Section V-5039 - Nonstandard Cast Iron Boilers
Universal Citation: LA Admin Code V-5039
Current through Register Vol. 50, No. 9, September 20, 2024
A. The maximum allowable working pressure of a nonstandard boiler composed principally of cast iron shall not exceed 15 psig for steam service or 30 psig for hot water service.
B. The maximum allowable working pressure of a nonstandard boiler having cast iron shell or heads and steel or wrought iron tubes shall not exceed 15 psig for steam service or 30 psig for hot water service.
AUTHORITY NOTE: Promulgated in accordance with R.S. 23:531 and R.S. 51:1424.
Disclaimer: These regulations may not be the most recent version. Louisiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.