Louisiana Administrative Code
Title 51 - PUBLIC HEALTH-SANITARY CODE
Part XIV - Plumbing
Chapter 8 - Indirect and Special Wastes
Section XIV-809 - Limitations
Universal Citation: LA Admin Code XIV-809
Current through Register Vol. 50, No. 9, September 20, 2024
A. The following limitations/requirements shall apply to indirect waste pipes.
1. Indirect waste piping exceeding 2 ft (610
mm) long shall be trapped.
2. The
maximum length of the indirect waste to indirect waste receptor shall not
exceed 15-feet (4527 mm). Should an indirect waste pipe exceed 15 feet in
length, a local vent shall be provided at a maximum of every 15 feet in
length.
B. Cleaning. Indirect waste piping shall be so installed as to permit ready access for flushing and cleansing.
AUTHORITY NOTE: Promulgated in accordance with R.S. 40:4(A)(7) and R.S. 40:5(2)(3)(7)(9)(16)(17)(20).
Disclaimer: These regulations may not be the most recent version. Louisiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.