Code of Maryland Regulations
Title 29 - MARYLAND STATE POLICE
Subtitle 06 - FIRE PREVENTION COMMISSION
Chapter 29.06.07 - Ground-Based Sparkling Devices
Section 29.06.07.13 - Generators

Universal Citation: MD Code Reg 29.06.07.13

Current through Register Vol. 51, No. 6, March 22, 2024

A. Scope. This regulation does not limit the type and quantity of fuel for generators and their fuel storage located not less than 50 feet from the exterior of the sales or distribution facility.

B. Generators using flammable or combustible liquid or gas fuels supplying power to ground-based sparkling devices sales or distribution facilities may not be located less than 20 feet from the exterior of the sales or distribution facility.

C. Combustible and flammable liquid generator fuel may not:

(1) Exceed 5 gallons; or

(2) Be stored less than 20 feet from the exterior of a sales or distribution facility.

D. Flammable gas generator fuel may not:

(1) Exceed 20 pounds; or

(2) Be stored less than 20 feet from the exterior of a sales or distribution facility.

Disclaimer: These regulations may not be the most recent version. Maryland may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.