Section XIII-7173 - Water Removal [193.2173]

Universal Citation: LA Admin Code XIII-7173

Current through Register Vol. 50, No. 9, September 20, 2024

A. Impoundment areas must be constructed such that all areas drain completely to prevent water collection. Drainage pumps and piping must be provided to remove water from collecting in the impoundment area. Alternative means of draining may be acceptable subject to the commissioner's approval. [ 49 CFR 193.2173(a)]

B. The water removal system must have adequate capacity to remove water at a rate equal to 25 percent of the maximum predictable collection rate from a storm of 10-year frequency and 1-hour duration, and other natural causes. For rainfall amounts, operators must use the "Rainfall Frequency Atlas of the United States" published by the National Weather Service of the U.S. Department of Commerce. [ 49 CFR 193.2173(b)]

C. Sump pumps for water removal must:

1. be operated as necessary to keep the impounding space as dry as practical; and [ 49 CFR 193.2173(c)(1) ]

2. if sump pumps are designed for automatic operation, have redundant automatic shutdown controls to prevent operation when LNG is present. [ 49 CFR 193.2173(c)(2) ]

AUTHORITY NOTE: Promulgated in accordance with R.S. 30:551.C.

Disclaimer: These regulations may not be the most recent version. Louisiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.