Section 410.220 - Natural and Mechanical Ventilation
Universal Citation: 105 MA Code of Regs 105.410
Current through Register 1531, September 27, 2024
(A) Habitable rooms, and rooms with a toilet, bathtub or shower shall have:
(1) Windows, skylights, or doors through the
exterior walls or roofs that can be easily opened with a combined opening of at
least 4% of the floor area of that habitable room or room containing a toilet,
bathtub or shower; or
(2)
Mechanical ventilation capable of exhausting air to the outdoors.
(B) When the board of health has determined that natural ventilation is insufficient to remove excess moisture, mechanical ventilation is required.
(C) Mechanical ventilation shall be installed and maintained in accordance with 780 CMR: Massachusetts State Building Code.
(D) Each mechanical ventilation system shall be equipped with a readily accessible means for shut-off, unless such system is designed to run constantly or is barometrically controlled.
Disclaimer: These regulations may not be the most recent version. Massachusetts may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.