Section 385-890-D-XI - Required Perimeter Supports
Universal Citation: 02 ME Code Rules ยง 385-890-D-XI
Current through 2024-38, September 18, 2024
A. Perimeter pier or other supports must be located as follows:
1. On both sides of side wall exterior doors
(such as entry, patio, and sliding glass doors) and any other side wall
openings of 48 inches or greater in width, and under load-bearing porch posts,
factory installed fireplaces, and fireplace stoves.)
2. Other perimeter supports must be:
a. Located in accordance with Table 2 to
Subchapter D, Section
III; or
b. Provided by other means such as additional
outriggers or floor joists.When this alternative is used, the design required
by Subchapter D, Section
I must consider the additional loads
in sizing the pier and footing supports under the main chassis beam.
B. For roof live loads of 40 psf or greater, a professional registered engineer or professional architect must determine the maximum sidewall opening permitted without perimeter pier or other supports.
C. The location and installation of any perimeter pier support must not take the home out of compliance with the Manufactured Home Construction and Safety Standards (part 3280).
Disclaimer: These regulations may not be the most recent version. Maine may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.