Code of Maine Rules
02 - DEPARTMENT OF PROFESSIONAL AND FINANCIAL REGULATION
385 - MANUFACTURED HOUSING BOARD
Chapter 890 - MANUFACTURED HOME INSTALLATION STANDARDS
Subchapter G - DUCTWORK AND PLUMBING AND FUEL SUPPLY SYSTEMS
Section 385-890-G-III - Water Supply
Current through 2024-38, September 18, 2024
A. Crossover
Multi-section homes with plumbing in both sections require water-line crossover connections to join all sections of the home.The crossover design requirements are located in, and must be designed in accordance with part 3280.609.
B. Maximum Supply Pressure and Reduction
When the local water supply pressure exceeds 80 psi to the manufactured home, a pressure-reducing valve must be installed.
C. Mandatory Shutoff Valve
D. Wells as a Source of Supply
A well shall not be located within the boundaries of a manufactured home pad.
E. Freezing Protection
Water line crossovers completed during installation must be protected from freezing. The freeze protection design requirements are located in, and must be designed in accordance with the requirements of part 3280.603.
Only pipe heating cable listed for manufactured home use is permitted to be used, and it must be installed in accordance with the cable manufacturer installation instructions.
F. Testing Procedures