Louisiana Administrative Code
Title 55 - PUBLIC SAFETY
Part V - Fire Protection
Chapter 50 - Boiler Construction, Maintenance, Inspection and General Use
Subchapter C - Existing Installations- Power Boilers
Section V-5029 - Gage Glass Connections
Current through Register Vol. 50, No. 9, September 20, 2024
A. Gage glasses and/or gage cocks that are not connected directly to a shell or drum of the boiler shall be connected by one or the following methods.
B. Each boiler (except those not requiring water level indicators) shall have three or more gage cocks located within the visible length of the water glass, except when the boiler has two water glasses located on the same horizontal lines.
C. Boilers not over 36 inches in diameter in which the heating surface does not exceed 100 square feet need have but two gage cocks.
D. The gage cock connections shall be not less than 1/2 inch pipe size.
AUTHORITY NOTE: Promulgated in accordance with R.S. 23:531 and R.S. 51:1424.