A. Each impounding system serving an LNG storage tank must have a minimum volumetric liquid impoundment capacity of:
1. 110 percent of the LNG tank's maximum
liquid capacity for an impoundment serving a single tank; [
49 CFR
193.2181(a)]
2. 100 percent of all tanks or 110 percent of
the largest tank's maximum liquid capacity, whichever is greater, for the
impoundment serving more than one tank; or [
49 CFR
193.2181(b)]
3. if the dike is designed to account for a
surge in the event of catastrophic failure, then the impoundment capacity may
be reduced to 100 percent in lieu of 110 percent. [
49 CFR
193.2181(b)
]
AUTHORITY NOTE: Promulgated in accordance with R.S. 30:551.C.
Disclaimer: These regulations may not be the most recent version. Louisiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.