Louisiana Administrative Code
Title 51 - PUBLIC HEALTH-SANITARY CODE
Part XIV - Plumbing
Chapter 6 - Water Supply and Distribution
Section XIV-611 - Sizing of Water Distribution System
Current through Register Vol. 50, No. 9, September 20, 2024
A. Minimum Sizes. The sizing of the water distribution system shall conform to good engineering practice (e.g., see §1805, Appendix B of this code). See §611. C of this code for the minimum required size of fixture branches and individual manifold distribution lines. See §611. D of this code for the minimum required size of fixture supplies and §611. E of this code for the minimum pressure required at fixture outlets.
B. Calculation of Sizes. When required by the plumbing official, the sizing of the water distribution system shall be calculated by a registered mechanical engineer or other acceptable authority.
C. Size of Fixture Branches and Manifold Individual Distribution Lines. The minimum size of fixture branches or manifold individual distribution lines shall be in accordance with the following Table 611.
Table 611 Minimum Size of Fixture Branches and Individual Manifold Distribution Lines |
||
Type of Fixture or Device |
Fixture Branch Pipe Size (in.) |
Individual Manifold Distribution Line Size (in.) |
Bathtubs (60" x 32" and smaller) |
1/2 |
1/2 |
Bathtubs (Larger than 60" x 32") |
1/2 |
1/2 |
Combination Sink and Tray |
1/2 |
1/2 |
Drinking Fountain |
1/2 |
1/2 |
Dishwasher (Domestic) |
1/2 |
1/2 |
Kitchen Sink, Residential |
1/2 |
1/2 |
Kitchen Sink, Commercial |
3/4 |
3/4 |
Lavatory |
1/2 |
1/2 |
Laundry Tray 1, 2, or 3 Compartments |
1/2 |
1/2 (1 Tray) |
Wall Hydrants |
1/2 |
1/2 |
Shower (Single Head) |
1/2 |
1/2 |
Sinks (Service, Slop) |
1/2 |
1/2 |
Sinks Flushing Rim |
3/4 |
3/4 |
Urinal (Flush Tank) |
1/2 |
1/2 |
Urinal (Direct Flush Valve) |
3/4 |
3/4 |
Water Closet (Flushometer Valve Type) |
1 |
1 |
Water Closet (Gravity or Flushometer Tank Type) |
1/2 |
1/2 |
Hose Bibbs |
1/2 |
1/2 |
D. Size of Fixture Supply. The fixture supply piping, tubing, or flexible connector shall be sized in accordance with the fixture manufacturer's recommendations but in no case shall the size interfere with the minimum fixture outlet discharge pressure requirements specified in §611. E of this code.
E. Minimum Pressure. Minimum fairly constant service pressure at the point of outlet discharge shall be not less than 8 psi (55.2 kPa) flowing for all fixtures except for direct flush valves, for which it shall be not less than 15 psi (103 kPa) flowing, and except where special equipment is used requiring higher pressure. In determining the minimum pressure, allowance shall be made for the pressure drop due to friction loss in the piping system during maximum demand periods as well as head, meter, and other losses in the system.
F. Auxiliary Pressure, Supplementary Tanks. If the residual pressure in the system is below the minimum allowable at the highest water outlet when the flow in the system is at peak demand, an automatically controlled pressure tank or automatically controlled pump or gravity tank of sufficient capacity shall be installed. Its capacity shall be sufficient to supply sections of the building installation which are too high to be supplied directly from the water main.
G. Low Pressure Cutoff. When a booster pump is used on an auxiliary pressure system, there shall be installed a low-pressure (<15 psi gauge) cutoff on the booster pump to prevent the creation of negative pressures on the suction side of the water system. Other arrangements may be used if found adequate and if approved by the plumbing official.
H. Variable Street Pressures. When the street main has a wide fluctuation in pressure, the water distribution system shall be designed for minimum pressure available.
I. Hazard and Noise. Where water pressures are excessive or where required to eliminate water hammer or when deemed necessary by local authorities, approved engineered water hammer arresters or calculated air chambers shall be provided to safeguard the water distribution system against destructive water hammer hazard and noise.
J. Water Pressure Reducing Valve or Regulators. The following shall apply relative to water pressure reducing valves or regulators.
Table 611.J Minimum Capacity Based on Pipe Size |
||||||
Nominal Pipe Size (in.) |
1/2 |
3/4 |
1 |
1 1/4 |
1 1/2 |
2 |
Average velocity through pipe (ft/s) |
10.5 |
10.0 |
9.5 |
9.0 |
8.5 |
7.5 |
Flow(gpm) |
9.95 |
16.65 |
25.0 |
42.0 |
54.8 |
77.5 |
K. Manifold Water Distribution Systems. Manifold water distribution systems shall comply with the following.
Table 611.K Maximum Gallons Per Minute (GPM) Available2 |
||
Nominal Size ID (Inches) |
Velocity1 |
|
4 fps |
8 fps |
|
1/2 |
2 |
5 |
3/4 |
6 |
11 |
1 |
10 |
20 |
1 1/4 |
15 |
31 |
1 1/2 |
22 |
44 |
NOTES:
AUTHORITY NOTE: Promulgated in accordance with R.S. 40:4(A)(7) and R.S. 40:5(2)(3)(7)(9)(16)(17)(20).