Louisiana Administrative Code
Title 55 - PUBLIC SAFETY
Part V - Fire Protection
Chapter 50 - Boiler Construction, Maintenance, Inspection and General Use
Subchapter C - Existing Installations- Power Boilers
Section V-5031 - Stop Valves
Current through Register Vol. 50, No. 9, September 20, 2024
A. Each steam outlet from a boiler (except safety valve and water column connections) shall be fitted with a stop valve located as close as practicable to the boiler.
B. When a stop valve is so located that water can accumulate, ample drains shall be provided. The drainage shall be piped to a safe location and shall not be discharged on the top of the boiler or its settings.
C. When boilers provided with manholes are connected to a common steam main, the steam piping connected from each boiler shall be fitted with two stop valves having an ample free blow drain between them. The discharge of the drain shall be visible to the operator while manipulating the valves and shall be piped clear of the boiler setting. The stop valves shall consist preferably of one automatic non-return valve (set next to the boiler) and a second valve of the outside-screw-and-yoke type.
AUTHORITY NOTE: Promulgated in accordance with R.S. 23:531 and R.S. 51:1424.