Code of Massachusetts Regulations
105 CMR - DEPARTMENT OF PUBLIC HEALTH
Title 105 CMR 410.000 - Minimum Standards of Fitness for Human Habitation, State Sanitary Code, Chapter II
Section 410.280 - Natural and Mechanical Ventilation

Universal Citation: 105 MA Code of Regs 105.410

Current through Register 1531, September 27, 2024

The owner shall provide for each habitable room, and room containing a toilet, bathtub or shower, ventilation to the outdoors consisting of:

(A) windows, skylights, doors or transoms in the exterior walls or roofs that can be easily opened to a minimum of 4% of the floor area of that habitable room or room containing a toilet, bathtub or shower, provided, that a skylight which if open exposes the interior of the dwelling to direct rainfall shall not satisfy this requirement; or

(B) Mechanical ventilation capable of exhausting air at the following rates:

Occupancy Classification

Required Air Changes Per Hour

Habitable rooms other than bath, toilet or shower rooms

2

Bath, toilet or shower rooms

5

Disclaimer: These regulations may not be the most recent version. Massachusetts may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.