Current through Register Vol. 50, No. 9, September 20, 2024
A.
Rapid Rate Gravity Filters. General design criteria for rapid rate gravity
filters is as follows.
1. Pretreatment. The
use of rapid rate gravity filters shall require pretreatment.
2. Rate of Filtration. The rate of filtration
shall be determined through consideration of such factors as raw water quality,
degree of pretreatment provided, filter media, water quality control
parameters, and competency of operating personnel. Typical filtration rates
range from 2 to 4 gpm/sqft. Maximum filtration rates for plants treating
surface waters or ground water under the influence of surface water shall not
exceed 3.0 gpm/sqft. For surface water treatment plants or GUISW with proposed
filtration rates above 3.0 gpm/sqft, data from pilot testing shall be submitted
to the state health officer for consideration and approval.
3. Number. Plants employing rapid rate
gravity filters shall provide at least two filter units. The filters shall be
capable of meeting the plant design capacity at the plants average daily flow
of the maximum month with one filter unit removed from service. Where declining
rate filtration is provided, the variable aspect of filtration rates, and the
number of filters must be considered when determining the design capacity for
the filters.
4. Structural Details
and Hydraulics. The filter structure shall be designed to provide for:
a. vertical walls within the
filter;
b. no protrusion of the
filter walls into the filter media;
c. head room to permit normal inspection and
operation;
d. minimum depth of
filter box of 8.5 feet;
e. minimum
water depth over the surface of the filter media of three feet;
f. trapped effluent to prevent backflow of
air to the bottom of the filters;
g. prevention of floor drainage in to the
filter;
h. prevention of flooding
by providing overflow;
i. maximum
velocity of treated water in pipe and conduits to filters of two feet per
second;
j. cleanouts and straight
alignment for influent pipes or conduits where solids loading is heavy, or
following lime-soda softening;
k.
washwater drain capacity to carry maximum flow;
l. handrails or walls around filter banks
adjacent to normal walkways; and
m.
construction to prevent cross connections and common walls between potable and
non-potable water.
5.
Washwater troughs should be constructed to have:
a. the bottom elevation above the maximum
level of expanded media during washing;
b. a two-inch freeboard at the maximum rate
of wash;
c. the top edge level and
all at the same elevation;
d.
spacing so that each trough serves the same number of square feet of filter
area;
e. maximum horizontal travel
of suspended particles to reach the trough not to exceed three feet;
f. means to exclude the loss of media when
providing for concurrent air/high rate water backwashing; and
g. a two-inch freeboard at the main wash
water gullet at the maximum rate of wash.
6. Filter Material. The granular filter media
shall be in accordance with AWWA B100 and have the following characteristics:
a. a total depth of not less than 24 inches
and generally not more than 30 inches;
b. a uniformity coefficient of the smallest
material not greater than 1.65;
c.
a minimum of 12 inches of media with an effective size range no greater than
0.45 mm to 0.55 mm unless specified otherwise per the following.
i. Anthracite shall have:
(a). an effective size of 0.45 mm - 0.55 mm
with uniformity coefficient not greater than 1.65 when used alone;
(b). an effective size of 0.8 mm - 1.2 mm
with a uniformity coefficient not greater than 1.7 when used as a cap;
and
(c). an effective size for
anthracite used as a single media on potable groundwater for iron and manganese
removal only shall be a maximum of 0.8 mm (effective sizes greater than 0.8 mm
may be approved based upon onsite pilot plant studies or other demonstration
acceptable to the state health officer).
ii. Sand shall have:
(a). an effective size of 0.45 mm to 0.55 mm;
and.
(b). a uniformity coefficient
of not greater than 1.65.
iii. High density sand shall have:
(a). an effective size of 0.2 to 0.3
mm;
(b). a uniformity coefficient
of not greater than 1.65.
iv. Granular activated carbon (GAC) shall be
in accordance with AWWA B604 and the design of shall meet the following:
(a). There shall be provisions for a free
chlorine residual and adequate contact time in the water following the filters
and prior to distribution (See §177.C and §177 D)
(b). There shall be means for periodic
treatment of filter material for control of bacterial and other
growth.
(c). Provisions shall be
made for frequent replacement or regeneration. Regeneration of GAC shall be in
accordance with AWWA B604.
v. Other Media. Other media will be
considered based on experimental data and operating
experience.
d.
