Code of Maryland Regulations
Title 09 - MARYLAND DEPARTMENT OF LABOR
Subtitle 17 - BOARD OF STATIONARY ENGINEERS
Chapter 09.17.02 - Computerized Monitoring System
Section 09.17.02.06 - Alarm

Universal Citation: MD Code Reg 09.17.02.06

Current through Register Vol. 51, No. 19, September 20, 2024

A computerized monitoring system shall be equipped with an alarm that will activate when:

A. The stack flue gas reaches a high temperature;

B. The burner status indicator indicates the burner is "off";

C. The flame safety control status indicates a "flame failure"; and

D. One of the following occurs, as applicable:

(1) For steam boilers, the:
(a) Steam reaches low or high pressure; or

(b) Water reaches low or high level;

(2) For a hot water boiler operating at 30 to 299 horsepower, the water reaches low or high temperature; or

(3) For a hot water boiler operating at 300 or more horsepower the water reaches low or high:
(a) Pressure;

(b) Temperature; or

(c) Level.

Disclaimer: These regulations may not be the most recent version. Maryland may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.