Louisiana Administrative Code
Title 51 - PUBLIC HEALTH-SANITARY CODE
Part XII - Water Supplies
Chapter 3 - Water Quality Standards
Section XII-341 - Separation of Water Mains and Sewer Mains [formerly paragraph 12:015]

Universal Citation: LA Admin Code XII-341

Current through Register Vol. 50, No. 3, March 20, 2024

A. Sewer and water mains shall be laid in separate trenches not less than 6 feet apart horizontally, when installed in parallel. Crossing water and sewer mains shall have a minimum vertical separation of 18 inches. In cases where it is not possible to maintain a 6 foot horizontal separation, the state health officer may allow a waiver of this requirement on a case by case basis if supported by data from the design engineer.

AUTHORITY NOTE: Promulgated in accordance with R.S. 40:4 (A)(6)(8) and R.S. 40:5 (5)(6)(9).

Disclaimer: These regulations may not be the most recent version. Louisiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.