Louisiana Administrative Code
Title 55 - PUBLIC SAFETY
Part V - Fire Protection
Chapter 30 - Portable Fire Extinguishers, Fire Hoses, Hydrostatic Testing, Fixed Fire Suppression Equipment and/or Systems and Fire Detection and Alarm Equipment and/or Systems Rules
Section V-3055 - Plan Review
Current through Register Vol. 50, No. 9, September 20, 2024
A. No system requiring plan submittal in accordance with R.S. 40:1574 et seq., shall be installed or integrated prior to submitting plans with required documentation and receiving authorization to install such system from the Plan Review Section of the Office of the State Fire Marshal. However, the installation of wiring only for fire detection and alarm systems shall be permitted upon receipt of plans by the Office of the State Fire Marshal, Plan Review Section. No fire detection devices or panels shall be installed prior to review or written authorization by the Office of the State Fire Marshal.
B. Only listed qualifiers of a firm shall be listed on applications for full plan review or exemption to full plan review. Additionally, any correspondence regarding a submittal, to include but not be limited to, telephone, email or written correspondence, shall only be through a listed qualifier of the firm, owner of the firm, a professional of record or owner of the building.
AUTHORITY NOTE: Promulgated in accordance with R.S. 40:1664.2.