If the maximum firing
rate per combustion chamber exceeds 1,000,000 BTU/hour, the main burner supply
line shall be equipped as indicated in 248 CMR 7.03(10)(c)3.a. and b.:
a.Two safety shutoff valves, in series, or
one safety shutoff valve of the type incorporating a valve seal overtravel
interlock, when the maximum firing rate per combustion chamber exceeds
1,000,000 BTU/hour but less than 5,000,000 BTU/hour.
b.Two safety shutoff valves, in series, one
of which is of the type incorporating a valve seal overtravel interlock when
the maximum firing rate per combustion chamber exceeds 5,000,000 BTU/hour.
The Board may prescribe two safety shutoff valves in series,
for combustion chambers with inputs less than 1,000,000 BTU/hour, in buildings
of public assembly.
(d) Safety shutoff valves shall be suitable
for the application and shall have a shutoff time not to exceed that specified
in 248 CMR 7.03: Table 1. They shall be constructed so that
they cannot be restrained or blocked in the open position. Such valves shall
close upon being de-energized regardless of the positions of damper-operating
levers or reset handles.
(e) An
electrically operated safety shutoff valve shall not depend on electricity to
shut off the gas supply.
(f) A
pressure-operated safety shutoff valve shall close upon failure of its
operating pressure.
(g) Permanent
and ready means for making easy, accurate, periodic tightness tests of the main
burner gas safety shutoff valves shall be provided in the piping.
FIGURE 3A.
Illustration of Gas Train
248 CMR 3.00 through
7.00 requirements 400,000 to
Less Than 1,000,000 BTU/hour Input
Click to view
image
FIGURE 3B.
Illustration of Gas Train
248 CMR 3.00 through
7.00 1,000,000 to Less Than
2,500,000 BTU/hour Input
Click to view
image
FIGURE 3C.
Illustration of Gas Train
248 CMR 3.00 through
7.00 requirements for
2,500,000 to less than 5,000,000 BTU/hour Input
Click to view
image
FIGURE 3D
Illustration of Gas Train
248 CMR 3.00 through
7.00 requirements for
5,000,000 to less than 12,500,000 BTU/hour Input
Click to view
image
(11)
Main Gas Pressure Regulators
and Gas Pressure Interlocks.
(a)
Each burner assembly shall be equipped with a listed main gas pressure
regulator that will regulate within plus or minus 10% of the operating pressure
at all firing rates. (See 248 CMR 7.03: Figure 3
for location).
(b) Spring
or weight-loaded regulators shall have springs covered by a suitable housing.
Under no circumstances shall a weight and lever type of regulator be
used.
(c)
Main Gas
Pressure Regulators:
1.Except
where zero governors are used in connection with air-gas mixers, all main gas
pressure regulators shall be independently vented to a safe outdoor
location.
2.Vent lines from main
gas pressure regulators shall not be connected into a common line with the
bleed line from gas operated diaphragm valves or from pressure relief
valves.
3.Vent lines shall be
steel, wrought iron pipe or corrugated stainless steel tubing (CSST) with
Product-approved devices provided at termination points to prevent stoppage of
the lines by foreign material, water or insects and, shall extend no less than
18 inches above the roof surface.
4.Vent lines shall be sized as specified in
248 CMR 7.03: Table 2.
5.Vent lines shall be supported in accordance
with 248 CMR 1.00 through
10.00.
6.Vent lines shall be run to the outside
using the shortest practical route and shall not be trapped or installed in a
manner that restricts air-flow.
7.Vent lines that penetrate roofs and
sidewalls shall be run through metallic sleeves that are sealed from the
weather and insects.
8.CSST vent
lines that penetrate roofs shall transition to steel pipe no less than one foot
inside the building.
9.Vent lines
that terminate outside a building shall be located no less than four-feet away
from any building opening or air intake and ten feet away from forced air
intakes. Outside
(d)
Pressure Switches.
1.If the maximum firing rate per combustion
chamber is 1,000,000 BTU/hour or over, gas pressure supervision shall be
provided by listed pressure switches, or listed combination high-low switch,
interlocked to accomplish a non-recycling safety shutdown in the event of
either high or low gas pressure.
2.Pressure setting shall be adjusted by the
installer in accordance with the burner or equipment manufacturer's
instructions.
