Current through Register Vol. 50, No. 9, September 20, 2024
A.
Commercial Dishwashing Machines. The following applies to commercial
dishwashing machines.
1. Protection.
Commercial dishwashing machines shall meet the requirements of
§609 B of this code.
2. Waste Connection. Each unit may be
separately trapped or discharge indirectly into a properly trapped and vented
fixture. A commercial dishwashing machine shall not be directly connected to a
drainage system. When a commercial dishwashing machine is located within 5 feet
of a trapped floor drain, the dishwasher waste outlet may be connected directly
on the inlet side of a properly vented floor drain trap.
3. Sanitization. Commercial dishwashing
machines shall be installed and operated in accord with the manufacturer's
recommendations and with the mechanical cleaning and sanitizing requirements
contained within Part XXIII (Eating and Drinking Establishments) of the
Louisiana State Sanitary Code (LAC 51:XXIII).
4. Flow Pressure. When spray-type dishwashing
machines are used in commercial installations, the pressure measured in the
final rinse water line shall be at least 15 psi (103 kPa) and not more than 25
psi (172 kPa) when the final rinse spray is operating. A suitable pressure
gauge and gage cock shall be provided in a readily accessible location
immediately upstream from the final rinse sprays to permit checking the flow
pressure of the final rinse water. If necessary, a permanently installed
pressure regulator shall be provided on the final rinse water line in order to
maintain the proper water pressure in the line when the final rinse spray is
operating.
B. Domestic
Dishwashing Machines. The following applies to domestic dishwashing machines.
1. Protection. Domestic dishwashing machines
shall meet the requirements of §807. B of this code.
2. Waste Connection. Each unit may be
separately trapped or discharge indirectly into a properly trapped and vented
fixture. A domestic dishwashing machine shall not be directly connected to a
drainage system. It may be connected through a wye connection into the tail
piece of a sink or into the body of a disposal unit with the flexible
dishwasher hose looped up to within 2 inches of the bottom of the counter
top.
C. Drinking
Fountains. The following applies to drinking fountains.
1. Design and Construction. Drinking
fountains shall conform to ASME A 112.19.1 or CSA B45.2 if of enameled cast
iron or enameled steel; or ASME A 112.19.2 or CSA B45.1 if of ceramic.
Mechanically refrigerated drinking fountains shall also conform to ARI 1010.
All drinking fountains shall conform to NSF 61.
2. Protection of Water Supply. Stream
projectors shall be so assembled as to provide an orifice elevation as
specified by ASME A 112.1.2.
3.
Prohibited Location. Drinking fountains shall not be installed in public toilet
rooms.
4. Minimum Required
Separation from Contamination. Drinking fountain fixtures shall provide a
minimum of 18 inches of separation from its water outlet (spigot) to any source
of contamination. Combination sink/drinking fountain units shall provide a
minimum of 18 inches between the drinking fountain water outlet (spigot) and
the nearest outside rim of the sink bowl [or other source(s) of contamination].
a. Exception. This 18 inch minimum separation
may only be reduced by the use of a vertical shield made of a smooth, easily
cleanable surface that is attached flush with the top surface of the unit and
extends to a distance at least 18 inches in height above the drinking fountain
water outlet (spigot) level.
b.
Prohibited Fixture. Combination sink/drinking fountain units which share the
same sink bowl are prohibited except in individual prison cells.
5. Minimum Fixture Requirements.
Water dispensing type drinking fountains which connect to the potable water
distribution system but require the use of an individual cup or container shall
be permitted to substitute for not more than 50 percent of the required number
of drinking fountains. Bottled water-type dispensers are prohibited from
counting toward the minimum required number of drinking fountains.
D. Garbage Can Washers. Garbage
can washers shall be separately trapped. The receptacle receiving the wash from
garbage cans shall be provided with a removable basket or strainer to prevent
discharge of large particles into the building drainage system. Any water
supply connection shall be protected against backflow by an air gap (water
distribution) or an approved backflow prevention device.
