A. Nonstandard Construction.
(1) Except as otherwise provided in this
regulation, the age limit of a boiler of nonstandard construction installed
before the Act became effective shall be 30 years.
(2) A boiler of nonstandard construction
installed before the Act became effective, not having a lap-riveted
longitudinal joint, may continue to operate for more than 30 years without
reduction in working pressure after a:
(a)
Thorough internal and external inspection; and
(b) Hydrostatic pressure test at 1-1/2 times
the allowable working pressure, held for a period of at least 30 minutes,
during which no distress or leakage develops.
(3) A boiler having a lap-riveted
longitudinal joint, which operates at a pressure greater than 50 PSI, has an
age limit of 20 years.
(4) The
chief boiler inspector may authorize a reasonable time for replacement, not to
exceed 1 year.
B. Standard Construction.
(1) The age limit of a
boiler of standard construction installed before July 1, 1969 shall be
determined by a:
(a) Thorough internal and
external inspection; and
(b)
Hydrostatic pressure test conducted at 1-1/2 times the maximum allowable
working pressure, with water temperature between 70°F and 140°F and not
less than the nil ductility temperature of the material.
(2) A boiler that exhibits no distress or
leakage under test conditions may continue in operation at the same working
pressure.
C. The shell or drum of a boiler having a lap-seam crack along a longitudinal riveted joint in either a butt seam or a lap joint may not be used under steam pressure.
Disclaimer: These regulations may not be the most recent version. Maryland may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.