Section 150.700 - Heating and Air Conditioning Systems

Universal Citation: 105 MA Code of Regs 105.150

Current through Register 1531, September 27, 2024

(A) Every facility shall be equipped with a heating system which is sufficient to maintain a minimum temperature of 75/F throughout the facility at all times at winter design temperatures.

(B) Heating fixtures and all exposed pipes shall be shielded for the safety of residents.

(C) Each heating fixture shall be equipped with hand controls unless an individual automatic room control is provided.

(D) Every facility whose architectural plans are approved after the promulgation of 105 CMR 150.700(D) for new construction or major renovations such as the installation of a heating air conditioning and ventilation system or complete interior reconstruction shall be equipped with a cooling system which is capable of maintaining a maximum temperature of 75/F throughout the resident areas affected by the new construction or renovation at all times at summer design temperatures. Temperatures must be maintained at a level which ensures the comfort and health of residents of the facility.

Disclaimer: These regulations may not be the most recent version. Massachusetts may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.