E. Floor Drains. The following applies to
floor drains.
1. Installation. The
installation of floor drains shall comply with the following.
a. Floor drains shall connect into a trap so
constructed that it can be readily cleaned and of a size to efficiently serve
the purpose for which it is intended. The drain inlet shall be located so that
it is, at all times, in full view and accessible.
b. Floor drains shall have a minimum 2-inch
diameter drain outlet and connect to a trap no less than 2-inches in
diameter.
c. Floor drains subject
to backflow shall not be directly connected to the drainage system or shall be
provided with a backwater valve.
d.
Floor drains shall be provided with removable strainers meeting §807. G.2 of
this code, the open area of which shall be not less than two-thirds of the
cross-sectional area of the trap to which it connects.
2. Required Locations. Floor drains shall be
installed in the following areas:
a. Floor
drains shall be installed in all public toilet rooms, etc., (see definition of
Public or Public Use in Chapter 2 of this code) and shall be fed (the water
seal replenished) by an approved automatic trap priming device meeting the
requirements of and installed in accordance with §415. E.4 a, §415. E.4 b, or
§415. E.4.c of this code.
i. Exceptions
(a). Floor drains are not required in the
toilet rooms serving hotel/motel guest rooms or patient rooms of hospitals and
nursing homes.
(b). In existing
ground floor construction, the addition of floor drains in public toilet rooms
is only required when substantial renovation or fixture additions to the public
toilet room(s) occurs which requires the concrete slab to be broken or when a
serious health threat to the public exists.
b. In public coin operated laundries and in
the central washing facilities of apartment buildings or in rooms containing
connections for laundry machines except in one and two family dwellings, the
rooms containing the laundry machines shall be provided with adequate floor
drains located to readily drain the entire floor area. When such floor drains
are not embedded in concrete, the floors shall be properly lined as required by
§415. I.2 of this code and the required floor drains shall meet the design
criteria for shower drains in §415. I.1 of this code.
c. Recess rooms located within medical
facilities which contain the recessed or concealed portions of sterilizers
shall be provided with a minimum of one acceptable floor drain in accordance
with §1305. C.2 of this code.
d.
Each toilet room and laundry room in the service buildings of travel trailer
parks shall be provided with a minimum 2-inch floor drain in accordance with
§1509. F of this code.
3.
Prohibited Locations. The following applies to prohibited locations of floor
drains.
a. No floor drain or other plumbing
fixture except electric water heaters shall be installed in a room containing
air handling machinery when such room is used as a plenum. When rooms are used
as a plenum, equipment drains shall be conveyed through an indirect waste
receptor located outside such rooms or other approved point of
disposal.
b. Floor drains directly
connected to the plumbing system shall not be located in elevator
pits.
c. No floor drains shall be
permitted in food storage areas unless installed in accordance with §807. A of
this code.
d. Floor drains are not
permitted in walk-in coolers or freezers unless they are provided with indirect
connections to the sanitary sewer located outside the walk-in cooler or
freezer.
4. Trap Seal
Protection. Floor drain or similar traps shall be regularly and automatically
fed (the water seal replenished) by the addition of water, liquid waste, or
industrial waste (such as the normal and regular operation of a plumbing
fixture or condensate waste draining thereto) into the floor drain or, in lieu
thereof, shall be protected by the use of:
a.
an ASSE 1018 automatic trap priming device (see §625. D of this
code);
b. an electronic potable
water supply fed trap priming device meeting ASSE 1044 (see §625. D of this
code);
c. a drainage type device
meeting ASSE 1044 which captures liquid wastes only from:
i. the tail piece of a lavatory;
ii. the discharge side of the atmospheric
vacuum breaker located downstream of a flushometer valve servicing a water
closet or a clinical sink (the take off point on the discharge pipe must be at
least 4" below the critical level of the vacuum breaker); or,
iii. the refill/hush tube of ballcocks (only
on ballcocks that utilize an atmospheric vacuum breaker in accordance with the
requirements of §609. C.2 of this code).
d. an ASSE 1072 listed barrier type floor
drain trap seal protection device; or,
e. a combination of the methods listed above,
i.e., the use of an ASSE 1072 device in addition to the use of either an ASSE
1018 or ASSE 1044 automatic trap priming device.
