Section XIII-7921 - Testing Transfer Hoses [49 CFR 193.2621]

Universal Citation: LA Admin Code XIII-7921

Current through Register Vol. 50, No. 9, September 20, 2024

A. Hoses used in LNG or flammable refrigerant transfer systems must be:

1. tested once each calendar year, but with intervals not exceeding 15 months, to the maximum pump pressure or relief valve setting; and [ 49 CFR 193.2621(a)]

2. visually inspected for damage or defects before each use. [ 49 CFR 193.2621(b) ]

AUTHORITY NOTE: Promulgated in accordance with R.S. 30:551.C.

Disclaimer: These regulations may not be the most recent version. Louisiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.