Louisiana Administrative Code
Title 51 - PUBLIC HEALTH-SANITARY CODE
Part XIV - Plumbing
Chapter 13 - Medical Facilities Plumbing Systems [formerly Appendix G - Medical Facilities Plumbing Systems]
Section XIV-1305 - Drainage and Venting
Current through Register Vol. 50, No. 9, September 20, 2024
A. Ice Storage Chest Drains. Any drain serving an ice storage chest or box shall discharge over an indirect waste receptor separate from all other fixture wastes. Each terminal shall discharge through an air gap (drainage system) above the receptor. The end shall be covered with a removable screen of not less than 10 mesh per square inch (15.5 mesh per 1000 sq mm), and if discharging vertically, the terminal shall be cut at an angle of 45° (0.785 rad).
B. Bedpan Washers and Clinical Sinks. Bedpan washers and clinical sinks shall be connected to the soil pipe system and vented following the requirements as applied to water closets, except that bedpan washers require additional local vents.
C. Sterilizer Wastes. Wastes for sterilizers shall conform with the following.
D. Aspirators. In operating rooms, emergency rooms, recovery rooms, delivery rooms, examining rooms, autopsy rooms, and other locations except laboratories, where aspirators are installed for removing blood, pus, or other fluids, the discharge from any aspirator shall be indirectly connected to the drainage system. The suction line shall be provided with a bottle or similar trap to protect the water supply.
E. Vacuum System Stations. Vacuum system station locations shall be considered from the standpoint of convenience and practical use. The receptacles should be built into cabinets or recesses but shall be visible and readily accessible.
F. Bottle System. Vacuum (fluid suction) systems intended for collecting, removing or disposing of blood, pus or other fluids by the so-called bottle system shall be provided with receptacles, which are equipped with an overflow preventative device, at each vacuum outlet station. Each vacuum outlet station should be equipped with a secondary safety receptacle as an additional safeguard against fluids, other than air entering the vacuum piping systems.
G. Central Disposal System Equipment. All central vacuum (fluid suction) systems shall assure continuous service. Systems equipped with collecting or control tanks shall provide for draining and cleaning of the tanks while the system is in operation. In hospitals or institutions having emergency power provisions, the system shall be capable of remaining in service during the use of emergency power. The exhausts from a vacuum pump used in connection with a vacuum (fluid suction) system shall discharge separately to the outer atmosphere. The exhaust discharge shall not create a nuisance or hazard within, without, around or about the premises. Termination of the exhaust to the atmosphere shall be the same as required for sanitary sewer vents.
H. Central Vacuum and Disposal Systems. Central vacuum and disposal systems shall conform with the following.
I. Condensate Drains for Space Cooling and Heating Systems. The lowest point of a condensate riser or risers shall be trapped and discharged over an indirect waste sink. The trap may be either a "P" or a "running trap" with a cleanout. A branch shall be installed upstream from the condensate drain trap for flushing and resealing purposes. The condensate drain and trap shall be located above the lowest floor level of the building.
J. Vent Material. Material for local vents serving bedpan washers and sterilizer vents serving sterilizers shall be sufficiently rust proof, erosion and corrosion resistant to withstand intermittent wetting and drying from steam vapors, to withstand the distilled water solvent action of the steam vapors and to withstand frequent and immediate changes of temperatures.
K. Vent Connections Prohibited. Connections between local vents serving bedpan washers, sterilizer vents serving sterilizing apparatus and normal sanitary plumbing systems are prohibited. Furthermore, only one type of apparatus shall be served by a given local vent.
L. Local Vents and Stacks. Local vents and stacks shall comply with the following.
M. Sterilizer Vents and Stacks. Sterilizer vents and stacks shall comply with the following.
N. Sterilizer Vent Stack Sizes. Sterilizer vent stack sizing shall comply with the following.
Table 1305.N.1 Stack Sizes for Bedpan Steamers and Boiling Type Sterilizers (in) (Number of connections of various sizes permitted to various sized sterilizer vent stacks) |
|||
Stack Size (in) |
Connection Size (in) |
||
1 1/2 |
2 |
||
1 1/2 (see note 1) |
1 |
or |
0 |
2 |
2 |
or |
1 |
2 (see note 2) |
1 |
and |
1 |
3 (see note 1) |
4 |
or |
2 |
3 (see note 2) |
2 |
and |
2 |
4 (see note 1) |
8 |
or |
4 |
4 (see note 2) |
4 |
and |
4 |
NOTES:
Table 1305.N.2 Stack Sizes for Pressure Sterilizers (in) (Number of connections of various sizes permitted to various sized vent stacks) |
||||
Stack Size (in) |
Connection Size (in) |
|||
3/4 |
1 |
1 1/4 |
1 1/2 |
|
1 1/2 (Note 1) |
3 or |
2 or |
1 or |
1 |
1 1/2 (Note 2) |
2 and |
1 |
||
2 (Note 1) |
6 or |
3 or |
2 or |
1 |
2 (Note 2) |
3 and |
2 |
||
2 (Note 2) |
2 and |
1 and |
1 |
|
2 (Note 2) |
1 and |
1 and |
1 |
|
3 (Note 1) |
15 or |
7 or |
5 or |
3 |
3 (Note 2) |
1 and |
2 and |
2 |
|
1 and |
5 and |
1 |
NOTES:
O. Radioactive Materials. All radioactive materials shall be disposed of in a manner so as not to create a hazard to operation and maintenance personnel of the institution or to the public. Specific permission shall be secured from the proper authority to dispose of any radioactive material to the drainage system.
AUTHORITY NOTE: Promulgated in accordance with R.S. 40:4(A)(7) and R.S. 40:5(2)(3)(7)(9)(16)(17)(20).