Section 09.17.02.07 - Automatic Shutdown
Universal Citation: MD Code Reg 09.17.02.07
Current through Register Vol. 51, No. 19, September 20, 2024
A computerized monitoring system shall be equipped with an automatic burner shutdown mechanism that will activate when:
A. Stack flue gas reaches high temperature; and
B. One of the following occurs, as applicable:
(1) For a steam boiler:
(a) Steam reaches high pressure; or
(b) Water reaches Low or high
level;
(2) For a hot
water boiler operating at 30 to 299 horsepower, water reaches high temperature;
or
(3) For a hot water boiler
operating at 300 or more horsepower, water reaches:
(a) High pressure;
(b) High temperature; or
(c) Low level.
Disclaimer: These regulations may not be the most recent version. Maryland may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.