F. Food Waste Grinder Units. The
following applies to food waste grinder units.
1. Separate Connections. Domestic food waste
disposal units may be connected and trapped separately from any other fixture
or compartment. Units may have either automatic or hand-operated water-supply
control. See
§609 of this code.
2. Commercial Type Grinders. Food grinders
used in commercial buildings shall have an automatic water-supply and shall be
provided with not less than 2-inch (51mm) waste line. Each waste line shall be
trapped and vented as provided in other Sections of this code (see §1005. K.1 of this code).
G.
Laundry Trays. The following applies to laundry trays.
1. Waste Outlets. Each compartment of a
laundry tray shall be provided with a waste outlet not less than 1 1/2 inches
in diameter.
2. Overflow. Laundry
tray overflows shall conform to the requirements of §413. D of this
code.
H. Multiple
Washsinks. The following applies to multiple washsinks.
1. Circular Type. Each 18 inches (457 mm) of
wash sink circumference (circular type), when provided with water outlets for
such space, shall be equivalent to one lavatory.
2. Straight-Line Type. Multiple wash sinks of
the straight-line type shall have hot and cold combination spouts not closer
than 24 linear inches (610 mm) from adjacent similar spouts and each spout
shall be considered the equivalent of one lavatory.
I. Shower Compartments. The following applies
to shower compartments.
1. Shower. Shower
compartments shall conform to Table 415.I of this Part and shall have approved
shower pan material or the equivalent thereof as determined by the plumbing
official. The pan shall turn up on three sides at least 2 inches (51 mm) above
finished curb level. The remaining side shall wrap over the curb. Shower drains
shall be constructed with a clamping device so that the pan may be securely
fastened to the shower drain thereby making a watertight joint. Shower drains
shall have an approved weephole device system to insure constant drainage of
water from the shower pan to the sanitary drainage system. There shall be a
watertight joint between the shower drain and trap. Shower receptacle waste
outlets shall be not less than 2 inches and shall have a removable strainer.
a. Exception. Shower compartments with
prefabricated receptors conforming to the standards listed in Table 415.I of
this Part, or special use shower compartments for accessible use which comply
with the ANSI A117.1 accessibility standard.
Table 415.I
Prefabricated Shower Receptor Standards
|
Materials
|
Standards
|
Plastic Bathtub and Shower Units
|
ANSI Z124.1.2
|
Chlorinated Polyethylene (CPE) Sheeting for
Concealed Water-Containment Membrane
|
ASTM D 4068
|
Polyvinyl Chloride (PVC) Plastic Flexible Concealed
Water-Containment Membrane
|
ASTM D 4551, See §303. G.7 of this code
|
2. Construction. Floors under shower
compartments shall be laid on a smooth and structurally sound base and shall be
lined and made watertight with sheet lead, copper or other acceptable
materials.
3. Public or
Institutional Showers. Floor of public shower rooms shall be drained in such a
manner that no waste water from any shower head will pass over floor areas
occupied by other bathers.
J. Special Fixtures. The following applies to
special fixtures.
1. Water Drain and
Connections. Baptistries, ornamental and lily pools, aquaria, ornamental
fountain basins and similar constructions when provided with water supplies
shall be protected from backsiphonage as required in §609. A and Table 609.F.6
of this code.
2. Approval.
Specialties requiring water and waste connections shall be submitted for
approval of the plumbing official.
3. Accessible Fixtures. Accessible fixtures
shall comply with the requirements of ANSI A117.1.
K. Swimming Pools, Spas, and Hot Tubs. The
following applies to swimming pools, spas, and hot tubs.
