Louisiana Administrative Code
Title 43 - NATURAL RESOURCES
Part XIII - Office of Conservation-Pipeline Safety
Subpart 5 - Liquefied Natural Gas Facilities: Federal Safety Standards
Chapter 79 - Maintenance [49 CFR Part 193 Subpart G]
Section XIII-7915 - Isolating and Purging [49 CFR 193.2615]

Universal Citation: LA Admin Code XIII-7915

Current through Register Vol. 50, No. 9, September 20, 2024

A. Before personnel begin maintenance activities on components handling flammable fluids which are isolated for maintenance, the component must be purged in accordance with a procedure which meets the requirements of "Purging Principles and Practices (incorporated by reference, see LAC 43:XIII.6713)"; unless the maintenance procedures under LAC 43:XIII.7905 provide that the activity can be safely performed without purging. [ 49 CFR 193.2615(a)]

B. If the component or maintenance activity provides an ignition source, a technique in addition to isolation valves (such as removing spool pieces or valves and blank flanging the piping, or double block and bleed valving) must be used to ensure that the work area is free of flammable fluids. [ 49 CFR 193.2615(b)]

AUTHORITY NOTE: Promulgated in accordance with R.S. 30:551.C.

Disclaimer: These regulations may not be the most recent version. Louisiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.
This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.