Code of Massachusetts Regulations
220 CMR - DEPARTMENT OF PUBLIC UTILITIES
Title 220 CMR 126.00 - Underground Electric Supply And Communication Lines 50,000 Volts And Below
Section 126.34 - Cable in Conduit Systems
Current through Register 1531, September 27, 2024
(1) General. On systems operating above 2 KV to ground, the design of the conductors or cables installed in non-metallic conduit should consider the need for an effectively grounded shield and/or sheath.
(2) Installation.
Exception: 220 CMR 126.34(2)(b) does not apply to grounding or bonding conductors.
Where cable and/or equipment is to be installed in a joint use manhole or vault, it shall be done only with the concurrence of all parties concerned.
Supply and communication cables should be racked from separate walls. Crossings should be avoided.
Where supply and communication cables must be racked from the same wall, the supply cables should be racked below the communication cables.
Supply and communication facilities shall be installed to permit access to either without moving the other.
Clearances shall be maintained as specified in 220 CMR 126.34: Table 1.
Table 1
Minimum Separation Between Supply and Communications Facilities in Joint Use Manholes and Vaults
Phase-to-Phase Supply Voltage |
Inches of Separation (Surface to Surface) |
0, to 15,000 |
6 |
15,001 to 50,000 |
9 |
Exception 1: These separations do not apply to grounding conductors.
Exception 2: These separations may be reduced by mutual agreement between the parties concerned when suitable barriers or guards are installed.
Exception: 220 CMR 126.34(2)(d) i. does not apply where the position of a cable, in conjunction with diagrams or maps supplied to workmen, or other means give sufficient identification.
(3) Grounding and Bonding.
(4) Fire-proofing. Although fire-proofing is not a requirement, it may be provided in accordance with each utility's normal service reliability practice to provide protection from external fire.
(5) Communication Cables Containing Special Supply Circuits. Special circuits operating at voltages in excess of 400 volts to ground and used for supplying power solely to communications equipment may be included in communications cables under the following conditions:
Exception: The requirements of 220 CMR 126.34(5) do not apply to supply circuits of 550 volts or less which carry power not in excess of 3200 watts.