Characteristics of support media shall include the following.
i. Torpedo Sand. A three-inch layer of
torpedo sand shall be used as a supporting media for filter sand where
supporting gravel is used, and shall have:
(a). effective size of 0.8 mm to 2.0 mm;
and
(b). uniformity coefficient not
greater than 1.7.
ii.
Gravel, when used as the supporting media shall consist of cleaned and washed,
hard, durable, rounded silica particles and shall not include flat or elongated
particles. The coarsest gravel shall be 2.5 inches in size when the gravel
rests directly on a lateral system, and shall extend above the top of the
perforated laterals. Not less than four layers of gravel shall be provided in
accordance with the following size and depth distribution.
Table 175.A.6.e
|
Size
|
Depth
|
3/32 to 3/16 inches
|
2 to 3 inches
|
3/16 to 1/2 inches
|
2 to 3 inches
|
1/2 to 3/4 inches
|
3 to 5 inches
|
3/4 to 1 1/2 inches
|
3 to 5 inches
|
1 1/2 to 2 1/2 inches
|
5 to 8 inches
|
Reduction of gravel depths and other size gradations may be
considered upon justification to the state health officer.
7. Filter
bottoms and strainer systems. Departures from these standards may be acceptable
for high rate filters and for proprietary bottoms. Porous plate bottoms shall
not be used where iron or manganese may clog them or with waters softened by
lime. The design of manifold-type collection systems shall:
a. ensure even distribution of washwater and
even rate of filtration over the entire area of the filter;
b. provide the ratio of the area of the final
openings of the strainer systems to the area of the filter at 0.003;
c. provide the total cross-sectional area of
the laterals at twice the total area of the final openings;
d. provide the cross-sectional area of the
manifold at 1.5 to 2 times the total area of the laterals;
e. lateral perforations without strainers
shall be directed downward.
8. Filter media wash facilities are required
except for filters used exclusively for iron, radionuclides, arsenic or
manganese removal. Wash water systems shall be designed with:
a. water pressure per manufacturers
requirements;
b. a properly
installed vacuum breaker or other approved device to prevent back siphonage if
connected to the filtered or finished water system;
c. rate of flow of 2.0 gallons per minute per
square foot of filter area (4.9 m/hr) with fixed nozzles or 0.5 gallons per
minute per square foot (1.2 m/hr) with revolving arms if provided.
d. Air scouring. When provided, general
design criteria for air scouring is as follows.
i. Air flow for air scouring the filter shall
be 3-5 standard cubic feet per minute square foot of filter area (0.9-1.5
m3/min/m2) when the air is introduced in the underdrain; a lower air rate shall
be used when the air scour distribution system is placed above the
underdrains.
ii. When employing
concurrent air scour and water back wash a method for avoiding excessive loss
of the filter media during backwashing shall be provided.
iii. Air scouring shall be followed by a
fluidization wash sufficient to re-stratify the media.
iv. Air shall be free from
contamination.
v. Air scour
distribution systems should be placed below the media and supporting bed
interface; if placed at the interface the air scour nozzles shall be designed
to prevent media from clogging the nozzles or entering the air distribution
system.
vi. Piping for the air
distribution system shall not be flexible hose which will collapse when not
under air pressure and shall not be a relatively soft material which may erode
at the orifice opening with the passage of air at high velocity.
vii. Air delivery piping shall not pass down
through the filter media nor shall there be any arrangement in the filter
design which would allow short circuiting between the applied unfiltered water
and the filtered water.
viii. The
backwash water delivery system must be capable of 15 gallons per minute per
square foot of filter surface area (37 m/hr); however, when air scour is
provided the backwash water rate must be variable and should not exceed 8
gallons per minute per square foot (20 m/hr) unless operating experience shows
that a higher rate is necessary to remove scoured particles from filter media
surfaces.
ix. The filter
underdrains shall be designed to accommodate air scour piping when the piping
is installed in the underdrain.
