Louisiana Administrative Code
Title 43 - NATURAL RESOURCES
Part XIII - Office of Conservation-Pipeline Safety
Subpart 5 - Liquefied Natural Gas Facilities: Federal Safety Standards
Chapter 71 - Design [49 CFR Part 193 Subpart C]
Section XIII-7101 - Scope [49 CFR 193.2101]
Current through Register Vol. 50, No. 9, September 20, 2024
A. Each LNG facility designed after March 31, 2000 must comply with the requirements of this part and of NFPA-59A-2001 (incorporated by reference, see LAC 43:XIII.6713). If there is a conflict between this Part and NFPA-59A-2001, the requirements in this part prevail. [ 49 CFR 193.2101(a)]
B. Each stationary LNG storage tank must comply with Section 7.2 of NFPA-59A-2006 (incorporated by reference, see LAC 43:XIII.6713) for seismic design of field fabricated tanks. All other LNG storage tanks must comply with API Std-620 (incorporated by reference, see LAC 43:XIII.6713) for seismic design. [ 49 CFR 193.2101(b)]
AUTHORITY NOTE: Promulgated in accordance with R.S. 30:551.C.