Louisiana Administrative Code
Title 56 - PUBLIC WORKS
Part I - Water Wells
Chapter 3 - Water Well Construction
Section I-315 - Location in Relation to Possible Sources of Contamination

Universal Citation: LA Admin Code I-315

Current through Register Vol. 50, No. 9, September 20, 2024

A. The horizontal distance between any water well and any possible sources of contamination shall be as great as possible but in no case less than the following minimum distances.

Possible Sources of Contamination

Minimum Distance (in feet)

Septic Tanks

50

Storm or Sanitary Sewer

501

Cesspools, outdoor privies, oxidation ponds, subsurface absorption fields, pits, etc.

1002

Sanitary landfills, feed lots, manure piles, solid-waste dumps and similar installations

100

Another water well

253

Drainage canal, ditch, stream, pond or lake

504

1 This distance may be reduced to 30 feet if the sewer is of cast iron with leaded joints or schedule 40 plastic pipe with water-tight joints.

2 For domestic water wells, this distance may be reduced to 50 feet.

3 This minimum distance requirement does not take into consideration the effects of interference from pumping nearby wells in the same aquifer.

4 Horizontally measured from the water edge to the well at the highest water level which may have occurred in a 10 year period.

AUTHORITY NOTE: Promulgated in accordance with R.S. 38:3091-R.S. 38:309.8.

Disclaimer: These regulations may not be the most recent version. Louisiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.