9. Appurtenances. The following shall be
provided for every filter:
a. a means of
sampling influent and effluent water sampling taps;
b. a meter indicating the instantaneous
effluent rate of flow;
c. where
used for surface water, provisions for filtering to waste with appropriate
measures for cross connection control;
d. a flow rate controller capable of
providing gradual rate increases when placing the filters back into operation;
and
e. for surface water or systems
using ground water under the direct influence of surface water with three or
more filters, on-line turbidimeters shall be installed on the effluent line
from each filter. All turbidimeters shall consistently determine and indicate
the turbidity of the water in NTUs. Each turbidimeter shall report to a
recorder that is designed and operated to allow the operator to accurately
determine the turbidity at least once every 15 minutes. Turbidimeters on
individual filters should be designed to accurately measure low-range
turbidities and have an alarm that will sound when the effluent level exceeds
regulatory turbidity limits. It is recommended that turbidimeters be placed in
a location that also allows measurement of turbidity during filter to
waste.
10. Backwash.
Provisions shall be made for washing filters as follows.
a. a minimum rate necessary to provide for a
50 percent expansion of the filter bed shall be provided with a minimum of 15
gpm/sqft. A reduced rate of 10 gallons per minute per square foot (24 m/hr) may
be acceptable for full depth anthracite or granular activated carbon
filters;
b. filtered water shall be
used for backwashing filters except in the application of GAC filters for
removing formed disinfection by-products;
c. washwater pumps shall be in duplicate
except in the application of GAC filters or an alternate means of obtaining
washwater is available;
d. a
washwater regulator or valve on the main washwater line to obtain the desired
rate of filter wash with the washwater valves on the individual filters open
wide;
e. a flow meter, preferably
with a totalizer, on the main washwater line located so that it can be easily
read by the operator during the washing process;
f. design to prevent rapid changes in
backwash water flow;
g. automated
systems shall be adjustable; and
h.
appropriate measures for cross-connection control.
B. Rapid Rate Pressure Filters.
The normal use of these filters is for iron and manganese removal. For raw
water with iron concentration of 2 mg/L or greater consideration should be
given to pretreatment prior to filtration. Pressure filters shall not be used
in the filtration of surface or other polluted waters or following lime-soda
softening.
1. Minimum criteria relative to
rate of filtration, structural details and hydraulics, filter media, etc.,
provided for rapid rate gravity filters also apply to pressure filters where
appropriate. At least two filter units shall be provided. The filters shall be
capable of meeting the average daily flow of the maximum month with one filter
unit removed from service.
2. Rate
of Filtration. The rate shall not exceed six gallons per minute per square foot
of filter area except where manufacturers performance studies of the unit have
demonstrated to the satisfaction of the state health officer that higher
filtration rates are achievable. Consideration shall be given to backwash
frequency and deteriorating water quality when selecting the filtration
rate.
3. The filters shall be
designed to provide for:
a. loss of head
gauges on the inlet and outlet pipes of each filter;
b. an easily readable meter or flow indicator
on each battery of filters;
c.
filtration and backwashing of each filter individually;
d. minimum side wall shell height of five
feet for vertical filters. A corresponding reduction in side wall height is
acceptable where proprietary bottoms permit reduction of the gravel
depth;
e. the top of the washwater
collectors to be at least 18 inches above the surface of the media;
f. the underdrain system to efficiently
collect the filtered water and to uniformly distribute the backwash water at a
rate not less than 15 gallons per minute per square foot of filter
area;
g. backwash flow indicators
and controls that are easily readable while operating the control
valves;
h. an air release valve on
the highest point of each filter;
i. an accessible manhole of adequate size to
facilitate inspection and repairs for filters 36 inches or more in diameter.
Manholes should be at least 24 inches in diameter where feasible;
j. means to observe the wastewater during
backwashing; and
k. construction to
prevent cross-connection.
C. Diatomaceous Earth Filtration. The use of these
filters may be considered for application to surface waters with low turbidity
and low bacterial contamination.
1.
Conditions of Use. Diatomaceous earth filters are expressly excluded from
consideration for the following conditions:
a.
bacteria removal;
b. color
removal;
c. turbidity removal where
either the gross quantity of turbidity is high or the turbidity exhibits poor
filterability characteristics; and
d. filtration of waters with high algae
counts.
2. Pilot Plant
Study. Installation of a diatomaceous earth filtration system shall be preceded
by a pilot plant study on the water to be treated.
a. Conditions of the study such as duration,
filter rates, head loss accumulation, slurry feed rates, turbidity removal,
bacteria removal, etc., must be approved by the state health officer prior to
the study.
b. Satisfactory pilot
plant results must be obtained prior to preparation of final construction plans
and specifications.
c. The pilot
plant study must demonstrate the ability of the system to meet applicable
drinking water standards at all times.
3. Types of Filters. Pressure or vacuum
diatomaceous earth filtration units will be considered for approval. However,
the vacuum type is preferred for its ability to accommodate a design which
permits observation of the filter surfaces to determine proper cleaning, damage
to a filter element, and adequate coating over the entire filter
area.
4. Treated water storage
capacity in excess of normal requirements shall be provided to:
a. allow operation of the filters at a
uniform rate during all conditions of system demand at or below the approved
filtration rate, and
b. guarantee
continuity of service during adverse raw water conditions without by-passing
the system.
5. Number of
Units. At least two units shall be provided. Where only two units are provided,
each shall be capable of meeting the plant design capacity (normally the
projected maximum daily demand) at the approved filtration rate. Where more
than two filter units are provided, the filters shall be capable of meeting the
plant design capacity at the approved filtration rate with one filter removed
from service.
6. Pre-coating
criteria includes the following.
a.
Application. A uniform precoat shall be applied hydraulically to each septum by
introducing a slurry to the tank influent line and employing a filter-to-waste
or recirculation system.
b.
Quantity. Diatomaceous earth in the amount of 0.2 pounds per square foot of
filter area (0.98 kg/m2) or an amount sufficient to apply a 1/8 inch coating
should be used with recirculation.
7. A body feed system to apply additional
amounts of diatomaceous earth slurry during the filter run is required to avoid
short filter runs or excessive head losses.
a. Rate of body feed is dependent on raw
water quality and characteristics and shall be determined in the pilot plant
study.
b. Operation and maintenance
can be simplified by providing accessibility to the feed system and slurry
lines.
c. Continuous mixing of the
body feed slurry is required.
8. Filtration criteria includes the
following.
a. Rate of Filtration. The
recommended nominal rate is 1.0 gallon per minute per square foot of filter
area (2.4 m/hr) with a recommended maximum of 1.5 gallons per minute per square
foot (3.7 m/hr). The filtration rate shall be controlled by a positive
means.
b. Head Loss. The head loss
shall not exceed 30 psi (210 kPa) for pressure diatomaceous earth filters, or a
vacuum of 15 inches of mercury (-51 kPa) for a
vacuum system.
c. Recirculation. A
recirculation or holding pump shall be employed to maintain differential
pressure across the filter when the unit is not in operation in order to
prevent the filter cake from dropping off the filter elements. A minimum
recirculation rate of 0.1 gallon per minute per square foot of filter area
(0.24 m/hr) shall be provided.
d.
Septum or Filter Element. The filter elements shall be structurally capable of
withstanding maximum pressure and velocity variations during filtration and
backwash cycles, and shall be spaced such that no less than one inch is
provided between elements or between any element and a wall.
e. Inlet Design. The filter influent shall be
designed to prevent scour of the diatomaceous earth from the filter
element.
9. Backwash. A
satisfactory method to thoroughly remove and dispose of spent filter cake shall
be provided (see Subchapter F. §257-275 of this Part).
10. The following appurtenances shall be
provided for every filter:
a. a means of
sampling for raw and filtered water;
b. loss of head or differential pressure
gauge;
c. rate-of-flow indicator,
preferably with totalizer;
d. a
throttling valve used to reduce rates below normal during adverse raw water
conditions;
e. evaluation of the
need for body feed, recirculation, and any other pumps, in accordance with
§217 of this Part; and
f. provisions for filtering to waste with
appropriate measures for backflow prevention.
D. Slow Sand Filters. The use of these
filters shall require prior engineering studies to demonstrate the adequacy and
suitability of this method of filtration for the specific raw water supply.
1. Quality of Raw Water. Slow rate gravity
filtration shall be limited to waters having maximum turbidities of 10 units
and maximum color of 15 units; such turbidity shall not be attributable to
colloidal clay. Microscopic examination of the raw water shall be made to
determine the nature and extent of algae growths and their potential adverse
impact on filter operations.
2.
Number. At least two units shall be provided. Where only two units are
provided, each shall be capable of meeting the plant design capacity (normally
the projected maximum daily demand) at the approved filtration rate. Where more
than two filter units are provided, the filters shall be capable of meeting the
plant design capacity at the approved filtration rate with one filter removed
from service.
