Code of Massachusetts Regulations
105 CMR - DEPARTMENT OF PUBLIC HEALTH
Title 105 CMR 675.000 - Requirements To Maintain Airqualityin Indoorskating Rinks (state Sanitary Code, Chapter Xi)
Section 675.009 - Required Corrective Measures
Current through Register 1531, September 27, 2024
If an air sample taken in accordance with the requirements of 105 CMR 675.000 reveals that the air level of carbon monoxide or nitrogen dioxide exceed the correction air levels of 105 CMR 675.008(A), the operator shall take both immediate corrective measures as described in 105 CMR 675.009(A) as well as one or more appropriate long term measures as described in 105 CMR 675,009(B).
(A) Immediate Corrective Measures. The operator shall immediately take steps to increase the ventilation in the indoor skating rink through any appropriate and safe means, and shall continue to ventilate the indoor skating rink at above normal rates or through extraordinary means until such time as a subsequent air sample taken by the operator reveals that air levels of carbon monoxide or nitrogen dioxide are below the correction air levels of 105 CMR 675.008(A). The operator shall take one or more follow-up air samples in intervals of 20 minutes or less after the taking of any sample which had revealed an exceedance of the correction air levels of 105 CMR 675,008(A) until such time as a follow-up air sample reveals that the air level of the contaminant(s) for which there was an exceedance have been reduced below the correction air levels of 105 CMR 675.008(A). The operator shall record the results of each follow-up air sample in the Record Keeping Log as well.
(B) Long Term Corrective Measures. The operator shall, as soon as reasonably practical, take one or more of the following steps to eliminate the problem which resulted in an exceedance of the correction air levels of 105 CMR 675.008(A) and to prevent any future exceedances of these levels: