Title 220 CMR 125.00 - Installation And Maintenance Of Electric Transmission Lines
Section 125.31 - Construction of Duct and Cable Systems
Current through Register 1531, September 27, 2024
(1) Material, Size, and Finish of Ducts. Ducts shall be of such material, size, mechanical strength, and finish as to facilitate the installation and maintenance of conductors or cables. Ducts shall be freed from burrs before laying and shall have clear bores.
(2) Grading of Ducts. Where it is necessary to drain ducts, the grade of the ducts shall be such as to permit proper and adequate drainage.
(3) Settling. Ducts should be suitably reinforced or be laid on suitable foundations of sufficient mechanical strength where necessary to protect them from settling.
(4) Clearances.
Exception: Where this is impracticable, or for other reasons, this clearance may be reduced by agreement between the parties concerned. In no case, however, shall the top of the conduit protection extend higher than the bottom of the ballast section which is subject to working or cleaning.
(5) Duct Entrances into Manholes. Iron pipe conduit terminating in manholes, hand holes or other permanent openings of underground systems, shall be provided with an effective shield, bushing, fair leader, or other smooth outlet.
(6) Duct Arrangement for Dissipation of Heat. Duct systems intended to carry transmission cables of large current capacity should be arranged, where practicable, so that ducts carrying such cables will not dissipate their heat solely through other ducts.