1. Water Circulation System Components. Water
circulation system components and disinfectant equipment for swimming pools,
spas or hot tubs shall meet the requirements of NSF 50. [For other swimming
pool and spa requirements, also see Part XXIV (Swimming Pools) - Louisiana
State Sanitary Code (LAC 51:XXIV)]
2. Suction Fittings. Suction fittings shall
conform to ASME A 112.19.8 or APSP 16. Public, Residential Spas shall comply
with the standards listed in the following Table 415.K below.
Table 415.K
Public and Residential Spas Standards
|
Materials
|
Standards
|
Public Spas
|
APSP-2
|
Residential Spas, Permanently Installed
|
APSP-3
|
Residential Spas, Portable
|
APSP-6
|
L. Urinals. The following applies to urinals.
1. Automatic Flushing Tank. Tanks flushing
more than one urinal shall be automatic in operation and of sufficient capacity
to provide the necessary volume to flush and properly cleanse all urinals
simultaneously.
2. Urinals Equipped
with Automatic Flush Valves. Flushometers shall be as prescribed in §415. N.5 of this code and no valve shall be used to flush more than one
urinal.
3. Nonwater Urinals.
Nonwater urinals shall conform with LAC 51:XIV.409.A.2.
4. Trough Urinals. Trough urinals may only be
used for stadiums, arenas, and jails, prisons, or other institutions of
detention or incarceration. Trough urinals, when used, shall conform to the
following requirements:
a. Shall not be less
than 6 inches deep and shall be furnished with one piece backs and have
strainers with outlets at least l 1/2 inches in diameter.
b. The washdown pipe shall be perforated so
as to flush with an even curtain of water against the back of the urinal. This
pipe shall be securely clamped as high as practicable to the back of the
urinal. Trough urinals, where so equipped, shall have tanks with a flushing
capacity of not less than 1 1/2 gallons of water for each 2 feet of urinal
length.
c. Trough urinals shall be
figured on the basis of one urinal for each 18 inches of length, provided that:
24-inch urinal equals 1 urinal; 36-inch urinal equals 2 urinals; 48-inch urinal
equals 2 urinals; 60-inch urinal equals 3 urinals; and a 72-inch urinal equals
4 urinals.
5. Privacy.
Privacy walls or partitions shall be provided for each urinal within public use
and employee use toilet rooms used by males. Such walls or partitions shall
conform to the following:
a. The wall or
partition finish surface shall be non-absorbent, smooth, and easily
cleanable.
b. The walls or
partitions shall begin at a height of not more than 14 inches above the
finished floor surface and shall extend not less than 60 inches above the
finished floor surface.
c. The
walls or partitions shall extend from the wall surface at each side of the
urinal a minimum of 18 inches or to a point not less than 6 inches beyond the
outermost front lip of the urinal measured from the finished back wall surface,
whichever is greater.
i. Exceptions. The
following conditions shall constitute an exception (or a partial exception) to
the requirement for privacy walls or partitions for each urinal within public
use toilet rooms used by males:
(a). toilet
rooms having wall-hung trough urinals only (which are currently only allowed in
stadiums, arenas, and in jails, prisons, and other places of detention or
incarceration);
(b). toilet rooms
used by children less than 5 years of age which are located in day care and
child-care facilities and which contain two or more urinals shall be permitted
to have one urinal without privacy walls or partitions; or,
(c). toilet rooms located in jails, prisons
and other places of detention or incarceration.
M. Washing Machines for
Residences. The following applies to washing machines for residences.
1. Protection. Domestic washing machines
shall meet the requirements of §609. A of this code.
2. Separate Trap. Each unit shall be
separately trapped or discharge indirectly into a properly trapped and vented
fixture (see §1001. I of this code).
3. Cross Fittings. Automatic washing machines
shall not be connected to a 2-inch or smaller cross-type fitting.
4. Central Facilities. When central washing
facilities are provided in lieu of washing machine connections in each living
unit, central facilities shall be located for the building served at the ratio
of not less than one washing machine for each 12 living units, but in no case
less than two machines for each building of 15 living units or less. See §415.
