Code of Massachusetts Regulations
248 CMR - BOARD OF STATE EXAMINERS OF PLUMBERS AND GAS FITTERS
Title 248 CMR 7.00 - Large Gas Utilization Equipment
Section 7.02 - General Provisions
Universal Citation: 248 MA Code of Regs 248.7
Current through Register 1531, September 27, 2024
(1) Before arranging for the selection or installation of large gas equipment, the licensed plumber or gas fitter shall check with the serving gas supplier as to the availability of gas, specifying the gas input rating and the gas pressure required at the entrance to gas train. (See 248 CMR 7.03: Figure 3).
(2) Combustion Air Supply and Ventilation.
(a)
General.
1.Figure 3
in Positive means for supplying an ample amount of outside air to permit
combustion of the gas shall be provided. Automatic or manually adjustable
control devices for outside air intake shall be interlocked with the
burner.
2.To determine air
requirements at the equipment, under standard atmospheric conditions (60EF and
30 inches mercury), the following minimum factors apply:
a.For equipment with draft hoods - 30 cubic
feet per 1000 Btu input;
b.or
equipment directly connected to a chimney without neutralizing air openings -
12 cubic feet per 1000 Btu input.
3.When equipment is located in an inside room
or space, air supply shall be provided through ducts or openings leading to the
outside air.
4.Openings to the
outside shall be unobstructed and screens, if used, shall have a minimum of
1/2 inch mesh.
5.When a room
or space in which equipment is installed is ventilated by mechanical means, air
sufficient to replace that exhausted and consumed by combustion shall be
supplied from a safe, uncontaminated source. The means for ventilation shall
not create an unsafe pressure condition in the boiler room.
6.In addition to the combustion air required,
sufficient air shall be supplied to the room to make the room safe for
occupancy and proper operation of equipment.
(b)
Equipment Equipped with Draft
Hoods.
1.The effective
cross-sectional area of the permanent outside air opening(s) to the room where
equipment is located shall be large enough to supply the air required in that
room.
2.For supplying combustion
air, the area of the opening shall be of a size at least equal to the equipment
breeching but not less than one square inch of free area per 5,000 Btu per hour
input (approximately equal to 1.4 square feet per million Btu), except as noted
in 248 CMR 7.02(2)(e).
(c)
Equipment Utilizing
Barometric Dampers.
1.The
effective cross-sectional area of the permanent outside air opening(s) to the
room where the equipment is located shall be large enough to supply the air
required in that room.
2.For
supplying air, the area of the opening shall be of a size at least equal to the
equipment breeching but not less than one square inch of free area per 14,000
Btu per hour input (approximately equal to 0.5 square foot per million Btu),
except as noted in 248 CMR 7.02(2)(e).
(d)
Equipment Directly Connected
to Chimney without Neutralizing Air Openings.
1.The effective cross-sectional area of the
permanent outside air opening(s) to the room where the equipment is located
shall be large enough to supply the air required in that room.
2.For supplying air, the area of the opening
shall be of a size at least equal to the equipment breeching but not less than
one square inch of free area per 17,500 Btu per hour input (approximately equal
to 0.4 square foot per million Btu), except as noted in 248 CMR
7.02(2)(e).
(e)
Exceptions.
1.Ducts to a Room where Equipment
is Located: In determining the cross-sectional area of duct(s)
used to convey air from the outdoors to the boiler room, the resistance to air
flow imposed by the duct(s) shall be considered.
2.Forced Air Supply to a Room
where Equipment is Located: If mechanical means for room air
supply are used, the size of the duct or opening may be reduced to not less
than that needed to provide the required quantity of air.
(3) Accessibility for Cleaning and Inspection. Sufficient and reasonable accessibility shall be offered for Inspection, cleaning, repair and replacement of all burners, combustion controls, safety devices and boiler components.
(4) Venting of Flue Gases.
(a)
Chimneys.
1.All
equipment shall be securely connected to a chimney in good condition and of
proper construction and ample size to carry away the flue gases and permit
satisfactory burner operation under all weather and operating
conditions.