3. Structural Details
and Hydraulics. Slow rate gravity filters shall be so designed as to provide:
a. headroom to permit normal movement by
operating personnel for scraping and sand removal operations;
b. adequate access hatches and access ports
for handling of sand and for ventilation; and
c. an overflow at the maximum filter water
level.
4. Rates of
Filtration. The permissible rates of filtration shall be determined by the
quality of the raw water and shall be on the basis of experimental data derived
from the water to be treated. The nominal rate may be 45 to 150 gallons per day
per square foot of sand area (1.8 - 6.1 m/day), with somewhat higher rates
acceptable when demonstrated to the satisfaction of the approving
authority.
5. Underdrains. Each
filter unit shall be equipped with a main drain and an adequate number of
lateral underdrains to collect the filtered water. The underdrains shall be
placed as close to the floor as possible and spaced so that the maximum
velocity of the water flow in the underdrain will not exceed 0.75 feet per
second. The maximum spacing of laterals shall not exceed 3 feet if pipe
laterals are used.
6. Filter
material criteria shall be as follows.
a.
Filter sand shall be placed on graded gravel layers for a minimum depth of 30
inches.
b. The effective size shall
be between 0.15 mm and 0.30 mm. Larger sizes may be considered by the state
health officer.
c. The uniformity
coefficient shall not exceed 2.5.
d. The sand shall be cleaned and washed free
from foreign matter.
e. The sand
shall be rebedded when scraping has reduced the bed depth to no less than 19
inches. Where sand is to be reused in order to provide biological seeding and
shortening of the ripening process, rebedding shall utilize a "throw over"
technique whereby new sand is placed on the support gravel and existing sand is
replaced on top of the new sand.
7. Filter Gravel. The supporting gravel
should be similar to the size and depth distribution provided for rapid rate
gravity filters (see §177.A.6.d ii of this Part).
8. Depth of Water on Filter Beds. Design
shall provide a depth of at least three to six feet of water over the sand.
Influent water shall not scour the sand surface.
9. Control Appurtenances. Each filter shall
be equipped with:
a. means of sampling
influent and effluent water;
b. an
indicating loss of head gauge or other means to measure head loss;
c. an indicating rate-of-flow meter. A means
of controlling the rate of filtration and limiting the rate of filtration to a
maximum rate shall be provided;
d.
provisions for filtering to waste with appropriate measures for cross
connection control; and
e. an
effluent pipe designed to maintain the water level above the top of the filter
sand.
10. [Ripening]
Slow sand filters shall be operated to waste after scraping or rebedding during
a ripening period until the filter effluent turbidity falls to consistently
below the regulated drinking water standard established for the
system.
E. Direct
Filtration. Direct filtration, as used herein, refers to the filtration of a
surface water following chemical coagulation and possibly flocculation but
without prior settling. The nature of the treatment process will depend upon
the raw water quality. A full scale direct filtration plant shall not be
constructed without prior pilot studies which are acceptable to the state
health officer. In-plant demonstration studies may be appropriate where
conventional treatment plants are converted to direct filtration. Where direct
filtration is proposed, an engineering report shall be submitted prior to
conducting pilot plant or in-plant demonstration studies.
1. Engineering Report
a. In addition to the items considered in
§113 of this Part, "Engineering Report",
the report shall include a historical summary of meteorological conditions and
of raw water quality with special reference to fluctuations in quality, and
possible sources of contamination. The following raw water parameters shall be
evaluated in the report:
i. color;
ii. turbidity;
iii. bacterial concentration;
iv. microscopic biological
organisms;
v.
temperature;
vi. total solids;
vii. general inorganic chemical
characteristics; and
viii.
additional parameters as required by the state health officer.
b. The report shall also include a
description of methods and work to be done during a pilot plant study or, where
appropriate, an in-plant demonstration study.
2. Pilot Plant Studies. After approval of the
engineering report and pilot plant protocol, a pilot study or in-plant
demonstration study shall be conducted. The study must be conducted over a
sufficient time to treat all expected raw water conditions throughout the year.
