Louisiana Administrative Code
Title 43 - NATURAL RESOURCES
Part XIII - Office of Conservation-Pipeline Safety
Subpart 5 - Liquefied Natural Gas Facilities: Federal Safety Standards
Chapter 79 - Maintenance [49 CFR Part 193 Subpart G]
Section XIII-7903 - General [49 CFR 193.2603]
Current through Register Vol. 50, No. 9, September 20, 2024
A. Each component in service, including its support system, must be maintained in a condition that is compatible with its operational or safety purpose by repair, replacement, or other means. [ 49 CFR 193.2603(a)]
B. An operator may not place, return, or continue in service any component which is not maintained in accordance with this subpart. [ 49 CFR 193.2603(b)]
C. Each component taken out of service must be identified in the records kept under §193.2639 [ 49 CFR 193.2603(c)]
D. If a safety device is taken out of service for maintenance, the component being served by the device must be taken out of service unless the same safety function is provided by an alternate means. [ 49 CFR 193.2603(d)]
E. If the inadvertent operation of a component taken out of service could cause a hazardous condition, that component must have a tag attached to the controls bearing the words "do not operate" or words of comparable meaning. [ 49 CFR 193.2603(e)]
AUTHORITY NOTE: Promulgated in accordance with R.S. 30:551.C.