Code of Massachusetts Regulations
220 CMR - DEPARTMENT OF PUBLIC UTILITIES
Title 220 CMR 109.00 - Design, Construction, Operation and Maintenance of Intrastate Pipelines Operating In Excess of 200 PSIG
Section 109.12 - Valves
Current through Register 1531, September 27, 2024
(1) Each valve installed on a pipeline shall comply with the following:
(2) Each pipeline shall have sectionalizing block valves spaced so that each point on the pipeline is within four miles of a sectionalizing block valve. If the pipeline passes through an area designated as a Class 4 location, as defined in 49 CFR 192.5, the federal transmission line spacing requirements shall be applicable, as set forth in 49 CFR 192.179(a)(1).
(3) Each section of a pipeline located between sectionalizing block valves shall have a blow-down valve. Each blow-down valve shall be sized so as to reduce the time needed to reduce the pressure in the pipeline safely and quickly. The discharge point of each blow-down valve shall be located to minimize the hazard to the public in the event gas is vented to the atmosphere.
(4) Where practicable, each regulating station that supplies gas to a pipeline shall have a valve in the pipe supplying the regulating station, provided that the pipe is owned by an operator under the jurisdiction of the Department. The valve shall be located where it can be operated during an event that could preclude access to the station.