The pilot plant filter must be of a similar type and operated in the same
manner as proposed for full scale operation. The pilot study must determine the
contact time necessary for optimum filtration for each coagulant proposed. The
study shall emphasize but not be limited to, the following items:
a. chemical mixing conditions including shear
gradients and detention periods;
b.
chemical feed rates;
c. use of
various coagulants and coagulant aids;
d. flocculation conditions;
e. filtration rates;
f. filter gradation, types of media and depth
of media;
g. filter breakthrough
conditions;
h. adverse impact of
recycling backwash water due to solids, algae, trihalomethane formation and
similar problems;
i. length of
filter runs;
j. length of backwash
cycles;
k. quantities and make-up
of the wastewater. Prior to the initiation of design plans and specifications,
a final report including the engineer's design recommendations shall be
submitted to the state health officer.
3. Pretreatment. The final coagulation and
flocculation basin design should be based on the pilot plant or in-plant
demonstration studies augmented with applicable portions of
§175 D, "Coagulation" and
§175 E, "Flocculation" of this
Part.
4. Filtration. Filters shall
be rapid rate gravity filters with dual or mixed media. The final filter design
shall be based on the pilot plant or in-plant demonstration studies and all
portions of§177 A"Rapid rate gravity filters" of this Part. Pressure filters
or single media sand filters shall not be used.
5. Appurtenances. The following shall be
provided for every filter:
a. influent and
effluent sampling taps;
b. an
indicating loss of head gauge;
c. a
meter indicating instantaneous rate of flow;
d. where used for surface water, provisions
for filtering to waste with appropriate measures for cross connection
control;
e. measures for providing
gradual rate increases when placing the filters back into operation;
and
f. for systems with three or
more filters, on-line turbidimeters shall be installed on the effluent line
from each filter. All turbidimeters shall consistently determine and indicate
the turbidity of the water in NTUs. Each turbidimeter shall report to a
recorder that is designed and operated to allow the operator to accurately
determine the turbidity at least once every 15 minutes. Turbidimeters on
individual filters should be designed to accurately measure low-range
turbidities and have an alarm that will sound when the effluent level exceeds
0.3 NTU.
F.
Deep Bed Rapid Rate Gravity Filters. Deep bed rapid rate gravity filters, as
used herein, generally refers to rapid rate gravity filters with filter
material depths equal to or greater than 48 inches. Filter media sizes are
typically larger than those listed in §177.A.6.d of this Part.
1. Deep bed rapid rate filters may be
considered based on pilot studies pre-approved by the state health
officer.
2. The final filter design
shall be based on the pilot plant studies and shall comply with all applicable
portions of §177.A of this Part. Careful attention shall be paid to the design
of the backwash system which usually includes simultaneous air scour and water
backwash at subfluidization velocities.
G. Biologically Active Filters. Biologically
active filtration, as used herein, refers to the filtration of surface water
(or a ground water with iron, manganese, ammonia or significant natural organic
material) which includes the establishment and maintenance of biological
activity within the filter media.
1.
Objectives of biologically active filtration may include control of
disinfection byproduct precursors, increased disinfectant stability, reduction
of substrates for microbial regrowth, breakdown of small quantities of
synthetic organic chemicals, reduction of ammonia-nitrogen, and oxidation of
iron and manganese. Biological activity can have an adverse impact on
turbidity, particle and microbial pathogen removal, disinfection practices;
head loss development; filter run times and distribution system corrosion.
Design and operation should ensure that aerobic conditions are maintained at
all times. Biologically active filtration often includes the use of ozone as a
pre-oxidant/disinfectant which breaks down natural organic materials into
biodegradable organic matter and granular activated carbon filter media which
may promote denser biofilms.
2.
Biologically active filters may be considered based on pilot studies
pre-approved by the state health officer. The study objectives must be clearly
defined and must ensure the microbial quality of the filtered water under all
anticipated conditions of operation.
a. The
pilot study shall be of sufficient duration to ensure establishment of full
biological activity. The pilot study shall establish empty bed contact time,
biomass loading, and/or other parameters necessary for successful operation as
required by the state health officer.
3. The final filter design shall be based on
the pilot plant studies and shall comply with all applicable portions of §177.A of this Part.
AUTHORITY
NOTE: Promulgated in accordance with the provisions of
R.S.
40:4(A)(8),
40:4.13.D.(1)(2) and
40:5(A)(2)(3)(5)(6)(7)(17).