3.Pressure switches
that require venting to the outside atmosphere shall be vented in accordance
with 248 CMR 7.03(11)(c). Pressure switches only may be manifolded.
(e) Accessible IPS plugged
pressure tappings or connections shall be provided; one located upstream of the
main gas pressure regulator and another located near the burner head to permit
accurate measurement of gas pressure. (
See 248 CMR 7.03:
Figure 3.)
TABLE 2
Minimum Pipe Size/CSST for Venting
Gas Train Components in
248 CMR
7.04 Figures 3a, 3b, 3c, and 3d.
Gas Train Components
|
Maximum lengths of iron pipe or corrugated stainless
steel tubing (CSST) from components to outside the building
|
0 - 40 feet
|
0 - 100 feet
|
0 - 200 Feet
|
Main Gas Pressure Regulator
- Steel Pipe Size
- CSST Size (Low Pressure Gas only)
|
3/4 inch IPS 30/31 EHD
|
1 inch IPS 37 EHD
|
11/4 inch IPS 46/48 EHD
|
High & Low Gas Pressure Switches When
Manifolded
- Steel Pipe Size
- CSST Size (Low Pressure Gas only
|
3/4 inch IPS 30/31 EHD
|
1 inch IPS 37 EHD
|
11/2 inch IPS 60/62 EHD
|
Block and Bleed Valves (when used)
- Steel Pipe Size
- CSST Size (Low Pressure Gas only
|
Full IPS Relief
|
Increase IPS/CSST one Size
|
Increase IPS/CSST two Sizes
|
(12)
Operating
Sequencing. (See also
248 CMR
7.04, Initial Start-Up and Final
Adjustments).
Each installation shall be equipped to provide for sequencing
in accordance with the following and in the order listed.
(a) Natural and mechanical draft systems with
continuously burning pilot(s) capable of igniting any gas flowing from the main
burner shall, upon demand for heat:
1.Prove
all interlocks.
2.Prove combustion
air flow for mechanical draft systems.
3.Prove in light-off position, if either an
automatically operated damper, or an automatically operated air shutter, or
both, are employed.
4.Prove
combustion (input) control, if employed, in light-off position.
5.Prove pilot(s).
6.Admit fuel to main burner.
7.Prove main flame, if required, in
accordance with 248 CMR 7.03(4)(e).
8.Release combustion (input)
control.
9.Upon flame failure at
point of supervision, shut off fuel by primary safety control.
10.Shut off fuel to main burner on release
from demand.
(b) Natural
draft systems with intermittent pilot or interrupted pilot shall, upon demand
for heat:
1.Prove all interlocks.
2.Prove open for at least 90 seconds if
either an automatically operated damper, an automatically operated air shutter,
or both, are employed.
3.Prove in
the light-off position if either an automatically operated damper, and
automatically operated air shutter, or both are employed.
4.Prove combustion (input) control, if
employed, in light-off position.
5.Prove pilot(s).
6.Admit fuel to main burner.
7.Prove main flame, if required, in
accordance with 248 CMR 7.03(4)(e).
8.Release combustion (input)
control.
9.Upon flame failure at
point of supervision, shut off fuel by primary safety control.
10.Shut off fuel on release from
demand.
11.If an automatically
operated damper is employed, return to stand-by position.
(c) Mechanical draft systems with
intermittent pilot or interrupted pilot shall, on demand:
1.Prove all interlocks.
2.If an automatically operated damper is
employed, prove in open position.
3.Start fan(s) and prove air flow. Provide at
least a four-air change purge of the combustion chamber and equipment passes.
The four air changes must be accomplished in not more than 90 seconds with
burners having maximum firing rate per combustion chamber of not more than
2,500,000 Btu per hour. With burners having maximum firing rates per combustion
chamber in excess of 2,500,000 Btu per hour, the four air changes shall be
accomplished without time limitation by an air flow rate not less than 60% of
the air flow provided for the maximum firing rate.
4.Prove combustion (input) control and
automatically operated damper, if employed, in light-off position.
5.Prove pilot(s).
6.Admit fuel to main burner.
7.Prove main flame, if required, in
accordance with 248 CMR 7.03(4)(e).
8.Release combustion (input)
control.
9.Upon flame failure at
point of supervision, shut off fuel by primary safety control.
10.Shut off fuel on release from
demand.
11.If an automatically
operated damper is employed, return to stand-by position.