Section 150.600 - Corridors

Universal Citation: 105 MA Code of Regs 105.150

Current through Register 1531, September 27, 2024

(A) Corridors.

(1) Corridors in areas used primarily by residents in nursing homes shall not be less than eight feet wide. Corridor width in all other corridors shall comply with 780 CMR 10.00: Means of Egress and International Building Code section 1018.2.

(2) Existing corridors in an HB/LTCF may be retained as long as they are at least four feet wide.

(B) Handrails shall be provided on both sides of corridors. Handrails shall be firmly anchored and shall not project more than 31/2 inches into the required minimum width of the corridor and shall be no less than 30 inches above the finished floor. They shall have curved returns.

(C) A facility shall not permit the installation of any fixed appurtenance with may become an obstacle to traffic or reduce the required minimum width of corridor, ramp or stair.

Disclaimer: These regulations may not be the most recent version. Massachusetts may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.