Section 09.12.01.30 - Stamping

Universal Citation: MD Code Reg 09.12.01.30

Current through Register Vol. 51, No. 6, March 22, 2024

A. At the first post-installation internal or certificate inspection, the inspector shall assign to a boiler or pressure vessel a Maryland serial number that is:

(1) At least 5/16 of an inch in height;

(2) Configured as follows:
(a) For power boilers ----- MD 0000,

(b) For heating boilers --- MD 0000H,

(c) For pressure vessels -- MD 0000V,

(d) For nuclear vessels --- MD 0000N; and

(3) Stamped on:
(a) The boiler or pressure vessel, or

(b) A metal tag at least 1 inch in height, securely attached to the front of:
(i) A low pressure heating boiler constructed of cast iron, or

(ii) A pressure vessel constructed of cast iron or other material of a thickness that should not be stamped.

B. Unless a record is kept showing the location of stamping so that the stamping can be uncovered readily, stamping:

(1) May not be concealed by lagging or paint; and

(2) Shall be exposed at all times.

C. When a boiler or pressure vessel stamp is indistinct:

(1) An inspector shall direct the owner to have the boiler or pressure vessel restamped;

(2) The owner shall:
(a) Request from the chief boiler inspector permission to restamp, and

(b) Submit with the request, proof of the original stamp; and

(3) If the chief boiler inspector authorizes restamping, an inspector shall:
(a) Observe the restamping, and

(b) File with the chief boiler inspector notice of the restamping, and a facsimile of the stamp applied.

D. A condemned boiler or pressure vessel shall be stamped with:

(1) Letters 5/16 of an inch in height; and

(2) The configuration XXX MD XXX.

Disclaimer: These regulations may not be the most recent version. Maryland may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.