E.2.b of this code.
N.
Water Closets. The following applies to water closets.
1. Public Use. Water closet bowls for public
use including, but not limited to, hotel and motel guest rooms and patient
rooms of hospitals and nursing homes shall be of the elongated type.
2. Flushing Device. Water closet gravity,
tanks, flushometer tanks and flushometer valves shall have a flushing capacity
sufficient to properly flush the water closet bowls to which they are
connected.
3. Float Valves. Float
valves in water closet tanks shall close tight and provide water to properly
refill the trap seal in the bowl.
4. Close-Coupled Tanks. The flush valve seat
in close-coupled water closet combinations shall be 1 inch (25.4 mm) or more
above the rim of the bowl, so that the flush valve will close even if the
closet trapway is clogged. Any closets with flush valve seats below the rim of
the bowl shall be so constructed that in case of trap stoppage, water will not
flow continuously over the rim of the bowl.
5. Automatic Flush Valve. Flushometers shall
be so installed that they will be readily accessible for repairing. When the
valve is operated, it shall complete the cycle of operation automatically,
opening fully and closing positively under the service pressure. At each
operation, the valve shall deliver water in sufficient volume and at a rate
that will thoroughly flush the fixture and refill the fixture trap. Means shall
be provided for regulating flush valve flow. Not more than one fixture shall be
served by a single flush valve.
6.
Seats. Water closets shall be equipped with seats of smooth nonabsorbent
material. All seats of water closets provided for public use including, but not
limited to, hotel and motel guest rooms and patient rooms of hospitals and
nursing homes shall be of the open-front type. Integral water closet seats
shall be of the same material as the fixture. The seat contour shall be the
same contour as the water closet.
7. Water Closet Compartment. Each water
closet utilized by the public or employees shall occupy a separate compartment
with walls or partitions and a lockable door enclosing the individual fixture
to ensure privacy. Such walls or partitions shall conform to the following:
a. The wall or partition finish surface shall
be non-absorbent, smooth, and easily cleanable.
b. The walls or partitions shall begin at a
height of not more than 14 inches above the finished floor surface (except when
same would be higher than the bowl rim of a child-sized toilet) and shall
extend not less than 66 inches above the finished floor surface. For
child-sized toilets, the walls or partitions shall begin at a height no higher
than the bowl rim of the child-sized toilet.
i. Exceptions. The following conditions shall
constitute an exception (or a partial exception) to the requirement for
separate compartments for each water closet:
(a). toilet rooms containing only a single
water closet (or only a single water closet and lavatory) with a lockable
door;
(b). toilet rooms located in
day care and child-care facilities which care for children less than 5 years of
age and containing two or more water closets shall be permitted to have one
water closet without an enclosing compartment; or,
(c). toilet rooms located in jails, prisons
and other institutions of detention or incarceration.
O. Whirlpool
Bathtubs. The following applies to whirlpool bathtubs.
1. Access. An access panel of sufficient size
shall be installed to provide access to the pump for repair and
replacement.
2. Pump. When not
factory assembled to the tub assembly, the circulation pump shall be accessibly
located above the crown weir of the trap. The pump drain line shall be properly
graded to assure minimum water retention in the volute after fixture
use.
3. Operation. Leak testing and
pump operation shall be performed in accordance with manufacturer's
recommendations.
4. Hydro-massage
Bathtubs. Hydro-massage bathtubs shall comply with ASME A 112.19.7.
5. Whirlpool Bathtub Appliances. Whirlpool
bathtub appliances shall comply with ASME A 112.19.7.
6. Suction Fittings. Suction fittings for use
in whirlpool bathtubs shall comply with ASME A 112.19.8 or APSP 16.
AUTHORITY NOTE:
Promulgated in accordance with
R.S.
40:4(A)(7),
R.S.
40:5(2)(3)(7)(9)(16)(17)(20),
and HCR 4 of the 2008 Regular Session.