Section 450.330 - Heating

Universal Citation: 105 MA Code of Regs 105.450
Current through Register 1531, September 27, 2024

Each facility shall provide heat for every bed room, bathroom and toilet compartment, and other habitable area, at a temperature of at least 68°F between 7:00 AM. and 11:00 P.M. and at least 64°F between 11:01 P.M. and 6:59 AM., every day other than during the period of June 15th through September 15th, in each year. The temperature shall at no time exceed 78 F during the heating season. For each degree less than -15°F that the temperature falls, the minimum temperature requirements may likewise be reduced by 1°F. The temperature shall be read at a height of three feet above floor level at any point in the room more than two feet from the inside of every exterior wall.

Disclaimer: These regulations may not be the most recent version. Massachusetts may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.