Louisiana Administrative Code
Title 43 - NATURAL RESOURCES
Part XI - Office of Conservation-Pipeline Division
Subpart 5 - Compressed Natural Gas
Chapter 55 - Design
Section XI-5515 - Hose and Hose Connections (Formerly section 2533)

Universal Citation: LA Admin Code XI-5515

Current through Register Vol. 50, No. 9, September 20, 2024

A. Hose and metallic hose shall be of or lined with materials that are resistant to corrosion and the actions of compressed natural gas (CNG).

B. Hose, metallic hose, flexible metal hose, tubing, and their connections shall be suitable for the most severe pressure and temperature conditions expected under normal operating conditions with a burst pressure of at least four times the maximum working pressure.

C. Hose assemblies shall be tested by the manufacturer or its designated representative prior to use at pressures equal to not less than twice the service pressure.

D. Hose shall be continuously and distinctly marked, indicating the manufacturer's name or trademark, CNG service, and working pressure. Metallic hose shall have a manufacturer's permanently attached tag marked with the manufacturer's name or trademark, CNG service, and working pressure.

AUTHORITY NOTE: Promulgated in accordance with R.S. 30:751 and 752.

Disclaimer: These regulations may not be the most recent version. Louisiana may have more current or accurate information. We make no warranties or guarantees about the accuracy, completeness, or adequacy of the information contained on this site or the information linked to on the state site. Please check official sources.