2.The chimney shall be
designed and built to sufficiently remove the maximum volume of flue gases
which may be produced by the equipment connected to it, as well as any other
combustion equipment, under the least conditions of draft which can be
encountered. The design should also provide proper construction to resist wind
forces, weathering, interior corrosion and flue gas temperatures.
3.The chimney shall be pre-inspected and, if
necessary, tested to determine whether it is in suitable condition to handle
the flue gases to be dispersed. Any defects shall be corrected.
4.An existing chimney shall be checked as to
cross-sectional area, arrangement, and height to determine if it will
sufficiently remove the volume of flue gases produced by the equipment, under
the least condition of draft that may be encountered. This shall include
consideration of pressure and temperature conditions at which the flue gases
enter the chimney and the effect of flue gases which may be fed into the
chimney from other combustion equipment.
(b)
Chimney
Connectors.
1.Connectors from
equipment to a chimney shall be of noncombustible material capable of
withstanding the corrosion effects and temperatures of the flue gases to be
handled. They shall have sufficient strength to withstand the physical stresses
likely to occur under the conditions of use and shall be securely
supported.
2.The connector shall be
installed so as to avoid excessive turns or other construction features which
create unnecessary resistance to flow of flue gases.
3.The joint between the connector and the
chimney shall be sealed to prevent gas leakage or air infiltration.
4.A connector shall not extend into a chimney
beyond the inner wall of the chimney flue.
5.The connector shall be sized as recommended
by the equipment or burner manufacturer. If the manufacturer's recommendations
are not available, the connector shall be the size of the flue collar, or if a
draft hood is used, shall be the size of the outlet of the draft hood unless
the connector is designed and installed in accordance with industry recognized
and approved engineering methods.
6.On multiple installations, separate
connectors should be run to the chimney. When this is not practical, each
connector shall be y-connected to a common breeching, the cross-sectional area
of which shall be not less than the combined areas of the individual
connectors.
(c)
Draft Control.
1.Equipment requiring controlled chimney
draft shall be capable of automatically regulating the draft as recommended by
the equipment manufacturer. Such controls may be of the barometric type which
regulates the draft in the breeching or the mechanically operated damper type
which controls the pressure in the equipment firebox or the draft hood type
which is nonadjustable.
2.A
double-acting barometric draft regulator, if used, shall be equipped with a
device with a manual reset which will automatically shut off the fuel to the
burner in the event flue gas spillage exceeds 60 seconds.
3.Mechanically operated dampers shall be
designed to maintain a safe damper opening at all times and be arranged to
prevent firing of the burner unless the damper is in the proper
position.
4.Draft
Control:
a.When a draft control
device is used, it shall be installed without alteration in accordance with the
manufacturer's instructions.
b.In
no case shall a barometric draft control device be installed in a false
ceiling, in a different room or in any place or manner that will permit a
difference in pressure between a draft relief opening and the combustion air
supply.
c.A draft control device
shall be installed in the position for which it was designed with reference to
the horizontal and vertical planes and shall be located so that a relief
opening is not obstructed.
d.When
induced or forced draft devices are used, provision shall be made to prevent
flow of gas to the burners upon failure of these devices.
5.Adjustable manual dampers should be removed
except when a damper must be used to control excess chimney draft. Positive
means shall then be provided to lock the damper in the proper position by
welding or riveting. As an alternate, a portion of the damper can be removed to
prevent full closure.
6.Full
closing outlet isolation dampers shall be interlocked so that the boiler firing
system cannot be operated unless its isolation damper is in the proper open
position.
7.Adjustable (modulating)
dampers, shall be arranged to maintain a safe fuel-air ratio over the full
operating range. Linkage shall be arranged to resist accidental damage and
disengagement. Any counter-balancing arms or weights attached to the damper
shall be located or shielded as to prevent personal injury or damage to
equipment in case of breakage.
8.When a draft hood is used, it shall be
installed without alteration in accordance with the manufacturer's
instructions. In no case shall a draft hood be installed in a false ceiling, in
a different room, or in a manner that will permit a difference in pressure
between the draft hood relief opening and the combustion air supply.
Disclaimer: These regulations may not be the most recent version. Massachusetts may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google
Privacy Policy and
Terms of Service apply.